Table J-1: Definitions of Analog Input Function Block System Parameters
Parameter
Index Number Units
Description
ACK_OPTION
23
None
Used to set auto acknowledgment of alarms.
ALARM_HYS
24
Percent
The amount the alarm value must return within the alarm limit
before the associated active alarm condition clears.
ALARM_SEL
38
None
Used to select the process alarm conditions that will cause the
OUT_D parameter to be set.
ALARM_SUM
22
None
The summary alarm is used for all process alarms in the block. The
cause of the alert is entered in the subcode field. The first alert to
become active will set the Active status in the Status parameter. As
soon as the Unreported status is cleared by the alert reporting task,
another block alert may be reported without clearing the Active
status, if the subcode has changed.
ALERT_KEY
04
None
The identification number of the plant unit. This information may
be used in the host for sorting alarms, etc.
BLOCK_ALM
21
None
The block alarm is used for all configuration, hardware, connection
failure or system problems in the block. The cause of the alert is
entered in the subcode field. The first alert to become active will set
the Active status in the Status parameter. As soon as the
Unreported status is cleared by the alert reporting task, another
block alert may be reported without clearing the Active status, if
the subcode has changed.
BLOCK_ERR
06
None
This parameter reflects the error status associated with the
hardware or software components associated with a block. It is a bit
string, so that multiple errors may be shown.
CHANNEL
15
None
The CHANNEL value is used to select the measurement value.
You must configure the CHANNEL parameter before you can
configure the XD_SCALE parameter.
FIELD_VAL
19
Percent
The value and status from the transducer block or from the
simulated input when simulation is enabled.
GRANT_DENY
12
None
Options for controlling access of host computers and local control
panels to operating, tuning, and alarm parameters of the block. Not
used by device.
HI_ALM
34
None
The HI alarm data, which includes a value of the alarm, a timestamp
of occurrence and the state of the alarm.
HI_HI_ALM
33
None
The HI HI alarm data, which includes a value of the alarm, a
timestamp of occurrence and the state of the alarm.
HI_HI_LIM
26
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI HI alarm
condition.
HI_HI_PRI
25
None
The priority of the HI HI alarm.
HI_LIM
28
EU of
PV_SCALE
The setting for the alarm limit used to detect the HI alarm
condition.
HI_PRI
27
None
The priority of the HI alarm.
IO_OPTS
13
None
Allows the selection of input/output options used to alter the PV.
Low cutoff enabled is the only selectable option.
Reference Manual
Analog-Input Block
00809-0100-4530
April 2019
Reference Manual
459
Содержание Rosemount 5300 Series
Страница 1: ...Reference Manual 00809 0100 4530 Rev FA April 2019 Rosemount 5300 Level Transmitter Guided Wave Radar ...
Страница 26: ...Transmitter overview Reference Manual April 2019 00809 0100 4530 26 Rosemount 5300 Level Transmitter ...
Страница 112: ...Electrical installation Reference Manual April 2019 00809 0100 4530 112 Rosemount 5300 Level Transmitter ...
Страница 158: ...Configuration Reference Manual April 2019 00809 0100 4530 158 Rosemount 5300 Level Transmitter ...
Страница 168: ...Operation Reference Manual April 2019 00809 0100 4530 168 Rosemount 5300 Level Transmitter ...
Страница 244: ...Service and troubleshooting Reference Manual April 2019 00809 0100 4530 244 Rosemount 5300 Level Transmitter ...
Страница 380: ...Product certifications Reference Manual April 2019 00809 0100 4530 380 Rosemount 5300 Level Transmitter ...
Страница 396: ...Configuration parameters Reference Manual April 2019 00809 0100 4530 396 Rosemount 5300 Level Transmitter ...
Страница 487: ...Reference Manual 00809 0100 4530 April 2019 Reference Manual 487 ...