8
Reference Manual
00809-0400-4728, Rev CA
Configuration
September 2018
Configuration
2.3.6
Capabilities
Virtual Communication Relationship (VCR)
There are a total of 12 VCR’s. One is permanent and 11 are fully configurable by the host system. 16 link
objects are available.
Block execution times
Analog input = 45 ms
PID = 60 ms
2.3.7
Surges/transients
The transmitter will withstand electrical transients of the energy level encountered in static discharges or
induced switching transients. However, high-energy transients, such as those induced in wiring from
nearby lightning strikes, welding, heavy electrical equipment, or switching gears, can damage both the
transmitter and the sensor. To protect against high-energy transients, install the transmitter into a
suitable connection head with the integral transient protector, option T1. Refer to the Rosemount 644
Product Data Sheet for more information.
2.4
F
OUNDATION
Fieldbus function blocks
For reference information on the Resource, Sensor Transducer, AI, LCD Transducer blocks refer to
F
OUNDATION
Fieldbus Block Information on
. Reference information on the PID block can be found
in the Function Block
Resource block (index number 1000)
The Resource Function Block (RB) contains diagnostic, hardware, and electronics information. There are
no linkable inputs or outputs to the Resource Block.
Sensor transducer block (index number 1100)
The Sensor Transducer Function Block (STB) temperature measurement data includes sensor and
terminal temperature. The STB also includes information about sensor type, engineering units,
linearization, reranging, damping, temperature compensation, and diagnostics.
Network parameter
Value
Slot Time
8
Maximum Response Delay
2
Maximum Inactivity to Claim LAS Delay
32
Minimum Inter DLPDU Delay
8
Time Sync class
4 (1ms)
Maximum Scheduling Overhead
21
Per CLPDU PhL Overhead
4
Maximum Inter-channel Signal Skew
0
Required Number of Post-transmission-gab-ext Units
0
Required Number of Preamble-extension Units
1
Содержание Rosemount 644 FOUNDATION
Страница 2: ......
Страница 6: ...4 Reference Manual 00809 0100 4728 Rev CA Title Page September 2018 Title Page ...
Страница 10: ...4 Reference Manual 00809 0400 4728 Rev CA Introduction September 2018 Introduction ...
Страница 34: ...28 Reference Manual 00809 0400 4728 Rev CA Configuration September 2018 Configuration ...
Страница 48: ...Reference Data September 2018 Reference Manual 00809 0400 4728 Rev CA Reference Data 42 ...
Страница 63: ......