4.11
Analog Input block
4.11.1
Configure the AI block
A minimum of four parameters are required to configure the AI block. The parameters
are described below with example configurations shown at the end of this section.
CHANNEL
Select the channel that corresponds to the desired sensor measurement:
Table 4-5: AI Block Channels for the Rosemount 5900C
AI Block Parameter
TB Channel Value
Process Variable
Level
1
CHANNEL_LEVEL
Distance
2
CHANNEL_DISTANCE
Level Rate
3
CHANNEL_LEVELRATE
Signal Strength
4
CHANNEL_SIGNAL_STRENGTH
Internal Temperature
5
CHANNEL_HOUSING_TEMPERA
TURE
Volume
6
CHANNEL_VOLUME
L_TYPE
The L_TYPE parameter defines the relationship of the transmitter measurement (Level,
Distance, Level Rate, Signal Strength, Internal Temperature, and Volume) to the desired
output of the AI Block. The relationship can be direct, indirect, or indirect root.
Direct
Select direct when the desired output will be the same as the transmitter
measurement (level, distance, level rate, signal strength, volume, and
internal temperature).
Indirect
Select indirect when the desired output is a calculated measurement based
on the transmitter measurement (level, distance, level rate, signal
strength, volume, and internal temperature). The relationship between the
transmitter measurement and the calculated measurement will be linear.
Indirect
square root
Select indirect square root when the desired output is an inferred
measurement based on the transmitter measurement and the relationship
between the sensor measurement and the inferred measurement is square
root.
XD_SCALE and OUT_SCALE
The XD_SCALE and OUT_SCALE each include three parameters: 0%, 100%, and
engineering units. Set these based on the L_TYPE:
L_TYPE is
direct
When the desired output is the measured variable, set the XD_SCALE to
represent the operating range of the process. Set OUT_SCALE to match
XD_SCALE.
Configuration
Reference Manual
September 2019
00809-0100-5901
162
Reference Manual
Содержание Rosemount 5900C
Страница 1: ...Reference Manual 00809 0100 5901 Rev DA September 2019 Rosemount 5900C Radar Level Gauge ...
Страница 6: ...Contents Reference Manual September 2019 00809 0100 5901 vi Reference Manual ...
Страница 12: ...Introduction Reference Manual September 2019 00809 0100 5901 12 Reference Manual ...
Страница 116: ...Installation Reference Manual September 2019 00809 0100 5901 116 Reference Manual ...
Страница 204: ...Configuration Reference Manual September 2019 00809 0100 5901 204 Reference Manual ...
Страница 208: ...Operation Reference Manual September 2019 00809 0100 5901 208 Reference Manual ...
Страница 244: ...Service and troubleshooting Reference Manual September 2019 00809 0100 5901 244 Reference Manual ...
Страница 278: ...Specifications and reference data Reference Manual September 2019 00809 0100 5901 278 Reference Manual ...
Страница 290: ...Product Certifications Reference Manual September 2019 00809 0100 5901 290 Reference Manual ...