Reference Manual
00809-0100-4021, Rev JA
Installation
April 2017
Installation
2.5.5
LCD display
Transmitters ordered with the LCD display option (code M5) are shipped with the LCD display installed.
After-market installation of the LCD display on a conventional transmitter requires a small instrument
screwdriver and the LCD display kit, which includes:
LCD display assembly
Extended cover with cover O-ring in place
Captive screws (quantity 2)
10-pin interconnection header
To install the LCD display:
1. If the transmitter is installed in a loop, set the loop to manual (HART)/out-of-service (F
OUNDATION
Fieldbus) mode and disconnect the power.
2. Remove the housing cover from the electronics side of the transmitter. Do not remove the
transmitter covers in explosive atmospheres with a live circuit.
3. Ensure that the transmitter write protect switch is set to the Off position. If transmitter security is On,
the transmitter cannot be configured to recognize the LCD display. If security On is desired, configure
the transmitter for the LCD display, and then install the meter.
4. Insert the interconnection header in the 10-pin socket on the face of the electronics module. Insert
the pins into the electronics LCD display interface.
5. The meter can be rotated in 90-degree increments for easy viewing. Position one of the four 10-pin
sockets on the back of the meter to accept the interconnection header.
6. Attach the LCD display assembly to the interconnection pins, then thread and tighten the LCD display
screws into the holes on the electronics module.
7. Attach the extended cover; tighten at least one-third turn after the O-ring contacts the transmitter
housing. Both transmitter covers must be fully engaged to meet explosion proof requirements.
8. Apply power and set the loop to automatic (HART)/in-service (F
OUNDATION
Fieldbus) mode.
Once the LCD display is installed, configure the transmitter to recognize the meter option. Refer to
(HART Protocol) or
LCD display Transducer Block (index number 1200)
OUNDATION
Fieldbus).
Note
Observe the following LCD display temperature limits:
Operating: –40 to 185 °F (–40 to 85 °C)
Storage: –76 to 185 °F (–60 to 85 °C)
Содержание Rosemount 3144P
Страница 2: ......
Страница 10: ...8 Reference Manual 00809 0100 4021 Rev JA Title Page April 2017 Title Page ...
Страница 16: ...6 Reference Manual 00809 0100 4021 Rev JA Introduction April 2017 Introduction ...
Страница 38: ...28 Reference Manual 00809 0100 4021 Rev JA Installation April 2017 Installation ...
Страница 182: ...172 Reference Manual 00809 0100 4021 Rev JA Operation and Maintenance April 2017 Operation and Maintenance ...
Страница 221: ...Product Certifications 211 Product Certifications April 2017 Reference Manual 00809 0100 4021 Rev JA ...
Страница 226: ...Product Certifications April 2017 Reference Manual 00809 0100 4021 Rev JA Product Certifications 216 ...
Страница 232: ...Product Certifications April 2017 Reference Manual 00809 0100 4021 Rev JA Product Certifications 222 ...
Страница 233: ...Product Certifications 223 Product Certifications April 2017 Reference Manual 00809 0100 4021 Rev JA ...
Страница 234: ...Product Certifications April 2017 Reference Manual 00809 0100 4021 Rev JA Product Certifications 224 ...
Страница 235: ...225 Reference Manual 00809 0100 4021 Rev JA April 2017 ...