Emerson Rosemount 702 Скачать руководство пользователя страница 1

Reference Manual

00809-0200-4702, Rev DA

July 2017

Rosemount

 702 Wireless Discrete Transmitter

Содержание Rosemount 702

Страница 1: ...Reference Manual 00809 0200 4702 Rev DA July 2017 Rosemount 702 Wireless Discrete Transmitter ...

Страница 2: ......

Страница 3: ...ation and position 4 1 3 4 Electrical 5 1 3 5 Verifying operating atmosphere 5 1 4 Product recycling disposal 6 2Section 2 Configuration Models 702DX22 and 702DX61 2 1 Safety messages 7 2 1 1 Connecting the switches 7 2 2 Configuring the Device Sensor 8 2 3 Configuring on the bench 8 2 4 Configuring the device network 9 2 4 1 Configuring transmitter with dry contact inputs measurement option code ...

Страница 4: ...702DX61 4 1 Safety messages 27 4 2 Configuring the transmitter to communicate with the wireless network 28 4 3 AMS Wireless Configurator 28 4 4 Field Communicator 28 4 5 Verifying operation 29 4 5 1 AMS Wireless Configurator 31 5Section 5 Operation and Maintenance Models 702DX22 and 702DX61 5 1 Safety Messages 33 5 2 Discrete input from switches and sensors 34 5 2 1 Dry contact inputs measurement ...

Страница 5: ...iring Switches and Output Circuits Models 702DX32 and 702DX42 7 1 Safety messages 59 7 2 Installing the transmitter 60 7 2 1 Direct mount 60 7 2 2 Remote mount 62 7 3 Wiring switches and sensors 63 7 3 1 Dry contact inputs measurement option code 32 42 702DX32 702DX42 63 7 3 2 Dry contact switch inputs 63 7 3 3 Output circuits measurement option code 42 702DX42 65 7 3 4 Safety shower and eye wash ...

Страница 6: ...ce diagnostic screens 95 9 6 Replacing the power module 97 9 7 Service support 98 AAppendix A Specifications and Reference Data A 1 Functional specifications 99 A 1 1 Discrete input 99 A 1 2 Switching threshold model 702DX22 99 A 1 3 Switching threshold models 702DX32 702DX42 99 A 1 4 Momentary discrete input models 702DX32 702DX42 99 A 1 5 Discrete output model 702DX42 99 A 1 6 Wireless output 99...

Страница 7: ...s 105 B 5 Installing in North America 105 B 6 USA 105 B 7 Canada 106 B 8 Europe 106 B 9 International 107 B 10 China 107 B 11 Japan 108 B 12 EAC Belarus Kazakhstan Russia 108 B 13 Installation Drawings 109 CAppendix C High Gain Remote Antenna Option C 1 Safety messages 115 C 2 Functional specifications 116 C 3 Installation considerations 117 C 4 Transient lightning considerations 117 C 5 Dimension...

Страница 8: ...viii Reference Manual 00809 0200 4702 Rev DA Contents July 2017 Contents ...

Страница 9: ...ire nuclear qualified hardware or products may cause inaccurate readings For information on Rosemount nuclear qualified products contact an Emerson Sales Representative Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Review the ap...

Страница 10: ...of Dangerous Goods It is the responsibility of the shipper to ensure compliance with these or any other local requirements Consult current regulations and requirements before shipping The power module with the wireless unit contains two C size primary lithium thionyl chloride batteries Each battery contains approximately 2 5 grams of lithium for a total of 5 grams in each pack Under normal conditi...

Страница 11: ...nsmitter Section 4 Commissioning Models 702DX22 and 702DX61 contains information for the commissioning of the Rosemount 702 Transmitter onto the wireless network and how to verify that the transmitter has successfully joined Section 5 Operation and Maintenance Models 702DX22 and 702DX61 provides detailed information on operation of the Rosemount 702 Transmitter with various switch and sensor confi...

Страница 12: ...ic safety installation drawings Appendix C High Gain Remote Antenna Option describes the high gain remote antenna its specifications and installation 1 2 Models covered The following Rosemount 702 Transmitters are covered by this manual 1 2 1 Rosemount 702DX22 Wireless Discrete Transmitter Two input channels Discrete input only 1 2 2 Rosemount 702DX61 Wireless Discrete Transmitter for liquid hydro...

Страница 13: ...configuration the transmitter converts the switch signal to a wireless enabled signal 1 3 2 Wireless considerations Power up sequence The Emerson Wireless Gateway should be installed and functioning properly before any wireless field devices are powered Install the Black Power Module SmartPower Solutions model number 701PBKKF part number 00753 9220 0001 into the Rosemount 702 Transmitter to power ...

Страница 14: ...eld Communicator to the power module The power module needs to be connected for the Field Communicator to interface with the transmitter Figure 1 3 Field Communicator Connections 1 3 3 Choosing an installation location and position When choosing an installation location and position take into account access to the Rosemount 702 Transmitter For best performance the antenna should be vertical with s...

Страница 15: ...ure to provide adequate clearance for cover removal 1 3 5 Verifying operating atmosphere Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations certifications Isolating the transmitter from sources of heat The transmitter will operate within specifications for ambient temperatures between 40 and 185 F 40 and 85 C Heat from the process is tran...

Страница 16: ...to 131 F 85 to 55 C or 86 F 30 C In this case an extension of 5 in 0 13 m meets t his requirement but 6 in 0 15 m provides an additional margin of protection thereby reducing risk of ambient thermal damage Temperature limits 1 4 Product recycling disposal Recycling of equipment and packaging should be taken into consideration The product and packaging should be disposed of in accordance with local...

Страница 17: ...ions to the switch terminals on the transmitter To ensure a proper switch connection anchor the switch lead wires into the appropriate compression terminals and tighten the screws Wiring the transmitter If the switch is installed in a high voltage environment and a fault condition or installation error occurs the sensor leads and transmitter terminals could carry lethal voltage Use extreme caution...

Страница 18: ...cator or AMS Wireless Configurator 2 3 Configuring on the bench Field Communicator When using a Field Communicator any configuration changes must be sent to the transmitter using the Send key F2 AMS Wireless Configurator configuration changes are implemented when the Apply button is clicked AMS Wireless Configurator AMS Wireless Configurator is capable of connecting to devices directly using a HAR...

Страница 19: ...gured by entering the Fast Key Sequence 2 2 1 1 The Join Key can also be configured using a Field Communicator with the Fast Key Sequence 2 2 1 2 AMS Wireless Configurator The final device network configuration piece is the Update Rate which by default is 1 minute It can be changed at commissioning or at any time by using AMS Wireless Configurator or the Gateway s web server The Update Rate should...

Страница 20: ...id hydrocarbon detection measurement option code 61 702DX61 Making terminal block connections Figure 2 2 Fuel Sensor Terminal Diagram Connect Tyco TraceTek and Fast Fuel sensor lead wires by matching the colors of wires to colors on terminal block Figure 2 3 Field Communicator Connections For HART Communication a Rosemount 702 DD is required COMM P N 00753 9200 0020 1 2 3 4 ...

Страница 21: ...ber of Available Neighbors 5 Number of Advertisements Heard 6 Number of Join Attempts 1 Sensor Calibration 2 Other 1 Discrete 1 2 Discrete 2 3 Ambient Temperature 4 Supply Voltage 1 Clear Alert History 1 Discrete Input 1 Sensor Wiring Offset 2 Discrete Input 2 Sensor Wiring Offset 1 Perform Master Reset 2 Measurement History 3 Advertise to New Devices 4 Install New Power Module 1 Network ID 2 Join...

Страница 22: ...s 3 Join Mode 4 Number of Available Neighbors 5 Number of Advertisements Heard 6 Number of Join Attempts 1 Other 1 Input 2 Electronics Temperature 3 Supply Voltage 1 Perform Master Reset 2 Measurement History 3 Advertise to New Devices 4 Install New Power Module 1 Network ID 2 Join Device to Network 3 Broadcast Rates 1 Configure Sensor 2 Sensor State 3 Sensor Status 4 Sensor Serial Number 1 Electr...

Страница 23: ... device is ready for commissioning Table 2 1 Rosemount 702 Fast Key sequence Function Key sequence Menu items Device Information 2 2 4 Manufacturer Model Final Assembly Number Universal Field Device Software Hardware Descriptor Message Date Model Number I II III SI Unit Restriction Country Guided Setup 2 1 Join Device to Network Configure Update Rate Configure Sensor Calibrate Sensor Configure Dis...

Страница 24: ...14 Reference Manual 00809 0200 4702 Rev DA Configuration Models 702DX22 and 702DX61 July 2017 Configuration Models 702DX22 and 702DX61 ...

Страница 25: ...ed personnel should perform the installation Explosions could result in death or serious injury Before connecting a Field Communicator in an explosive atmosphere make sure that the instruments are installed in accordance with intrinsically safe or non incendive field wiring practices Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous locations cert...

Страница 26: ...onfiguration on page 18 Use Remote mount instructions for the installation of liquid hydrocarbon sensors 3 2 1 Direct mount configuration 1 Install the switch according to standard installation practices making sure to use thread sealant on all of the connections 2 Attach the Rosemount 702 Transmitter housing to the switch by using the pipe fittings threaded into the conduit entries Note Direct mo...

Страница 27: ...gure 3 2 Power Module Installation 5 Close the housing cover and tighten to safety specifications Always ensure a proper seal by installing the electronic housing covers so that metal touches metal but do not over tighten 6 Position the antenna such that it is vertical either straight up or straight down as shown in Figure 3 3 The antenna should be approximately 3 ft 1 m from any large structures ...

Страница 28: ...Figure 3 2 on page 17 Figure 3 4 Remote Mount A Float switch B Rosemount 702 Transmitter Note Use caution when handling the power module it may be damaged if dropped from heights in excess of 20 ft Note Wireless devices should only be powered up after the Emerson Wireless Gateway in order of proximity from the Gateway beginning with the closest device This results in a simpler and faster network i...

Страница 29: ...agram 3 3 2 Wireless output specifications Dual input The Rosemount 702 Transmitter will accept the input from one or two single pole single throw switches on inputs S1 and S2 The wireless output of the transmitter will be both a primary variable PV and a secondary variable SV The PV is determined by the S1 input The SV is determined by the S2 input A closed switch drives a TRUE output An open swi...

Страница 30: ...determination of the wireless outputs Reference Figure 3 7 for details on the wireless outputs available when using limit contact logic Figure 3 7 Dual Input Limit Contacts Dual input opposing contact logic When configured for opposing contact logic the Rosemount 702 Transmitter will accept the input from a single pole double throw switch on inputs S1 and S2 and will use opposing contact logic for...

Страница 31: ...able The connections to the Fast Fuel Sensor TraceTek Sensing cable are made by matching the appropriately colored wires to the matching colored termination lugs The Rosemount 702 Transmitter can support up to three Tyco Fast Fuel Sensors These sensors are connected using TraceTek Modular Leader Cable TT MLC MC BLK optional modular jumper cables TT MJC xx MC BLK and branching connectors TT ZBC MC ...

Страница 32: ...l jumper cable D TT ZBC xx MC BLK branch connector Note All part numbers on this page refer to products sold by Tyco Thermo Controls LLC The Rosemount 702 Transmitter can support up to 500 ft 150 m of TraceTek hydrocarbon or solvent sensor cable TT5000 or TT5001 series The total amount of sensor cable connected to a single transmitter is not to exceed 500 ft However leader cable jumper cables if u...

Страница 33: ...000 or TT5001 sensor cable total per transmitter F TT ZBC xx MC BLK branch connector 3 4 LCD display If an LCD display is ordered it will be shipped attached to the transmitter Note An LCD display is not available with measurement option code 61 for liquid hydrocarbon detection The optional LCD display can be rotated in 90 degree increments by squeezing the two tabs pulling out rotating and snappi...

Страница 34: ...osemount Wireless LCD part number 00753 9004 0002 Figure 3 13 Optional LCD Display A LCD pins B LCD display C LCD cover 3 5 Grounding the transmitter The Rosemount 702 Transmitter operates with the housing grounded or floating Floating systems however can cause extra noise that may affect many types of readout devices If the signal appears noisy or erratic grounding at a single point may solve the...

Страница 35: ...ter housing 2 Ensure that the transmitter housing is electrically isolated from the switch wiring A Float switch B Shield ground point C Rosemount 702 Transmitter Option 2 1 Ground switch wiring shield at the switch 2 Ensure that the switch wiring and shield are electronically isolated from the transmitter housing A Float switch B Shield ground point C Rosemount 702 Transmitter Note Always use fac...

Страница 36: ...26 Reference Manual 00809 0200 4702 Rev DA Mounting Wiring Switches and Sensors Models 702DX22 and 702DX61 July 2017 Mounting Wiring Switches and Sensors Models 702DX22 and 702DX61 ...

Страница 37: ...way has been installed and is functioning properly Wireless devices should be powered up in order of proximity from the gateway beginning with the device closest to the Emerson Wireless Gateway This will result in a simpler and faster network installation Failure to follow these installation guidelines could result in death or serious injury Make sure only qualified personnel perform the installat...

Страница 38: ...he gateway and other devices in the network If the Network ID and Join Key are not identical the Rosemount 702 Transmitter will not communicate with the network The Network ID and Join Key may be obtained from the Emerson Wireless Gateway on the Setup Network Settings page on the web server shown in Figure 4 1 Figure 4 1 Gateway Network Settings 4 3 AMS Wireless Configurator Right click on the Ros...

Страница 39: ... and Join Key of the Gateway Operating the local display The LCD displays the PV and SV values at the configured update rate but no faster than once every 60 seconds Diagnostic button display sequence More detailed diagnostic information can be obtained by removing the display cover of the Rosemount 702 Transmitter and momentarily depressing the DIAG button The LCD will display the diagnostic scre...

Страница 40: ...evices being joined and the number of devices in the current network For one device joining an existing network with multiple devices it may take up to five minutes It may take up to 60 minutes for multiple new devices to join the existing network Alarm configuration if the device joins the network and immediately has an alarm present it is likely due to sensor configuration Check the sensor wirin...

Страница 41: ...ter power up verify the correct configuration of the Network ID and Join Key and verify that Active Advertising has been enabled on the Gateway The Network ID and Join Key in the device must match the Network ID and Join Key of the Gateway The Network ID and Join Key may be obtained from the Gateway on the Setup Network Settings page on the web interface see Figure 4 4 on page 31 The Network ID an...

Страница 42: ...32 Reference Manual 00809 0200 4702 Rev DA Commissioning Models 702DX22 and 702DX61 July 2017 Operation and Maintenance ...

Страница 43: ...ng safety messages before performing an operation preceded by this symbol Failure to follow these installation guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Explosions could result in death or serious injury Before connecting a Field Communicator in an explosive atmosphere make sure the instruments are installed in accordance with in...

Страница 44: ...he input from one or two single pole single throw switches on inputs S1 and S2 The wireless output of the transmitter will be both a primary variable PV and a secondary variable SV The PV is determined by the S1 input The SV is determined by the S2 input A closed switch drives a TRUE output An Open switch drives a FALSE output Note Any dry contact input can be inverted by the device so as to give ...

Страница 45: ...Figure 5 3 Dual Input Limit Contacts Dual input opposing contact logic When configured for Opposing Contact Logic the Rosemount 702 Transmitter will accept the input from a single pole double throw switch on inputs S1 and S2 and will use opposing contact logic for the determination of the wireless outputs The following tables describe the wireless outputs available when using opposing contact logi...

Страница 46: ...uid hydrocarbon detection measurement option code 61 702DX61 Figure 5 5 Fuel Sensor Terminal The Liquid Hydrocarbon Detection configuration is intended for use with the Tyco TraceTek Fast Fuel Sensor or TraceTek Sensing cable Switch inputs Wireless outputs S1 S2 PV SV Open Open FAULT NaN FAULT NaN Open Closed FALSE 0 0 FALSE 0 0 Closed Open TRUE 1 0 TRUE 1 0 Closed Closed FAULT NaN FAULT NaN S1 CM...

Страница 47: ...atching colored termination lugs The Rosemount 702 Transmitter can support up to three Fast Fuel Sensors These sensors are connected using TraceTek Modular Leader Cable TT MLC MC BLK optional modular jumper cables TT MJC xx MC BLK and branching connectors TT ZBC MC BLK as suggested in Figure 3 11 on page 22 Using the AMS Device Manager with the liquid hydrocarbon detection option The following fig...

Страница 48: ...d 702DX61 Figure 5 8 Leak Status Figure 5 9 Leak Sensor Not Connected Status Table 5 1 Liquid Hydrocarbon Detection Interface for Modbus mapping PV SV Description interpretation 1 0 1 0 Normal condition no leak detected sensor status good 0 0 1 0 or 0 0 Leak detected sensor status good 1 0 0 0 Sensor Not Connected Assume Leak take appropriate action ...

Страница 49: ...e of PV_HEALTHY means that the device is either off of the network the data updates are not current or that there is a malfunction of the device such as an electronics failure In the case of a False state of PV_HEALTHY it is recommended to assume that the device is not connected to the network and to take appropriate action Mapping the PV SV and PV_HEALTHY Variables and Parameter Below is a shot o...

Страница 50: ...sequence The following screens will display when the power module is first connected to the Rosemount 702 Transmitter 1 All Segments On used to visually determine if there are any bad segments on the LCD 2 Device Identification used to determine Device Type 3 Device Information Tag user entered tag which is eight characters long will not display if all characters are blank 4 PV Screen Discrete inp...

Страница 51: ...ls 702DX22 and 702DX61 5 SV Screen Discrete input 2 6 TV Screen feature board temperature value 7 QV Screen voltage reading at the power module terminals 8 Alert Screen at least one alert is present this screen will not display if no alerts are present S N S R 2 True D E V 2 5 2 5 d e g c S u p l y 7 2 1 v o l t s a l e r t p r e s n t ...

Страница 52: ...ag user entered tag which is eight characters long will not display if all characters are blank 2 Device Identification used to determine Device ID 3 Network ID assuming the device has the correct join key this ID tells the user what network the device can connect with 4 Network Connection Status the device has joined a network and has been fully configured and has multiple parents 5 Supply Voltag...

Страница 53: ...on screen sequence 1 Diagnostic Button Screen 4 1 the device is attempting to start the radio 2 Diagnostic Button Screen 4 2 the device has just restarted 3 Diagnostic Button Screen 4 3 the device is starting to join the process 4 Diagnostic Button Screen 4 4 the device is in a disconnected state and requires a Force Join command to join the network 5 Diagnostic Button Screen 4 5 the device is sea...

Страница 54: ...work 7 Diagnostic Button Screen 4 7 the device is connected to the Network but is in a Quarantined state 8 Diagnostic Button Screen 4 8 the device is joined and operational but is running with limited bandwidth for sending periodic data 9 Diagnostic Button Screen 4 9 the device has joined a network and has been fully configured and has multiple parents n e t w k N E G O T n e t w k c o n e c t n e...

Страница 55: ...e device and will appear after screen 5 of the Diagnostic Button Screen Sequence 1 Device Information Status there is a critical error which may prevent the device from operating correctly Check additional status screens for more information 2 PV Screen Discrete input 1 or logic output value depending on how the device is configured 3 SV Screen Discrete input 2 4 TV Screen feature board temperatur...

Страница 56: ...er entered tag which is eight characters long will not display if all characters are blank 8 Diagnostic Button Screen 2 the device s identifier that is used to make up the HART long address the Rosemount 1420 Wireless Gateway may use this to help identify devices if no unique user tag is available 9 Diagnostic Button Screen 7 1 the terminal voltage has dropped below level of operating limit Replac...

Страница 57: ...on of the transmitter is invalid such that critical operation of the device may be affected check the extended configuration status to identify which configuration item s need to be corrected 13 Diagnostic Button Screen 9 2 configuration of the transmitter is invalid such that non critical operation of the device may be affected check the extended configuration status to identify which configurati...

Страница 58: ... electrical or mechanical damage Contacts should be protected to prevent premature discharge Use caution when handling the power module it may be damaged if dropped from heights in excess of 20 ft Battery hazards remain when cells are discharged Environmental considerations As with any battery local environmental rules and regulations should be consulted for proper management of spent batteries If...

Страница 59: ... assist you with any needed information or materials The center will ask for product model and serial numbers and will provide a Return Material Authorization RMA number The center will also ask for the process material to which the product was last exposed Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard If the pro...

Страница 60: ...50 Reference Manual 00809 0200 4702 Rev DA Operation and Maintenance Models 702DX22 and 702DX61 July 2017 Operation and Maintenance Models 702DX22 and 702DX61 ...

Страница 61: ... performing an operation preceded by this symbol Failure to follow these installation guidelines could result in death or serious injury Only qualified personnel should perform the installation Explosions could result in death or serious injury Before connecting a Field Communicator in an explosive atmosphere make sure that the instruments are installed in accordance with intrinsically safe or non...

Страница 62: ...ng the LCD display 5 Replace the cover and tighten if applicable 6 2 Discrete channel configuration Remove the power module side housing cover to expose the terminal block and HART communication terminals then connect the power module to power the unit for configuration The Rosemount 702 Transmitter will receive any HART Communication from a Field Communicator or AMS Wireless Configurator When usi...

Страница 63: ...with the Fast Key Sequence 2 2 1 2 Changing the update rate with a Field Communicator The final device network configuration piece is the update rate which by default is 1 minute It can be changed at commissioning or at any time by using AMS Wireless Configurator or the Emerson Wireless Gateway s web server The Update Rate should be between one second and 60 minutes To change the update rate with ...

Страница 64: ...4702 Rev DA Configuration Models 702DX32 and 702DX42 July 2017 Configuration Models 702DX32 and 702DX42 Figure 6 2 Field Communicator Connections For HART communication a Rosemount 702 DD is required COMM P N 00753 9200 0020 1 2 3 4 ...

Страница 65: ... Message 9 Model Number I 10 Model Number II 11 Model Number III Device Status 1 Active Alerts Active Alerts 1 Good only if no alerts 2 Failed Fix Now 3 Advisory 4 Maintenance Fix Soon Good only if no alerts 1 No Active Alerts Failed Fix Now 1 Electronics Failure 2 Input Output Failure 3 Radio Failure 4 Supply Voltage Failure Maintenance Fix Soon 1 Sensor Degraded 2 Terminal Temperature Out of Ran...

Страница 66: ...annel 2 Status 6 Setup Channel 1 7 Setup Channel 2 Setup Channel 1 1 Channel 1 Direction 2 Channel 1 Status 3 Channel 1 Count 4 Logic Option 5 Count Rollover Value 6 Reported Value 7 Fault State Option 8 Fault State Value 9 Fault State Time Setup Channel 2 1 Channel 2 Direction 2 Channel 2 Status 3 Channel 2 Count 4 Logic Option 5 Count Rollover Value 6 Reported Value 7 Fault State Option 8 Fault ...

Страница 67: ...Supply Voltage Status Communication 1 Join Status 2 Communication Status 3 Join Mode 4 Available Neighbors 5 Advertisements 6 Join Attempts Maintenance 1 Routine Maintenance 2 Manual Override 3 Reset Restore Simulate 1 Channel Input 2 Electronics Temperature 3 Supply Voltage Advisory 1 Electronics Warning 2 Electronics Temperature has Exceeded Limits 3 Module Temperature has Exceeded Limits 4 Supp...

Страница 68: ...ly when the device is ready for commissioning Table 6 1 Fast Key Sequence Function Key Sequence Menu Items Device Information 1 15 Manufacturer Model Final Assembly Number Universal Field Device Software Hardware Descriptor Message Date Model Number I II III SI Unit Restriction Country Guided Setup 2 1 Join Device to Network Configure Update Rate Configure Sensor Calibrate Sensor Configure Display...

Страница 69: ...Only qualified personnel should perform the installation Explosions could result in death or serious injury Before connecting a Field Communicator in an explosive atmosphere make sure that the instruments are installed in accordance with intrinsically safe or non incendive field wiring practices Verify that the operating atmosphere of the transmitter is consistent with the appropriate hazardous lo...

Страница 70: ...structions see Remote mount on page 62 Use Remote mount instructions for the installation of liquid hydrocarbon sensors 7 2 1 Direct mount 1 Install the switch according to standard installation practices making sure to use thread sealant on all of the connections 2 Attach the Rosemount 702 Transmitter housing to the switch by using the pipe fittings threaded into the conduit entries Note Direct m...

Страница 71: ...lts in a simpler and faster network installation Figure 7 2 Power Module Installation 5 Close the housing cover and tighten to safety specifications Always ensure a proper seal by installing the electronic housing covers so that metal touches metal but do not over tighten 6 The antenna should be positioned vertically typically straight up but the antenna may also be pointed straight down as shown ...

Страница 72: ... the transmitter connect the Black Power Module as shown in Figure 7 2 on page 61 Figure 7 4 Remote Mount A Float switch B Rosemount 702 Transmitter Note Use caution when handling the power module it may be damaged if dropped from heights in excess of 20 ft Note Wireless devices should only be powered up after the Gateway in order of proximity from the Gateway beginning with the closest device Thi...

Страница 73: ...am 7 3 2 Dry contact switch inputs Dual input The Rosemount 702 Transmitter will accept the input from one or two single pole single throw switches on inputs CH1 and CH2 The wireless output of the transmitter will be both a primary variable PV and a secondary variable SV The PV is determined by the CH1 input The SV is determined by the CH2 input A closed switch drives a TRUE output An Open switch ...

Страница 74: ... will use limit contact logic for the determination of the wireless outputs Reference Figure 9 3 on page 81 for details on the wireless outputs available when using limit contact logic Figure 7 7 Dual Input Limit Contacts Dual input opposing contact logic When configured for Opposing Contact Logic the 702 Transmitter will accept the input from a single pole double throw switch on inputs CH1 and CH...

Страница 75: ...not provide any voltage or current the output circuit must have power of its own The transmitter output has maximum switch capacity per channel of 26 volts DC and 100 milliamps A typical power supply for powering an output circuit can be 24 volts or lower Note It is very important that the polarity of the output circuit is as shown in the wiring diagrams with the positive side of the circuit wired...

Страница 76: ...o output circuits it is very important that the CMN terminal of each circuit be at the same voltage Employing a common ground for both output circuits is one way to ensure that both circuits have CMN terminals at the same voltage Figure 7 11 Dual Output Circuits with Common Ground If two output circuits are connected to a single Rosemount 702 Transmitter with a single power supply both CH and CMN ...

Страница 77: ...rrents or Voltages 7 3 4 Safety shower and eye wash monitoring The Rosemount 702 Transmitter can be used to monitor safety showers and eye wash stations by using switch kits provided by TopWorx an Emerson company These kits are ordered as a part of the transmitter model code and are available for both insulated and un insulated pipes These kits contain the switches brackets and cables that are nec...

Страница 78: ...and the Rosemount 702 Transmitter senses that switch closure This switch state is then transmitted by the transmitter to the Gateway which then sends that information to the control host or alert system When the shower valve is closed the switch remains in the activated state until it is reset by a technician The switch can be re set only by placing a ferrous metal object on the far side of the se...

Страница 79: ...orx switch is activated closed switch and the Rosemount 702 Transmitter senses that switch closure This switch state is then transmitted by the transmitter to the Gateway which then sends that information to the control host or alert system When the eye wash valve is closed the switch remains in the activated state until it is reset by a technician The switch can be re set only by placing a ferrou...

Страница 80: ...ping back into place If the LCD display pins are inadvertently removed from the interface board carefully re insert the pins before snapping the LCD display back into place Installing the optional LCD display To install the LCD display use Figure 7 19 on page 70 and the following instructions 1 Remove the LCD display cover Do not remove the instrument cover in explosive environments when the circu...

Страница 81: ... with local and national installation codes Grounding is accomplished through the process connection using the internal or external case grounding terminal Determining grounding requirements Each process installation has different grounding requirements Use the options recommended by the facility for the specific switch type or begin with Option 1 which is the most common Option 1 1 Connect switch...

Страница 82: ...72 Reference Manual 00809 0200 4702 Rev DA Mounting Wiring Switches and Output Circuits Models 702DX32 and 702DX42 July 2017 Mounting Wiring Switches and Output Circuits Models 702DX32 and 702DX42 ...

Страница 83: ...functioning properly Wireless devices should be powered up in order of proximity from the gateway beginning with the device closest to the Gateway This will result in a simpler and faster network installation Failure to follow these installation guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Explosions could result in death or serious...

Страница 84: ...Join Key may be obtained from the Emerson Wireless Gateway on the Setup Network Settings page on the web server shown in Figure 8 1 Figure 8 1 Gateway Network Settings AMS Wireless Configurator Right click on the Rosemount 702Transmitter and select Configure When the menu opens select Join Device to Network and follow the method to enter the Network ID and Join Key Field Communicator The Network I...

Страница 85: ...ess When the status bar is filled the device is successfully connected to the wireless network Start up Display Sequence When the Rosemount 702 Transmitter is first powered up the LCD display will display a sequence of screens All Segments On Device Identification Device Tag and then the user chosen variables of the Periodic Display Diagnostic button display sequence More detailed diagnostic infor...

Страница 86: ...and the number of devices in the current network For one device joining an existing network with multiple devices it may take up to five minutes It may take up to 60 minutes for multiple new devices to join the existing network Alarm configuration If the device joins the network and immediately has an alarm present it is likely due to sensor configuration Check the sensor wiring see Terminal Block...

Страница 87: ...nfigurator When the device has joined the network it will appear in the Device Manager as illustrated below Troubleshooting If the device is not joined to the network after power up verify the correct configuration of the Network ID and Join Key and verify that Active Advertising has been enabled on the Gateway The Network ID and Join Key in the device must match the Network ID and Join Key of the...

Страница 88: ...he network ID and join key The Network ID and Join Key may be obtained from the Gateway on the Setup Network Settings page on the web interface see Figure 8 5 on page 77 The Network ID and Join Key may be changed in the wireless device by using the following Fast Key sequence Function Key Sequence Menu Items Wireless 2 1 1 Join Device to Network ...

Страница 89: ...following safety messages before performing an operation preceded by this symbol Failure to follow these installation guidelines could result in death or serious injury Make sure only qualified personnel perform the installation Explosions could result in death or serious injury Before connecting a Field Communicator in an explosive atmosphere make sure the instruments are installed in accordance ...

Страница 90: ... specifications Dual Input The Rosemount 702 Transmitter will accept the input from one or two single pole single throw switches on inputs CH1 and CH2 The wireless output of the transmitter will be both a primary variable PV and a secondary variable SV The PV is determined by the CH1 input The SV is determined by the CH2 input A closed switch drives a TRUE output An Open switch drives a FALSE outp...

Страница 91: ...ount 702 Transmitter will accept the input from two single pole single throw switches on inputs CH1 and CH2 and will use limit contact logic for the determination of the wireless outputs The following tables describe the wireless outputs available when using limit contact logic Figure 9 3 Dual Input Limit Contacts Single input Dual input Switch Input Wireless output Switch input Wireless output CH...

Страница 92: ...pposing Contact 9 2 3 Momentary discrete inputs measurement option code 32 and 42 702DX32 702DX42 The Rosemount 702 Transmitter is capable of measuring momentary discrete inputs of 10 millisecond or more in duration regardless of the wireless update rate At each wireless update the device reports current discrete input state and an accumulating count of close open cycles for each input channel Swi...

Страница 93: ... Classic variable reporting mode the transmitter will report variables exactly like the previous version of the device measurement option code 22 In the Enhanced variable reporting mode the transmitter will provide both current state of the discrete channels and a count of the discrete state change cycles Following is a table that shows the variable mapping for both cases Variable Reporting can be...

Страница 94: ... set independently for each of the two channels Figure 9 7 Setting the Reported Value Reported Value Table 9 2 gives the reported value choices and the names for each possible state Also given are the corresponding analog value and discrete value for each possible state Value Name The Name of the reported value will be seen in AMS Wireless Configurator and on the device display The device display ...

Страница 95: ...nt or single channel application types Reported value Value name Analog Value Discrete Value Open switch Closed switch Open switch Closed switch Open switch Closed switch Default False True 0 000 1 000 240 242 Off On Off On 0 000 1 000 0 1 Opened Closed Opened Closed 46 000 6 000 46 6 Running Stopped Stopped Running 25 000 26 000 25 26 Slow Fast Slow Fast 8 000 7 000 8 7 Forward Reverse Forward Re...

Страница 96: ...of the circuit wired to the CH2 terminal and the negative side of the circuit wired to the CMN terminal If the output circuit is wired backwards it will remain active switch closed regardless of the state of the output channel Discrete output switch functionality The discrete output of the Rosemount 702 Transmitter is driven by the host control system through the Emerson Wireless Gateway and out t...

Страница 97: ... currents or voltages Special considerations for dual output circuits If both channels are connected to output circuits it is very important that the CMN terminal of each circuit be at the same voltage Employing a common ground for both output circuits is one way to ensure that both circuits have CMN terminals at the same voltage Figure 9 10 Dual Output Circuits with a Common Ground Connecting two...

Страница 98: ...control host the Rosemount 702 Transmitter then reports back the state of the output switch via the PV and SV There are various pairs of discrete states that correspond to an open or closed output switch This pair of discrete states is called the reported value and can be set in AMS Device Manager by going to Configure Manual Setup Discrete Channels Setup Channel X 1 or 2 under reported value ther...

Страница 99: ...ings Changing logic option from direct to Inverted has the effect of changing Open Switch to Closed Switch on the table above The manual override of an output channel changes the value from the Open Switch state to the Closed Switch state Reported value Value name Analog value Discrete value Open switch Closed switch Open switch Closed switch Open switch Closed switch Default False True 0 000 1 00...

Страница 100: ...lay when the power module is first connected to the Rosemount 702 Transmitter Parameter Name Description Read Write CHANNEL_1_STATE Analog value for channel 1 state Read CHANNEL_1_COUNTS Analog value for channel 1 state Read CHANNEL_1_STATE_D Discrete value for channel 1 state Read CHANNEL_1_SETPOINT_D Discrete value for channel 1 setpoint Read Write CHANNEL_2_STATE Analog value for channel 2 stat...

Страница 101: ... 702DX32 and 702DX42 3 Device Information Tag user entered tag which is 8 characters long will not display if all characters are blank 4 PV Screen Discrete State of Channel 1 5 SV Screen Discrete State of Channel 2 6 Electronics Temperature 7 Supply Voltage A b c d e f g h CH1 True CH2 True D E V 2 5 2 5 d e g c S u p l y 7 2 1 v o l t s ...

Страница 102: ...erly and the Diagnostic Button has been pressed 8 Channel 1 Count of close open cycles 9 Channel 2 Count of close open cycles 1 Diagnostic Button Screen 1 Tag user entered tag which is eight characters long will not display if all characters are blank 2 Diagnostic Button Screen 2 Device Identification used to determine Device ID 3 Diagnostic Button Screen 3 Network ID CH1 X X X X X X Counts CH2 X ...

Страница 103: ...t on the progress of the device in joining the wireless network 4 Diagnostic Button Screen 4 9 the device has joined a network and has been fully configured and has multiple parents 5 Diagnostic Button Screen 5 voltage reading at the power module terminals 1 Diagnostic Button Screen 4 1 the device is attempting to start the radio 2 Diagnostic Button Screen 4 2 the device has just restarted 3 Diagn...

Страница 104: ... 5 Diagnostic Button Screen 4 5 the device is searching for the Network 6 Diagnostic Button Screen 4 6 the device is attempting to join a network 7 Diagnostic Button Screen 4 7 the device is connected to the Network but is in a Quarantined state 8 Diagnostic Button Screen 4 8 the device is joined and operational but is running with limited bandwidth for sending periodic data n e t w k D I S C N T ...

Страница 105: ...ritical error which may prevent the electronics board from operating correctly 2 Diagnostic Button Screen 6 2 There is a warning which should be addressed but should not affect the device output 3 Diagnostic Button Screen 7 1 the terminal voltage has dropped below level of operating limit Replace the Black Power Module model number 701PBKKF Part Number 00753 9220 0001 4 Diagnostic Button Screen 7 ...

Страница 106: ...nfiguration status to identify which configuration item s need to be corrected 7 Diagnostic Button Screen 10 a switch attached to the transmitter has failed and valid readings from that switch are no longer possible check the switch and switch wiring connections check additional status for more detailed information of the failure source 8 Diagnostic Button Screen 11 The device has not yet received...

Страница 107: ...eactive as long as the batteries and the battery pack integrity are maintained Care should be taken to prevent thermal electrical or mechanical damage Contacts should be protected to prevent premature discharge Use caution when handling the power module It may be damaged if dropped from heights in excess of 20 feet Battery hazards remain when cells are discharged Environmental considerations As wi...

Страница 108: ... assist you with any needed information or materials The center will ask for product model and serial numbers and will provide a Return Material Authorization RMA number The center will also ask for the process material to which the product was last exposed Individuals who handle products exposed to a hazardous substance can avoid injury if they are informed of and understand the hazard If the pro...

Страница 109: ...eless update device reports current discrete state and accumulating count of close open cycles Accumulating count registers from 0 to 999 999 then re sets to 0 A 1 5 Discrete output model 702DX42 Maximum rating 26 Vdc 100 mA On resistance typical 1 Ohm A 1 6 Wireless output IEC 62591 WirelessHART 2 4 GHz DSSS A 1 7 Radio frequency power output from antenna External WK option antenna maximum of 10 ...

Страница 110: ...ion effect Wireless output unaffected when tested per the requirements of IEC60770 1 field or pipeline with high vibration level 10 60 Hz 0 21mm displacement peak amplitude 60 2000 Hz 3g Wireless output unaffected when tested per the requirements of IEC60770 1 field with general application or pipeline with low vibration level 10 60 Hz 0 15 mm displacement peak amplitude 60 500 Hz 2g Temperature l...

Страница 111: ...itter A Extended range external antenna B External antenna Dimensions are in inches millimeters Figure A 2 Rosemount 702 Transmitter Mounting Configurations with Optional Mounting Bracket A 2 in U bolt for pipe mounting B 1 in U bolt for transmitter mounting Dimensions are in inches millimeters 90 11 16 284 3 61 92 4 20 107 5 51 140 12 39 315 6 71 170 6 05 154 A B B 6 20 158 A ...

Страница 112: ...nput dry contact detects momentary inputs and counts 42 Discrete dual input or output configurable 61 1 Liquid hydrocarbon detection for use with TraceTek Fast Fuel Sensor or TraceTek Sensing cable Housing D Dual compartment housing aluminum E Dual compartment housing SST Conduit threads 1 1 2 14 NPT Certifications Measurement option codes I5 FM Intrinsically Safe Non Incendive and Dust Ignition P...

Страница 113: ...et and bolts Configuration C1 Factory configure date descriptor message fields and wireless parameters Cable gland G2 Cable gland 7 5 11 9 mm G4 3 Thin wire cable gland 3 8 mm Switches and kits SS01 Universal safety shower eyewash kit with UL switches SS02 Universal safety shower eyewash kit for insulated pipe with UL switches SS03 Universal safety shower eyewash kit with CSA switches SS04 Univers...

Страница 114: ...Specifications and Reference Data July 2017 Reference Manual 00809 0200 4702 Rev DA Specifications and Reference Data 104 ...

Страница 115: ...device may not cause harmful interference This device must accept any interference received including interference that may cause undesired operation This device must be installed to ensure a minimum antenna separation distance of 20 cm from all persons B 4 Ordinary Location Certification for FM Approvals As standard the transmitter has been examined and tested to determine that the design meets t...

Страница 116: ...sion 2 Certificate 1143113 Standards CAN CSA C22 2 No 0 10 CAN CSA C22 2 No 94 M91 CSA Std C22 2 No 142 M1987 CSA Std C22 2 No 60529 05 Markings Suitable for Class 1 Division 2 Groups A B C and D T3C Cl I Zone 2 IIC T3C B 8 Europe I1 ATEX Intrinsic Safety Certificate Baseefa07ATEX0239X Standards IEC 60079 0 2011 IEC 60079 11 2012 Markings II 1 G Ex ia IIC T4 Ga T4 60 C Ta 70 C For use with Rosemou...

Страница 117: ...m impact or abrasion if located in a Zone 0 area IY IECEx Intrinsic Safety for Zone 2 Certificate IECEx BAS 12 0082X Standards IEC 60079 0 2011 IEC 60079 11 2011 Markings Ex ic IIC T4 Gc T4 40 C Ta 70 C Ex ic IIC T5 Gc T5 40 C Ta 40 C Specific Conditions For Safe Use X 1 The surface resistivity of the antenna is greater than 1 GΩ To avoid electrostatic charge build up it must not be rubbed or clea...

Страница 118: ...al parameters option code 61 Sensor Switch Uo 6 6 V Uo 6 6 V Ui 26 mW Uo 7 8 V Io 13 4 mA Io 13 4 mA Ii 100 MA Io 92 MA Po 21 8 mW Po 21 8 mW PI 650 mW Po 180 mW COIIC 23 78 μF Co 10 9 μF N A Co 9 29 μF COIIB 499 78 μF N A N A N A COIIA 1000 μF N A N A N A LOIIC 200 mH Lo 0 025 mH N A LO 2 mH LOIIB 800 mH N A N A N A LOIIA 1000 mH N A N A N A Sensor terminal parameters option code 32 Terminal para...

Страница 119: ...Product Certifications 109 Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA B 13 Installation Drawings Figure B 1 Rosemount 702 FM Intrinsically Safe Installation Drawing ...

Страница 120: ...Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA Product Certifications 110 ...

Страница 121: ...Product Certifications 111 Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA Figure B 2 Rosemount 702 CSA Intrinsic Safety Installation Drawing ...

Страница 122: ...Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA Product Certifications 112 ...

Страница 123: ...Product Certifications 113 Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA ...

Страница 124: ...Product Certifications July 2017 Reference Manual 00809 0200 4702 Rev DA Product Certifications 114 ...

Страница 125: ...nnas for the wireless field device always use established safety procedures to avoid falling or contact with high power electrical lines Install remote antenna components for the wireless field device in compliance with local and national electrical codes and use best practices for lightning protection Before installing consult with the local area electrical inspector electrical officer and work a...

Страница 126: ...nections Coaxial material Heavy duty low loss LMR400 cable Minimum coaxial bend diameter 1 0 ft 0 3 m Antenna Remote mount omni directional antenna Fiberglass and aluminum construction 8 Db Gain Meets MIL STD 810G method 510 5 procedure I and II Physical specifications Weight 1 0 lb 0 4 kg RF lightning arrestor In line lightning arrestor Electrical connection lightning arrestor MUST be grounded pe...

Страница 127: ...to affix the drip loop to the lower portion of the mast ensuring that condensation or rainwater will flow away from the coaxial connections Applying coaxial sealant moisture protection Utilize the coaxial sealant that is included in the high gain remote mounting kit package Follow included instructions for application on the coaxial connection C 4 Transient lightning considerations Gateway transie...

Страница 128: ... 4702 Rev DA High Gain Remote Antenna Option 118 C 5 Dimensional drawings Figure C 1 Device Connection and RF Lightning Arrestor A Antenna B Mounting bracket C Mounting arrester D 25 ft 7 5 m cable E Min drip loop Ø12 in 0 3 m n n n 53 2 75 4 PLS X 20 2 ft 513m D A B C E ...

Страница 129: ... 119 C 6 Installing the high gain remote antenna 1 Mount the transmitter following best practice mounting procedures as outlined in the Quick Start Guide and Manual 2 Connect the RF lightning protector to the device and tighten 3 Connect antenna to mounting bracket and tighten nut carefully RF lightning protector ...

Страница 130: ...ble to both the antenna and the lightning protector connected to the transmitter leaving one loop minimum for a drip loop Ensure the drip loop is lower than the device allowing water to flow away from the device 5 Apply the coaxial sealant around each of the coaxial connections and at the lightning arrestor making sure the RF connections are completely sealed ...

Страница 131: ...09 0200 4702 Rev DA High Gain Remote Antenna Option 121 6 Attach U bolts to mounting bracket in correct orientation ensuring that antenna will be positioned in a vertical position 7 Tighten U bolts to mast and ensure that antenna is pointed in a vertical direction ...

Страница 132: ...High Gain Remote Antenna Option July 2017 Reference Manual 00809 0200 4702 Rev DA High Gain Remote Antenna Option 122 ...

Страница 133: ...on the equipment 2 Begin shower mounting kit installation by drilling two holes in the shower handle as shown 3 Attach the target arm to the shower handle using two 10 24 x 0 75 hex head screws two 10 lock washers and two 10 24 hex nuts 4 Loosely attach the target magnet to the target arm using two 10 24 x 0 75 flat head screws two 10 lock washers and two 10 24 Hex Nuts 5 Fasten the two mounting b...

Страница 134: ...mounting brackets 10 Series GO Switch and target arm so that the target magnet properly engages the switch Mark the position of the slot of the target arm Drill two holes in the eyewash handle as shown to be able to attach the target arm 14 Attach the target arm to the eyewash handle using two 10 24 x 0 50 round head screws two 10 lock washers and two 10 24 hex nuts 15 Tighten hardware to hold the...

Страница 135: ... PLATE MOUNTING 1 3 ARM TARGET 1 4 MAGNET TARGET 1 5 10 WASHER SPRING LOCK 4 6 10 24 NUT HEX 4 7 10 24 X 75 FLAT HEAD SCREW 2 8 1 4 20 NUT HEX 20 9 1 4 WASHER LOCK SPRING 12 10 1 4 WASHER PLAIN 12 11 1 4 20 X 75 SCREW HEX HEAD 4 12 10 24 X 0 75 HEX HEAD SCREW 2 13 2 9 11 9 10 2 9 11 8 7 6 5 4 1 3 13 7 6 1 2 2 9 11 9 11 9 10 9 10 11 12 9 10 11 12 12 11 10 9 3 2 9 10 11 2 9 10 11 4 8 7 6 1 5 13 7 6 ...

Страница 136: ...ED 4 2 1 4 20 NUT HEX 20 3 1 4 WASHER PLAIN 12 4 1 4 WASHER LOCK SPRING 12 5 BRACKET MOUNTING 1 6 10 24 X 75 FLAT HEAD SCREW 2 7 10 24 NUT HEX 4 8 10 WASHER SPRING LOCK 4 9 MAGNET TARGET 1 10 ARM TARGET 1 11 10 24 X 50 SCREW ROUND HEAD 2 12 1 4 20 X 75 SCREW HEX HEAD 4 13 1 6 3 4 5 3 4 5 3 4 5 3 4 5 11 10 12 9 8 2 2 13 5 4 3 13 5 4 3 13 5 4 3 13 5 4 3 1 2 3 4 5 2 3 4 5 2 3 4 5 6 13 5 4 3 7 8 9 11 ...

Страница 137: ...pon condition that it will not be used in any way detrimental to the interest of TOPWORX INC UNLESS OTHERWISE SPECIFIED TOLERANCES XX B 01 XXX B 005 ANGLES B UNIT OF MEASURE INCHES DO NOT SCALE THIS DRAWING ANSI Y14 5 ISO 1101 DRAWN DATE MFG APPROVED STATUS OF REVISION DATE BY IGB 11 12 2010 BD 11 12 2010 RKC 11 12 2010 Released 10 SERIES GO SWITCH KIT MOUNTING 4 U13060 S51 2 C 1 1 NONE 2 07 06 11...

Страница 138: ...ANCES XX B 01 XXX B 005 ANGLES B UNIT OF MEASURE INCHES DO NOT SCALE THIS DRAWING ANSI Y14 5 ISO 1101 DRAWN DATE MFG APPROVED STATUS OF REVISION DATE BY CMM 11 15 2010 BD 11 15 2010 RKC 11 15 2010 Released Type 10 Series Switch with or KIT MOUNTING 4 U13061 S51 2 C 1 1 NONE 2 07 06 11 RDC Without Latcher A A Parts List DESCRIPTION QTY ITEM VALVE BALL 5 NPT 1 1 10 WASHER SPRING LOCK 4 2 10 24 NUT H...

Страница 139: ...tion 5 high voltage environment 7 52 I Information System 9 52 J Join Key 9 29 31 53 75 77 L LCD 23 70 LCD pins 23 70 LCD temperature limits 24 70 lethal voltage 7 52 Limit Contacts 20 35 64 81 Liquid Hydrocarbon Detection 21 23 36 38 70 lithium 5 48 97 Local Display 29 N Network ID 9 29 31 53 75 77 nuclear qualified applications ix O Opposing Contact 20 35 64 65 82 P Power Module 5 power module 8...

Страница 140: ...130 Reference Manual 00809 0200 4702 Rev DA Index July 2017 Index update rate 29 W wireless enabled signal 3 wiring practice 25 71 ...

Страница 141: ......

Страница 142: ...i Free Zone South 2 Dubai United Arab Emirates 971 4 8118100 971 4 8865465 RFQ RMTMEA Emerson com Linkedin com company Emerson Automation Solutions Twitter com Rosemount_News Facebook com Rosemount Youtube com user RosemountMeasurement Google com RosemountMeasurement Standard Terms and Conditions of Sale can be found on the Terms and Conditions of Sale page The Emerson logo is a trademark and serv...

Отзывы: