Product Certifications
Product Certifications
July 2016
Reference Manual
00809-0100-4728, Rev MB
Specific Condition for Safe Use (X):
1. For information on the dimensions of the flameproof joints
the manufacturer shall be contacted.
B.3.4 IECEx Certifications
E7
IECEx Flameproof and Dust
Certificate: IECEx KEM 09.0015X
Ex d IIC T6 (Flameproof) -40 °C < T
amb
< 65 °C
Ex tD A20 IP 66 T 95 °C (Dust)
Vmax = 42.4 V
Specific Condition for Safe Use (X):
1. For information on the dimensions of the flameproof joints
the manufacturer shall be contacted.
I7
IECEx Intrinsic Safety
Certificate: IECEx BAS 07.0053X
Ex ia IIC T4/T5/T6
Special Conditions for Safe Use (X):
1. The apparatus must be installed in an enclosure which
affords it a degree of protection of at least IP20.
2. Non-metallic enclosures must have a surface resistance of
less than 1 G
; light alloy or zirconium enclosures must be
protected from impact and friction when installed.
N7
IECEx Type n
Certificate: IECEx BAS 07.0055
Ex nA nL IIC T5 (-40 °C
T
amb
70 °C)
NG
IECEx Type n Component
Certificate: IECEx BAS 07.0054U
Ex nA nL IIC T5 (-40 °C
T
amb
75 °C)
Input Parameter: Ui = 32 Vdc
Schedule of Limitations:
The component must be housed in a suitably certified enclosure
that provides a degree of protection of at least IP54.
B.3.5 Japanese Certifications
Japanese Industrial Standard (JIS) Approvals
I4
JIS Intrinsic Safety
E4
JIS Explosion Proof
B.3.6 Combination Approvals
K5
Combination of I5 and E5
Table B-3. Electrical Data
Transmitter
Sensor
V
max
= 32 Vdc
U
max
= 5 Vdc
I
max
= 24.0 mA
I
max
= 2.0 mA
Table B-4. Temperature Classification
P
i (W)
Temperature class
T
amb
1.3
T4
-50 °C to 60 °C
5.32 (FISCO Group IIC)
T4
-60 °C to 60 °C
Table B-5. Entity Parameters
Transmitter (I.S.)
Transmitter (FISCO)
Sensor
U
i
= 30 Vdc
U
i
= 17.5 Vdc
U
o
= 13.9 Vdc
I
i
= 300 mA
I
i
= 380 mA
I
o
= 23 mA
P
i
= 1.3 W
P
i
= 5.32 W
P
o
= 79 mW
C
i
= 2.1 nF
C
i
= 2.1 nF
C
i
= 7.7 nF
L
i
= 0 mH
L
i
= 0 mH
L
i
= 0 mH
Table B-6. Electrical Data
Transmitter
Sensor
RTD
Thermocouple
U
i
= 32 V
U
i
= 5 V
U
i
= 0
Table B-7. Certificate and Description
Certificate Description
Approval
group
Temp
code
C15744
Rosemount 644H with
meter and no sensor
Ex d II C
T6
C15745
Rosemount 644H without
meter and no sensor
Ex d II C
T6
C15749
Rosemount 644H without
meter and with RTD
Ex d II B
T4
C15750
Rosemount 644H without
meter and with
thermocouple
Ex d II B
T4
C15751
Rosemount 644H with
meter and thermocouple
Ex d II B
T4
C15752
Rosemount 644H with
meter and RTD
Ex d II B
T4
C15910
Rosemount 644H without
meter and with
thermocouple
Ex d II B +
H2
T4
C15911
Rosemount 644H with
meter and thermocouple
Ex d II B +
H2
T4
C15912
Rosemount 644H without
meter and with RTD
Ex d II B +
H2
T4
C15913
Rosemount 644H with
meter and RTD
Ex d II B +
H2
T4
Содержание Rosemount 644 HART
Страница 2: ......
Страница 16: ...6 Reference Manual 00809 0100 4728 Rev MB Introduction July 2016 Introduction ...
Страница 80: ...70 Reference Manual 00809 0100 4728 Rev MB Operation and Maintenance July 2016 Operation and Maintenance ...
Страница 86: ...76 Reference Manual 00809 0100 4728 Rev MB Troubleshooting July 2016 Troubleshooting ...
Страница 120: ...Product Certifications July 2016 Reference Manual 00809 0100 4728 Rev MB 110 Product Certifications Sheet 2 of 2 ...
Страница 122: ...Product Certifications July 2016 Reference Manual 00809 0100 4728 Rev MB 112 Product Certifications ...
Страница 138: ...128 Reference Manual 00809 0100 4728 Rev MB Index July 2016 Index ...
Страница 139: ......