www.emersonprocess.com/rosemount

Reference Manual

00809-0100-4001, Rev JA

November 2012

Rosemount 3051 Pressure Transmitter

with HART

®

 Protocol

This product is in the process of being discontinued.  Limited supply available.
Please consult a local Emerson Process Management contact for details.

Содержание Rosemount 3051

Страница 1: ...anual 00809 0100 4001 Rev JA November 2012 Rosemount 3051 Pressure Transmitter with HART Protocol This product is in the process of being discontinued Limited supply available Please consult a local Emerson Process Management contact for details ...

Страница 2: ......

Страница 3: ... United States 1 800 999 9307 7 00 am to 7 00 pm CST Asia Pacific 65 777 8211 Europe Middle East Africa 49 8153 9390 North American Response Center Equipment service needs 1 800 654 7768 24 hours includes Canada Outside of these areas contact your local Emerson Process Management representative The products described in this document are NOT designed for nuclear qualified applications Using non nu...

Страница 4: ...iv Reference Manual 00809 0100 4001 Rev JA Title Page November 2012 ...

Страница 5: ...ion procedures 10 2 8 1 Mount the transmitter 10 2 8 2 Impulse piping 14 2 8 3 Process connections 16 2 8 4 Inline process connection 18 2 8 5 Housing rotation 18 2 8 6 LCD display 19 2 8 7 Configure security and alarm 20 2 9 Electrical considerations 22 2 9 1 Conduit installation 22 2 9 2 Wiring 23 2 9 3 Transient protection terminal block 26 2 9 4 Grounding 27 2 10Hazardous locations certificati...

Страница 6: ...t 50 3 8 1 Process variables 51 3 8 2 Sensor temperature 51 3 9 Basic setup 52 3 9 1 Set process variable units 52 3 9 2 Set output Transfer function 52 3 9 3 Rerange 53 3 9 4 Damping 57 3 10LCD display 58 3 10 1LCD display configuration for 4 20 mA HART only 59 3 10 2Custom display configuration 4 20 mA HART only 59 3 11Detailed setup 61 3 11 1Failure mode alarm and saturation 61 3 11 2Alarm and ...

Страница 7: ...er scale 79 4 4 3 Recall factory trim analog output 80 4 5 Sensor trim 81 4 5 1 Sensor trim overview 81 4 5 2 Zero trim 82 4 5 3 Sensor trim 83 4 5 4 Recall factory trim sensor trim 84 4 5 5 Line pressure effect range 2 and range 3 84 4 5 6 Compensating for line pressure 85 5Section 5 Troubleshooting 5 1 Overview 89 5 2 Safety messages 89 5 2 1 Warnings 90 5 3 Diagnostic messages 92 5 4 Disassembl...

Страница 8: ... code T1 107 A 2 Functional specifications 108 A 2 1 Range and sensor limits 108 A 2 2 Zero and Span Adjustment Requirements HART and Low Power 109 A 2 3 Service 110 A 2 4 4 20 mA Output Code A 110 A 2 5 Foundation fieldbus output code F and Profibus output code W 110 A 2 6 Foundation fieldbus function block execution times 111 A 2 7 Foundation fieldbus Parameters 111 A 2 8 Standard Function Block...

Страница 9: ...ions Include with selected model number 147 A 5 4 Options Include with selected model number 152 A 6 Options 156 A 7 Spare parts 164 BAppendix B Product certifications B 1 Overview 175 B 2 Safety messages 175 B 2 1 Warnings 176 B 3 Approved manufacturing locations 176 B 4 European directive information 176 B 4 1 Ordinary location certification for factory mutual 176 B 5 Hazardous locations certifi...

Страница 10: ...x Reference Manual 00809 0100 4001 Rev JA Table of Contents November 2012 Table of Contents ...

Страница 11: ... troubleshooting techniques for the most common operating problems Appendix A Specifications and reference data supplies reference and specification data as well as ordering information Appendix B Product certifications contains intrinsic safety approval information European ATEX directive information and approval drawings 1 2 Service support To expedite the return process outside of the United St...

Страница 12: ...r Measures absolute pressure up to 4000 psia 275 8 bar Rosemount 3051T in line pressure transmitter Rosemount 3051T Gage and Absolute Pressure Transmitter Measures gage pressure up to 10000 psi 689 5 bar Rosemount 3051L liquid level transmitter Provides precise level and specific gravity measurements up to 300 psi 20 7 bar for a wide variety of tank configurations Rosemount 3051H high process temp...

Страница 13: ...sor and the sensor electronics The sensor electronics are installed within the sensor module and include a temperature sensor RTD a memory module and the capacitance to digital signal converter C D converter The electrical signals from the sensor module are transmitted to the output electronics in the electronics housing The electronics housing contains the output electronics board the local zero ...

Страница 14: ... and disposed of in accordance with local and national legislation regulations SENSOR MODULE ELECTRONICS BOARD 4 20 MA SIGNAL TO CONTROL SYSTEM Signal Processing Temp Sensor Sensor Module Memory Microcomputer Sensor linearization Rerange Damping Diagnostics Engineering Communication Module Memory Rerange values Configuration Digital to AnalogSignal Conversion Digital Communication Local Span and Z...

Страница 15: ... information in this section covers installation considerations for the Rosemount 3051 with HART protocols A Quick Installation Guide for HART protocol document number 00825 0100 4001 is shipped with every transmitter to describe basic pipe fitting and wiring procedures for initial installation Dimensional drawings for each 3051 variation and mounting configuration are included on page 13 2 2 Safe...

Страница 16: ...ion Proof Flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death Install and tighten process connectors before applying pressure Electrical shock can result in death or serious injury Avoid contact with the leads and terminals High voltage that may be present on leads can cause electrical shock Electrical shock...

Страница 17: ...range considerations Installation For the Rosemount 3051CD0 draft range pressure transmitter it is best to mount the transmitter with the isolators parallel to the ground Installing the transmitter in this way reduces oil head effect and provides for optimal temperature performance Be sure the transmitter is securely mounted Tilting of the transmitter may cause a zero shift in the transmitter outp...

Страница 18: ...amber to achieve a common gage reference 2 6 Environmental considerations Best practice is to mount the transmitter in an environment that has minimal ambient temperature change The transmitter electronics temperature operating limits are 40 to 185 F 40 to 85 C Refer to Appendix A Specifications and reference data that lists the sensing element operating limits Mount the transmitter so that it is ...

Страница 19: ...page 53 Set Output Type page 52 Set Damping page 57 Verify Apply Pressure Yes Within Specifications Yes No Refer to Section 4 Operation and maintenance ConfigureSecurity and Alarm page 20 Mount Transmitter page 10 Wire Transmitter pages 23 31 Power Transmitter page 25 Check Process Connection page 16 Trim Transmitter for Mounting Effects page 76 Done Review Transmitter Configuration page 42 Confir...

Страница 20: ...to Sensor Trim on page 10 Housing rotation See Housing rotation on page 18 Terminal side of electronics housing Mount the transmitter so the terminal side is accessible Clearance of 0 75 in 19 mm is required for cover removal Use a conduit plug in the unused conduit opening Circuit side of electronics housing Provide 0 75 in 19 mm of clearance for units with out an LCD display Three inches of clea...

Страница 21: ...th a lubricant to ease installation Carbon steel bolts do not require lubrication No additional lubricant should be applied when installing either type of bolt Bolts supplied by Emerson Process Management are identified by their head markings 3051 brackets Option code Process connections Mounting Materials Coplanar In line Traditional Pipe mount Panel mount Flat panel mount CS bracket SST bracket ...

Страница 22: ...63 41 4 09 104 4 5 114 1 405 35 7 Mounting Holes 0 375 Diameter 10 3 75 95 2 81 71 2 125 54 2 81 71 8 00 203 Note Dimensions are in inches millimeters 1 625 41 Figure 2 3 Mounti ng bracket option codes B1 B7 and BA 1 40 36 1 405 35 7 Figure 2 4 Panel mounting bracket option codes B2 and B8 Figure 2 5 Flat mounting bracket option codes B3 and BC ...

Страница 23: ...ue the bolts to the final torque value using the same crossing pattern Table 2 2 Bolt installation torque values Bolt material Initial torque value Final torque value CS ASTM A445 Standard 300 in lb 34 N m 650 in lb 73 N m 316 SST Option L4 150 in lb 17 N m 300 in lb 34 N m ASTM A 19 B7M Option L5 300 in lb 34 N m 650 in lb 73 N m Alloy 400 Option L6 300 in lb 34 N m 650 in lb 73 N m Carbon Steel ...

Страница 24: ...nsfer leaks GAGE ABSOLUTE TRANSMITTER DIFFERENTIAL TRANSMITTER Drain Vent Drain Vent Plug 1 75 44 4 1 50 38 4 1 75 44 4 1 50 38 4 Note Dimensions are in inches millimeters Drain Vent 2 88 73 4 TRANSMITTER WITH FLANGE BOLTS TRANSMITTER WITH FLANGE ADAPTERS AND FLANGE ADAPTER BOLTS Description Qty Size in mm Differential Pressure Flange Bolts 4 1 75 44 Flange Adapter Bolts 4 2 88 73 Gage Absolute Pr...

Страница 25: ...engths of the same size pipe Avoid purging through the transmitter Keep corrosive or hot above 250 F 121 C process material out of direct contact with the sensor module and flanges Prevent sediment deposits in the impulse piping Maintain equal leg of head pressure on both legs of the impulse piping Avoid conditions that might allow process fluid to freeze within the process flange Mounting require...

Страница 26: ...on the transmitter flanges are 1 4 18 NPT Flange adapters are available with standard 1 2 14 NPT Class 2 connections The flange adapters allow users to disconnect from the process by removing the flange adapter bolts Use plant approved lubricant or sealant when making the process connections Refer to Dimensional Drawings on page 120 for the distance between pressure connections This distance may b...

Страница 27: ...dapters Rosemount 1151 and Rosemount 3051S 3051 2051 3095 each require a unique O ring see Figure 2 9 Use only the O ring designed for the corresponding flange adaptor Figure 2 9 O Rings When compressed PTFE O rings tend to cold flow which aids in their sealing capabilities Note PTFE O rings should be replaced if the flange adapter is removed Failure to install proper flange adapter O rings may ca...

Страница 28: ...side pressure port 2 8 5 Housing rotation The electronics housing can be rotated up to 180 degrees in either direction to improve field access or to better view the optional LCD display To rotate the housing perform the following procedure 1 Loosen the housing rotation set screw using a in hex wrench 2 Turn the housing left or right up to 180 from its original position Over rotating will damage th...

Страница 29: ... 2 8 6 LCD display Transmitters ordered with the LCD option are shipped with the display installed Installing the display on an existing 3051 transmitter requires a small instrument screwdriver Figure 2 12 LCD display Housing Rotation Set Screw 5 64 in Interconnecting Pins Jumpers Top and Bottom LCD Display Extended Cover ...

Страница 30: ... to prevent accidental or deliberate change of configuration data If the transmitter write protection jumper is in the ON position the transmitter will not accept any writes to its memory Configuration changes such as digital trim and reranging cannot take place when the transmitter security is on Note If the security jumper is not installed the transmitter will continue to operate in the security...

Страница 31: ... power transmitter electronics boards Note Security jumper not installed Not Write Protected Alarm jumper not installed High Alarm 4 20 mA HART Without LCD Meter With LCD Display 1 5 Vdc HART Low Power Without LCD Meter With LCD Display Security Alarm Alarm Security TRANSMITTER SECURITY JUMPER POSITIONS Write Protect ON Write Protect OFF ...

Страница 32: ...stallation diagrams If all connections are not sealed excess moisture accumulation can damage the transmitter Make sure to mount the transmitter with the electrical housing positioned downward for drainage To avoid moisture accumulation in the housing install wiring with a drip loop and ensure the bottom of the drip loop is mounted lower than the conduit connections or the transmitter housing Seal...

Страница 33: ...wisted pairs to yield best results To ensure proper communication use 24 AWG or larger wire and do not exceed 5000 feet 1500 meters Figure 2 16 4 20 mA HART wiring Do not connect the power signal wiring to the test terminals Voltage may burn out the reverse polarity protection diode in the test connection RL 250 Power Supply ...

Страница 34: ...24 Reference Manual 00809 0100 4001 Rev JA Section 2 Installation November 2012 Installation Figure 2 17 1 5 Vdc low power wiring Power Supply Voltmeter ...

Страница 35: ... with a drip loop Arrange the drip loop so the bottom is lower than the conduit connections and the transmitter housing Power supply for 4 20 mA HART Transmitter operates on 10 5 42 4 Vdc The dc power supply should provide power with less than two percent ripple Note A minimum loop resistance of 250 ohms is required to communicate with a Field Communicator If a single power supply is used to power...

Страница 36: ...d in static discharges or induced switching transients However high energy transients such as those induced in wiring from nearby lightning strikes can damage the transmitter The transient protection terminal block can be ordered as an installed option Option Code T1 in the transmitter model number or as a spare part to retrofit existing 3051 transmitters in the field See Spare parts on page 164 f...

Страница 37: ...perly grounded Use the guidelines to ground the transmitter case Refer to page 27 Do not run the transient protection ground wire with signal wiring as the ground wire may carry excessive current if a lightning strike occurs 2 9 4 Grounding Use the following techniques to properly ground the transmitter signal wiring and case Power Supply Voltmeter DP Trim shield and insulate Insulate Shield Conne...

Страница 38: ...y is a recommended grounding point For 1 5 Vdc HART Low Power output the power wires may be grounded at only one point or left ungrounded The negative terminal of the power supply is a recommended grounding point Transmitter case Always ground the transmitter case in accordance with national and local electrical codes The most effective transmitter case grounding method is a direct connection to e...

Страница 39: ...stalled in accordance with all applicable codes and standards to maintain these certified ratings Refer to Hazardous locations certifications on page 177 for information on these approvals 2 11 Rosemount 305 306 and 304 manifolds The 305 Integral Manifold is available in two designs Traditional and Coplanar The traditional 305 Integral Manifold can be mounted to most primary elements with mounting...

Страница 40: ...anual 00809 0100 4001 Rev JA Section 2 Installation November 2012 Installation Figure 2 24 Manifolds 3051C AND 305 INTEGRAL COPLANAR 3051C AND 305 INTEGRAL TRADITIONAL 3051T AND 306 IN LINE 3051C AND 304 CONVENTIONAL ...

Страница 41: ...ed the flange bolts should be re tightened after installation to compensate for cold flow of the o rings Note Always perform a zero trim on the transmitter manifold assembly after installation to eliminate mounting effects 2 11 2 Rosemount 306 integral manifold installation procedure The 306 Manifold is for use only with a 3051T In line transmitter Assemble the 306 Manifold to the 3051T In line tr...

Страница 42: ...t ports will be open and the equalizing valve will be closed Drain Vent Valve Equalize closed Process Isolate closed Isolate open H L 1 To zero the 3051 close the block valve to the low pressure downstream side of the transmitter first Drain Vent Valve Drain Vent Valve Drain Vent Valve Equalize open Process Isolate closed Isolate open H L 2 Open the center equalize valve to equalize the pressure o...

Страница 43: ...alve on the low pressure side of the transmitter to return the transmitter to service Test Plugged Test Plugged Equalize closed Process Isolate open Isolate open H L In normal operation the two block valves between the process and instrument ports will be open and the equalizing valves will be closed Process Equalize closed Drain Vent closed Test Plugged Test Plugged Equalize closed Process Isolat...

Страница 44: ... Plugged Equalize closed Process Isolate closed Isolate open H L 2 Open the equalize valve on the high pressure upstream side of the transmitter Process Equalize open Drain Vent closed 3 Open the equalize valve on the low pressure downstream side of the transmitter The manifold is now in the proper configuration for zeroing the transmitter Test Plugged Test Plugged Equalize open Process Isolate cl...

Страница 45: ... gravity multiplied by the liquid height plus the vessel pressure equals the pressure at the bottom of the vessel To measure true level the vessel pressure must be subtracted from the vessel bottom pressure To do this make a pressure tap at the top of the vessel and connect this to the low side of the transmitter Vessel pressure is then equally applied to both the high and low sides of the transmi...

Страница 46: ...essure transmitter can be used in open vessels This system consists of an air supply pressure regulator constant flow meter pressure transmitter and a tube that extends down into the vessel Bubble air through the tube at a constant flow rate The pressure required to maintain flow equals the liquid s specific gravity multiplied by the vertical height of the liquid above the tube opening Figure 2 27...

Страница 47: ... and the transmitter datum line 600 in Let SG1 equal the specific gravity of the fluid 1 0 Let SG2 equal the specific gravity of the fluid in the wet leg 1 1 Let h equal the maximum head pressure to be measured in inches of water Let e equal the head pressure produced by Y expressed in inches of water Let s equal head pressure produced by z expressed in inches of water Let Range equal e s to h e s...

Страница 48: ...ent example mA dc Let X equal the vertical distance between the minimum and maximum measurable levels 100 in Let SG equal the specific gravity of the fluid 1 1 Let h equal the maximum head pressure to be measured in inches of water Let Range equal zero to h Then h X SG 100 x 1 1 110 inH2O Range 0 to 110 inH2O 20 inH2O 0 4 110 T AIR X ...

Страница 49: ... section contains information on commissioning and tasks that should be performed on the bench prior to installation Field Communicator and AMS Device Manager instructions are given to perform configuration functions For convenience Field Communicator fast key sequences are labeled Fast Keys for each software function below the appropriate headings 3 2 Safety messages Procedures and instructions i...

Страница 50: ...es are implemented when the Apply button is clicked 3 3 1 Setting the loop to manual Whenever sending or requesting data that would disrupt the loop or change the output of the transmitter set the process application loop to manual The Field Communicator or AMS Device Manager will prompt you to set the loop to manual when necessary Acknowledging this prompt does not set the loop to manual The prom...

Страница 51: ... on the transmitter terminal block or across the load resistor Connecting across the TEST terminals will prevent successful communication for 4 20 mA HART output Turn on the Field Communicator by pressing the ON OFF key or log into AMS Device Manager The Field Communicator or AMS Device Manager will search for a HART compatible device and indicate when the connection is made If the Field Communica...

Страница 52: ... the configuration data AMS device manager Right click on the device and select Configuration Properties from the menu Select the tabs to review the transmitter configuration data 3 5 Field communicator Version 1 8 Traditional 4 20 mA Fast Keys 1 5 Traditional 1 5 Vdc Fast Keys 1 5 Device Dashboard Fast Keys 1 7 Transmitter Model Type Tag Range Date Descriptor Message Minimum and Maximum Sensor Li...

Страница 53: ...nicator user interface Figure 3 3 Traditional interface The corresponding Menu Trees can be viewed on page 44 and page 45 The fast key sequence can be viewed on page 48 Figure 3 4 Device dashboard The corresponding Menu Trees can be viewed on page 46 through page 48 The fast key sequence can be viewed on page 50 ...

Страница 54: ... Reference Manual 00809 0100 4001 Rev JA Section 3 Configuration November 2012 Configuration 3 6 Field communicator menu trees Figure 3 5 Rosemount 3051 traditional HART menu tree for 4 20 mA HART output ...

Страница 55: ...45 Reference Manual 00809 0100 4001 Rev JA Section 3 Configuration November 2012 Configuration Figure 3 6 Rosemount 3051 traditional HART menu tree for 1 5 Vdc low power ...

Страница 56: ...Security Identification 1 Tag 2 Model 3 Transmitter S N 4 Date 5 Descriptor 6 Message HART 1 Universal Revision 2 Field Device Revision 3 Hardware Revision 4 Software Revision Materials of Construction 1 Sensor Config 2 Sensor Range 3 Upper Sensor Limits 4 Lower Sensor Limits 5 Isolator Material 6 Fill Fluid 7 Process Connection 8 Process Connection Matl 9 O ring Material Drain Vent Material RS Ma...

Страница 57: ...put 4 Percent of Range 5 Upper Sensor Limits 6 Lower Sensor Limits 7 Minimum Span 8 Range by Applying Pressure Display 1 Display Option 2 Decimal Places 3 Upper Range Value 4 Lower Range Value 5 Transfer Function 6 Units HART 1 Burst Mode 2 Burst Option 3 Polling Address Device Information 1 Identification 2 Flange 3 Remote Seal Security 1 Write Protect Status 2 Local Zero Span Burst Option PV ran...

Страница 58: ...Analog Output Alarm Type 1 4 3 2 4 1 4 3 2 4 Burst Mode Control 1 4 3 3 3 1 4 3 3 3 Burst Operation 1 4 3 3 4 1 4 3 3 4 Custom Meter Configuration 1 3 7 2 N A Home 1 Overview 2 Configure 3 Service Tools Service Tools 1 Alerts 2 Variables 3 Trends 4 Maintenance 5 Simulate Variables 1 Variable Summary 2 Pressure 3 Analog Output 4 Sensor Temperature Trends 1 Pressure 2 Sensor Temperature Maintenance ...

Страница 59: ... 1 3 4 3 Meter Options 1 4 3 4 N A Number of Requested Preambles 1 4 3 3 2 1 4 3 3 2 Poll Address 1 4 3 3 1 1 4 3 3 1 Poll a Multidropped Transmitter Left Arrow 4 1 1 Left Arrow 4 1 1 Range Values 1 3 3 1 3 3 Rerange 1 2 3 1 1 2 3 1 Scaled D A Trim 4 20 mA Output 1 2 3 2 2 1 2 3 2 2 Self Test Transmitter 1 2 1 1 1 2 1 1 Sensor Info 1 4 4 2 1 4 4 2 Sensor Temperature 1 1 4 1 1 4 Sensor Trim Points ...

Страница 60: ...1 7 5 Analog Output Alarm Type 1 7 5 Burst Mode Control 2 2 4 1 Burst Option 2 2 4 2 Custom Display Configuration 2 2 3 Damping 2 2 1 2 Date 2 2 6 1 4 Descriptor 2 2 6 1 5 Digital to Analog Trim 4 20 mA Output 3 4 2 Disable Zero Span Adjustment 2 2 5 2 Field Device Information 2 2 6 Loop Test 3 5 1 Lower Sensor Trim 3 4 1 2 Message 2 2 6 1 6 Poll Address 2 2 4 3 Range Values 1 5 Rerange with Keypa...

Страница 61: ...ect Process Variables from the menu The Process Variable screen displays the following process variables Pressure Percent of range Analog output 3 8 2 Sensor temperature The 3051 contains a temperature sensor near the pressure sensor in the sensor module When reading this temperature keep in mind the sensor is not a process temperature reading Field communicator Enter the fast key sequence Sensor ...

Страница 62: ...nd Square Root Activate the square root output option to make analog output proportional to flow As input approaches zero the 3051 automatically switches to linear output in order to ensure a more smooth stable output near zero see Figure 3 10 For 4 20 mA HART output the slope of the curve is unity y x from 0 to 0 6 percent of the ranged pressure input This allows accurate calibration near zero Gr...

Страница 63: ...m the square root extraction in the system 3 9 3 Rerange The Range Values command sets each of the lower and upper range analog values 4 and 20 mA points and 1 and 5 Vdc points to a pressure The lower range point represents 0 of range and the upper range point represents 100 of range In practice the transmitter range values may be changed as often as necessary to reflect changing process requireme...

Страница 64: ...nd span buttons option D4 Note If the transmitter security switch is ON adjustments to the zero and span will not be able to be made Refer to Configure security and alarm on page 20 for security information Rerange with a Field Communicator or AMS Device Manager Only The easiest and most popular way to rerange is to use the Field Communicator only This method changes the range values of the analog...

Страница 65: ...ator and applied pressure is a way of reranging the transmitter when specific 4 and 20 mA points 1 and 5 Vdc points are not calculated Note The span is maintained when the 4 mA point 1 Vdc point is set The span changes when the 20 mA point 5 Vdc point is set If the lower range point is set to a value that causes the upper range point to exceed the sensor limit the upper range point is automaticall...

Страница 66: ...0 mA 1 and 5 Vdc points are not known and a communicator is not available Note When you set the 4 mA 1 Vdc point the span is maintained when you set the 20 mA 5 Vdc point the span changes If you set the lower range point to a value that causes the upper range point to exceed the sensor limit the upper range point is automatically set to the sensor limit and the span is adjusted accordingly To rera...

Страница 67: ...ich increases the response time of the transmitter smoothing variations in output readings caused by rapid input changes Determine the appropriate damping setting based on the necessary response time signal stability and other requirements of the loop dynamics within your system The default damping value is 0 4 seconds and it can be set to any of ten pre configured damping values between 0 and 25 ...

Страница 68: ...ated diagnostic messages A display cover is provided to accommodate the display For 4 20 mA HART output the LCD display features a two line display The first line of five characters displays the actual measured value the second line of six characters displays the engineering units The LCD can also display diagnostic messages Refer to Figure 3 12 For 1 5 Vdc HART Low Power output the LCD display fe...

Страница 69: ... Local Display tab locate the Meter Type area Select the desired options to suit your application needs click Apply 2 An Apply Parameter Modification screen appears enter desired information and click OK 3 After carefully reading the warning provided select OK 3 10 2 Custom display configuration 4 20 mA HART only The user configurable scale is a feature that enables the LCD display to display flow...

Страница 70: ... Note Make sure the selection has been sent and the decimal point has changed before proceeding to the next step b SEND 4 To specify a custom upper range value a Select 2 CM Upper Value Type the value that you want the transmitter to read at the 20 mA point b SEND 5 To specify a custom lower range value a Select 3 CM Lower Value Type the value that you want the transmitter to read at the 4 mA poin...

Страница 71: ...Configure security and alarm on page 20 Table 3 3 4 20 mA HART alarm and saturation values Table 3 4 NAMUR Compliant alarm and saturation values Table 3 5 1 5 Vdc HART low power alarm and saturation values Caution Alarm level values will be affected by analog trim Refer to Analog output trim on page 77 Note When a transmitter is in an alarm condition the Field Communicator indicates the analog out...

Страница 72: ...perature is sent with a status bit set Saturation Primary variable is sent normally Temperature is sent normally 3 11 4 Alarm level verification If the transmitter electronics board sensor module or LCD display is repaired or replaced verify the transmitter alarm level before returning the transmitter to service This feature is also useful in testing the reaction of the control system to a transmi...

Страница 73: ...T prompt select 1 4mA 1 Vdc select 2 20mA 5 Vdc or select 3 Other to manually input a value a If you are performing a loop test to verify the output of a transmitter enter a value between 4 and 20 mA 1 and 5 Vdc b If you are performing a loop test to verify alarm levels enter the value representing an alarm state see Tables 3 3 3 4 and 3 5 on page 61 5 Check that the reference meter displays the c...

Страница 74: ...ed to the wrong loop there may be a fault in the wiring or power supply the transmitter may require an output trim or the reference meter may be malfunctioning After completing the test procedure the display returns to the Loop Test screen to choose another output value or to end loop testing 6 Select End and click Next to end loop testing 7 Select Next to acknowledge the loop can be returned to a...

Страница 75: ...d Communicator menu appears 5 Select 1 Offline 2 Saved Configuration 1 Module Contents to reach the MODULE CONTENTS menu 6 Use the DOWN ARROW to scroll through the list of configurations in the memory module and use the RIGHT ARROW to select and retrieve the required configuration 7 Select 1 Edit 8 Select 1 Mark All 9 Select SAVE 10 Use the DOWN ARROW to scroll through the list of configurations i...

Страница 76: ...om AMS Device Manager Explorer or Device Connection View into the User Configurations window The Compare Configurations window appears showing the Current values of the copied device on one side and mostly blank fields on the other User Configuration side 6 Transfer values from the current configuration to the user configuration as appropriate or enter values by typing the values into the availabl...

Страница 77: ...ynamic data pressure and temperature in engineering units pressure in percent of range and or analog output and does not affect the way other transmitter data is accessed Access to information other than dynamic transmitter data is obtained through the normal poll response method of HART communication A Field Communicator AMS Device Manager or the control system may request any of the information ...

Страница 78: ...d in the HART protocol Field Communicators and AMS Device Manager can test configure and format a multidropped transmitter the same way as a transmitter in a standard point to point installation Figure 3 13 shows a typical multidrop network This figure is not intended as an installation diagram Note A transmitter in multidrop mode has the analog output fixed at 4 mA If an LCD display is installed ...

Страница 79: ...r Field communicator To communicate with a multidropped transmitter configure the Field Communicator to poll for a non zero address 1 From the HOME screen enter the fast key sequence Communicating with a Multidropped Transmitter 2 On the polling menu scroll down and select Digital Poll In this mode the Field Communicator automatically polls for devices at addresses 0 15 upon start up AMS device ma...

Страница 80: ...onfiguration November 2012 Configuration Field communicator AMS device manager Click on the HART modem icon and select Scan All Devices Traditional 4 20 mA Fast Keys Left arrow 4 1 Traditional 1 5 Vdc Fast Keys Left arrow 4 1 Device Dashboard Fast Keys 1 2 ...

Страница 81: ...1 Pressure Transmitters Field Communicator and AMS instructions are given to perform configuration functions For convenience Field Communicator fast key sequences are labeled Fast Keys for each software function below the appropriate headings 4 2 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operatio...

Страница 82: ...r characterization curve due to a change in the sensor characteristics over time or a change in test equipment Trimming has two steps zero and sensor trims Refer to page 82 and page 83 Zero Trim page 82 Sensor Trim page 83 Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and int...

Страница 83: ...in the microprocessor to obtain a digital representation of the process input Digital PV 4 The Digital PV is converted to an analog value Digital to Analog Signal Conversion Rerange and Analog trim functions affect this value Select these options to change the range points 4 20 mA or 1 5 Vdc For a summary of recommended calibration procedures refer to Table 4 1 on page 4 74 Also Figure 4 1 on page...

Страница 84: ...determine calibration frequency that meets the needs of your application Transmitter Bench calibration tasks Field calibration tasks 3051CD 3051CG 3051L 3051TG Range 1 4 1 Set output configuration parameters a Set the range points b Set the output units c Set the output type d Set the damping value 2 Optional Perform a sensor trim Accurate pressure source required 1 Reconfigure parameters if neces...

Страница 85: ... P8 option 0 04 accuracy 5 year stability Step 1 Determine the performance required for your application Required Performance 0 30 of span Transmitter 3051CD Range 2 URL 250 inH2O 623 mbar Calibrated Span 150 inH2O 374 mbar Ambient Temperature Change 50 F 28 C Line Pressure 500 psig 34 5 bar TPE 0 117 of span Where Reference Accuracy 0 065 of span Ambient Temperature Effect Span Static Pressure Ef...

Страница 86: ... equal to the upper range point pressure 4 Compare the applied pressure to the pressure process variable valve on the Process Variables menu on the Field Communicator or the Process Variables screen in AMS For instructions on how to access process variables see page 51 of Section 3 Configuration Transmitter 3051CD Range 2 URL 250 inH2O 623 mbar Calibrated Span 150 inH2O 374 mbar Ambient Temperatur...

Страница 87: ...h the digital readout device with high accuracy test equipment perform an analog output trim See Analog output trim on page 77 4 4 Analog output trim The Analog Output Trim commands allow you to adjust the transmitter s current output at the 4 and 20 mA 1 and 5 Vdc points to match the plant standards This command adjusts the digital to analog signal conversion Figure 4 2 Output trim 4 4 1 Digital ...

Страница 88: ...e Vout terminal 3 Select OK after connecting the reference meter 4 Select OK at the SETTING FLD DEV OUTPUT TO 4 MA 1 Vdc prompt The transmitter outputs 4 0 mA 5 Record the actual value from the reference meter and enter it at the ENTER METER VALUE prompt The Field Communicator prompts you to verify whether or not the output value equals the value on the reference meter 6 Select 1 Yes if the refere...

Страница 89: ...smitter output value 8 Select Next to acknowledge the loop can be returned to automatic control 9 Select Finish to acknowledge the method is complete 4 4 2 Digital to Analog trim using other scale The Scaled D A Trim command matches the 4 and 20 mA 1 and 5 Vdc points to a user selectable reference scale other than 4 and 20 mA for example 2 to 10 volts if measuring across a 500 ohm load or 0 to 100...

Страница 90: ...es if the reference meter value equals the transmitter output value or No if it does not Click Next a If Yes is selected proceed to Step 10 b If No is selected repeat Step 8 10 Click Next at the Setting fld dev output to 20 mA screen 11 Repeat Step 8 Step 9 until the reference meter equals the transmitter output value 12 Select Next to acknowledge the loop can be returned to automatic control 13 S...

Страница 91: ...d in its final mounting position Since this correction maintains the slope of the characterization curve it should not be used in place of a sensor trim over the full sensor range When performing a zero trim ensure that the equalizing valve is open and all wet legs are filled to the correct levels Note Do not perform a zero trim on Rosemount 3051T Absolute pressure transmitters Zero trim is zero b...

Страница 92: ...asurement loop 2 From the HOME screen follow the fast key sequence Zero Trim 3 Follow the commands provided by the Field Communicator to complete the zero trim adjustment AMS Device Manager Right click on the device and select Calibrate then Zero trim from the menu 1 Click Next after setting the control loop to manual 2 Click Next to acknowledge warning 3 Click Next after applying appropriate pres...

Страница 93: ...or trim value should be the sensor trim point that is closest to zero Examples Calibration 0 to 100 H2O lower trim 0 upper trim 100 Calibration 100 to 0 H2O lower trim 0 upper trim 100 Calibration 100 to 100 H2O lower trim 100 or 100 upper trim 100 or 100 Note Select pressure input values so that lower and upper values are equal to or outside the 4 and 20 mA 1 and 5 Vdc points Do not attempt to ob...

Страница 94: ...oration of the as shipped factory settings of the sensor trim This command can be useful for recovering from an inadvertent zero trim of an absolute pressure unit or inaccurate pressure source This command is only available with 4 20 mA output Field communicator AMS Device Manager Right click on the device and select Calibrate then Recall Factory Trim from the menu 1 Click Next after setting the c...

Страница 95: ... by performing the Sensor Trim procedure on page 83 The following specifications show the static pressure effect for 3051 Range 4 and Range 5 transmitters used in differential pressure applications Zero Effect 0 1 of the upper range limit per 1000 psi 69 bar for line pressures from 0 to 2000 psi 0 to 138 bar For line pressures above 2000 psi 138 bar the zero effect error is 0 2 of the upper range ...

Страница 96: ...Value HT URV S 100 x P 1000 x URV In this example Complete the Sensor Trim procedure as described on page 83 In the example above at step 4 apply the nominal pressure value of 500 inH2O However enter the calculated correct lower trim LT value of 506 inH2O with the Field Communicator Repeat the procedure for the upper value Where LT Corrected Low Trim Value LRV Lower Range Value S Span shift per sp...

Страница 97: ...nance Note The range values for the 4 and 20 mA 1 and 5 Vdc points should be at the nominal URV and LRV In the example above the values are 1500 inH2O and 500 inH2O respectively Confirm the values on the HOME screen on the Field Communicator Modify if needed by following the steps in the Rerange section on page 53 ...

Страница 98: ...88 Reference Manual 00809 0100 4001 Rev JA Section 4 Operation and Maintenance November 2012 Operation and maintenance ...

Страница 99: ...the most common operating problems If you suspect malfunction despite the absence of any diagnostic messages on the Field Communicator display consider using Table 5 1 on page 5 91 to identify any potential problem 5 2 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises p...

Страница 100: ...sociated with a safe installation Before connecting a Field Communicator in an explosive atmosphere ensure the instruments in the loop are installed in accordance with intrinsically safe or non incendive field wiring practices In an Explosion Proof Flameproof installation do not remove the transmitter covers when power is applied to the unit Process leaks may cause harm or result in death Install ...

Страница 101: ... not in alarm condition Verify if 4 20 mA output trim is required Transmitter will not respond to changes in applied pressure Check test equipment Check impulse piping or manifold for blockage Verify the transmitter is not in multidrop mode Verify applied pressure is between the 4 and 20 mA set points Verify output is not in alarm condition Verify transmitter is not in Loop Test mode Digital Press...

Страница 102: ...ure or temperature updates are not being received in the sensor module A non volatile memory fault that will effect transmitter operation has been detected in the module by the memory verification routine Some non volatile memory faults are user repairable Use a Field Communicator to diagnose the error and determine if it is repairable Any error message that ends in FACTORY is not repairable In ca...

Страница 103: ...he memory verification routine The memory fault is in a location containing transmitter information To correct this problem use a Field Communicator to interrogate and reconfigure the appropriate portion of the transmitter memory This warning does not effect the transmitter operation Operation Normal operation messages appear on the LCD meter to confirm actions or inform you of transmitter status ...

Страница 104: ...rmation about the security jumper Field communicator diagnostics Table 5 2 is a list of messages used by the Field Communicator HC and their corresponding descriptions Variable parameters within the text of a message are indicated with variable parameter Reference to the name of another message is identified by another message Table 5 2 Field communicator messages Message Description 1k snsr EEPRO...

Страница 105: ... Device write protected Device is in write protect mode Data can not be written Device write protected Do you still want to shut off Device is in write protect mode Press YES to turn the Field Communicator off and lose the unsent data Display value of variable on hotkey menu Asks whether the value of the variable should be displayed adjacent to its label on the hotkey menu if the item being added ...

Страница 106: ...ing received from the sensor module Verify that the sensor module ribbon cable is attached correctly Or replace the transmitter No UPLOAD_VARIABLES in ddl for this device There is no menu named upload_variables defined in the device description for this device This menu is required for offline configuration No Valid Items The selected menu or edit display contains no valid items OFF KEY DISABLED A...

Страница 107: ...be sent The engineering units for this variable have been edited Send engineering units to the device before editing this variable Unsent data to online device SEND or LOSE data There is unsent data for a previously connected device which must be sent or thrown away before connecting to another device Upgrade 275 software to access XMTR function Continue with old description The communicator does ...

Страница 108: ...bolts and separate the transmitter from the process connection Leave the process connection in place and ready for re installation The Rosemount 3051T transmitter is attached to the process by a single hex nut process connection Loosen the hex nut to separate the transmitter from the process Do not wrench on neck of transmitter Do not scratch puncture or depress the isolating diaphragms Clean isol...

Страница 109: ...ptive screws that anchor the board to the housing The electronics board is electrostatically sensitive observe handling precautions for static sensitive components Use caution when removing the LCD as there is an electronic pin connector that interfaces between the LCD and electronics board The two screws anchor the LCD display to the electronics board and the electronics board to the housing 4 Us...

Страница 110: ... the module clockwise into the housing Important Make sure the sensor ribbon cable and internal black cap remain completely free of the housing as you rotate it Damage can occur to the cable if the internal black cap and ribbon cable become hung up and rotate with the housing 5 Thread the housing completely onto the sensor module The housing must be no more than one full turn from flush with the s...

Страница 111: ...gs 2 Install the process connection Possible options include a Coplanar Process Flange Hold the process flange in place by installing the two alignment screws to finger tightness screws are not pressure retaining Do not overtighten as this will affect module to flange alignment Install the four 1 75 in flange bolts by finger tightening them to the flange b Coplanar Process Flange with Flange Adapt...

Страница 112: ...C for two hours before calibration 5 5 4 Install the drain vent valve 1 Apply sealing tape to the threads on the seat Starting at the base of the valve with the threaded end pointing toward the installer apply two clockwise turns of sealing tape 2 Tighten the drain vent valve to 250 in lb 28 25 N m 3 Take care to place the opening on the valve so that process fluid will drain toward the ground and...

Страница 113: ...age 108 Physical specifications page 116 Dimensional Drawings page 120 Ordering Information page 131 Options page 156 Spare parts page 164 A 1 Performance specifications This product data sheet covers both HART and fieldbus protocols unless specified A 1 1 Conformance to specification 3 Sigma Technology leadership advanced manufacturing techniques and statistical process control ensure specificati...

Страница 114: ... than 15 1 accuracy Ranges 2 5 0 065 of span For spans less than 10 1 accuracy Ranges 2 4 High Accuracy Option P8 0 04 of span For spans less than 5 1 accuracy 3051T Ranges 1 4 0 065 of span For spans less than 10 1 accuracy Ranges 1 4 High Accuracy Option P8 0 04 of span For spans less than 5 1 accuracy Range 5 0 075 of span 3051CA Ranges 1 4 0 065 of span For spans less than 10 1 accuracy Ranges...

Страница 115: ...51C Ranges 2 5 Range 1 Range 0 3051T 3051H L 100 ms 255 ms 700 ms 100 ms Consult factory 152 ms 307 ms 752 ms 152 ms Consult factory Dead Time Td 45 ms nominal 97 ms Update Rate 22 times per second 22 times per second 1 Dead time and update rate apply to all models and ranges analog output only 2 Nominal total response time at 75 F 24 C reference conditions 3 Transmitter fieldbus output only segme...

Страница 116: ...n from 1 1 to 5 1 0 025 URL 0 125 span from 5 1 to 100 1 3051T Range 1 0 025 URL 0 125 span from 1 1 to 10 1 0 05 URL 0 125 span from 10 1 to 100 1 Range 2 4 0 025 URL 0 125 span from 1 1 to 30 1 0 035 URL 0 125 span from 30 1 to 100 1 Range 5 0 1 URL 0 15 span 3051CA All Ranges 0 025 URL 0 125 span from 1 1 to 30 1 0 035 URL 0 125 span from 30 1 to 100 1 3051H All Ranges 0 025 URL 0 125 span 0 35...

Страница 117: ...wer supply effect Less than 0 005 of calibrated span per volt A 1 11 Electromagnetic compatibility EMC Meets all relevant requirements of EN 61326 and NAMUR NE 21 A 1 12 Transient protection option code T1 Meets IEEE C62 41 Category Location B 6 kV crest 0 5 s 100 kHz 3 kV crest 8 20 microseconds 6 kV crest 1 2 50 microseconds ...

Страница 118: ...G 3051L and 3051H range and sensor limits Range Minimum span 3051CD 1 CG L H 1 Range 0 only available with 3051CD Range 1 only available with 3051CD or 3051CG Upper URL 0 0 1 inH2O 0 25 mbar 3 0 inH2O 7 47 mbar 1 0 5 inH2O 1 2 mbar 25 inH2O 62 3 mbar 2 2 5 inH2O 6 2 mbar 250 inH2O 0 62 bar 3 10 inH2O 24 9 mbar 1000 inH2O 2 49 bar 4 3 psi 0 20 bar 300 psi 20 6 bar 5 20 psi 1 38 bar 2000 psi 137 9 b...

Страница 119: ... 5 psia 34 5 mbar abs 1000inH2O 2 49 bar 0 5 psia 34 5 mbar abs 4 300 psi 20 6 bar 0 5 psia 34 5 mbar abs 300 psi 20 6 bar 0 5 psia 34 5 mbar abs 300 psi 20 6 bar 0 5 psia 34 5 mbar abs 5 2000 psi 137 9 bar 0 5 psia 34 5 mbar abs NA NA 2000 psi 137 9 bar 0 5 psia 34 5 mbar abs Table A 3 Range and sensor limits 3051CA Range 3051T Range Minimum span Range and sensor limits Minimum span Range and sen...

Страница 120: ...ansmitter 4 20 mA operates on 10 5 to 55 Vdc with no load Load Limitations Maximum loop resistance is determined by the voltage level of the external power supply as described by A 2 5 FOUNDATION fieldbus output code F and Profibus output code W Power Supply External power supply required transmitters operate on 9 0 to 32 0 Vdc transmitter terminal voltage Current Draw 17 5 mA for all configuratio...

Страница 121: ...ll factory defaults LCD Block Configures the local display 2 Analog Input Blocks Processes the measurements for input into other function blocks The output value is in engineering units or custom and contains a status indicating measurement quality PID Block Contains all logic to perform PID control in the field including cascade and feedforward Block Execution Time Resource Transducer LCD Block A...

Страница 122: ...ock Compares the integrated or accumulated value from one or two variables to pre trip and trip limits and generates discrete output signals when the limits are reached This block is useful for calculating total flow total mass or volume over time A 2 11 FOUNDATION fieldbus Diagnostics Suite Option Code D01 The 3051C FOUNDATION fieldbus Diagnostics provide Abnormal Situation Prevention ASP indicta...

Страница 123: ...sig 250 bar 4500 psig 310 3 bar for option code P9 Rosemount 3051CA Range 1 750 psia 51 7 bar Range 2 1500 psia 103 4 bar Range 3 1600 psia 110 3 bar Range 4 6000 psia 413 7 bar Rosemount 3051H All Ranges 3626 psig 25 MPa Rosemount 3051TG TA Range 1 750 psi 51 7 bar Range 2 1500 psi 103 4 bar Range 3 1600 psi 110 3 bar Range 4 6000 psi 413 7 bar Range 5 15000 psi 1034 2 bar For 3051L or Level Flan...

Страница 124: ...Code A If self diagnostics detect a gross transmitter failure the analog signal will be driven either below 3 75 mA or to 21 75 mA to alert the user NAMUR compliant values are available option code C4 High or low alarm signal is user selectable by internal jumper Output Code M If self diagnostics detect a gross transmitter failure the analog signal will be driven either below 0 94 V or above 5 4 V...

Страница 125: ...may not be readable and LCD updates will be slower at temperatures below 4 F 20 C 3051CD 3051CG 3051CA Silicone Fill Sensor 1 with Coplanar Flange 40 to 250 F 40 to 121 C 2 with Traditional Flange 40 to 300 F 40 to 149 C 2 3 with Level Flange 40 to 300 F 40 to 149 C 2 with 305 Integral Manifold 40 to 300 F 40 to 149 C 2 Inert Fill Sensor 1 40 to 185 F 40 to 85 C 4 5 3051H process fill fluid D C Si...

Страница 126: ...HART interface connections fixed to terminal block A 3 2 Process Connections All Models except 3051L and 3051T 1 4 18 NPT on 21 8 in centers 1 2 14 NPT on 2 21 8 or 21 4 in centers 3051L high side temperature limits process fill fluid Syltherm XLT 100 to 300 F 73 to 149 C D C Silicone 704 32 to 400 F 0 to 205 C D C Silicone 200 40 to 400 F 40 to 205 C Inert 50 to 350 F 45 to 177 C Glycerin and Wat...

Страница 127: ... thread 1 4 OD high pressure tube 60 cone available in SST for Range 5 transmitters only A 3 3 Process Wetted Parts Drain Vent Valves Process Flanges and Adapters Plated carbon steel SST CF 8M Cast 316 SST per ASTM A743 Cast C 276 CW 12MW per ASTM A494 Cast Alloy 400 M 30C per ASTM A494 Wetted O rings Glass filled PTFE or Graphite filled PTFE Process Isolating Diaphragms 316 SST Alloy C 276 or All...

Страница 128: ...apter CF 8M Cast version of 316 SST material per ASTM A743 A 3 5 Non Wetted Parts Electronics Housing Low copper aluminum or SST CF 3M or CF 8M Cast version of 316L or 316 SST material per ASTM A743 NEMA 4X IP 65 IP 66 Coplanar Sensor Module Housing CF 3M Cast version of 316L SST material per ASTM A743 Bolts ASTM A449 Type 1 zinc cobalt plated carbon steel ASTM F593G Condition CW1 Austenitic 316 S...

Страница 129: ...rence Manual 00809 0100 4001 Rev JA Appendix A Reference Data November 2012 Specifications and reference data Paint Polyurethane Cover O rings Buna N A 3 6 Shipping Weights Refer to Shipping weights on page 159 ...

Страница 130: ...andard Electronics Housing Terminal Block Cover O ring Cover Electronics Board Nameplate Sensor Module Housing Rotation Set Screw 180 Maximum Housing Rotation without Further Disassembly Flange Alignment Screw Not Pressure Retaining Flange Bolts Flange Adapters Drain Vent Valve Coplanar Flange Flange Adapter O Ring Process O Ring 1 Span and Zero Adjustments are not available with fieldbus or profi...

Страница 131: ...ppendix A Reference Data November 2012 Specifications and reference data 3051C Coplanar Flange 3051C Coplanar Flange with Rosemount 305 Coplanar Integral Manifold 8 2 209 4 1 105 6 4 163 4 3 110 5 0 127 7 54 192 5 5 140 Max Open 10 60 270 Max Open ...

Страница 132: ...Configurations with Optional Bracket B4 for 2 in Pipe or Panel Mounting PANEL MOUNTING PIPE MOUNTING Dimensions are in inches millimeters 4 3 110 2 8 72 7 1 181 2 8 71 6 2 156 4 8 120 1 1 28 5 16 11 2 Bolts for Panel Mounting Not Supplied 3 8 16 11 4 Bolts for Mounting to Transmitter 2 8 71 3 4 85 6 0 152 3 3 83 2 inch U Bolt for Pipe Mounting ...

Страница 133: ...ons are in inches millimeters 3051C Coplanar with Rosemount 305 Traditional Integral Manifold Dimensions are in inches millimeters 1 1 28 3 5 87 1 1 28 Drain Vent Valve 1 2 14 NPT Flange Adapter Optional 7 9 201 1 63 41 2 126 54 1 1 28 3 5 87 1 1 28 Drain Vent Valve 1 2 14 NPT Flange Adapter Optional 6 25 159 3 63 92 8 9 266 6 2 158 Max Open 2 7 69 Max Open 2 1 54 ...

Страница 134: ...for 2 in Pipe or Panel Mounting Panel Mounting Bracket option B2 B8 2 in Pipe Mounting Bracket option B1 B7 BA 2 in Pipe Mounting Bracket option B3 B9 BC 9 2 235 2 7 67 6 2 158 PANEL MOUNTING BRACKET 2 81 71 5 16 x 7 8 Bolts for Panel Mounting Not Supplied 1 1 28 1 4 33 4 6 116 9 6 243 Impulse Piping 3 8 95 2 7 67 4 2 PIPE MOUNTING BRACKET 11 52 293 4 85 123 6 2 158 5 32 135 1 94 49 ...

Страница 135: ...0809 0100 4001 Rev JA Appendix A Reference Data November 2012 Specifications and reference data 3051T Dimensional Drawings 3051T with Rosemount 306 Integral Manifold 7 2 183 4 1 105 5 0 127 4 3 110 4 1 105 4 85 123 6 25 159 ...

Страница 136: ...ce Data November 2012 Specifications and reference data 3051T Typical Mounting Configurations with Optional Mounting Bracket Pipe Mounting Panel Mounting Dimensions are in inches millimeters 3 5 90 6 3 160 2 50 6 2 156 2 9 72 4 3 110 2 8 71 4 8 120 6 9 175 5 1 130 ...

Страница 137: ... Flange Configuring Flush Mount Only 3 and 4 in Flange Configuration Optional Flushing Connection Ring Lower Housing Diaphragm Assembly and Mounting Flange Dimensions are in inches millimeters A 4 1 104 H A Housing Rotation Set Screw Extension 2 4 or 6 51 102 or 152 E 4 1 104 D H 5 0 127 6 6 168 8 2 209 4 3 109 7 0 179 Flushing Connection E F G C B ...

Страница 138: ... 92 3 76 1 25 32 6 62 168 8 25 210 8 0 88 22 2 58 66 5 0 127 DIN 2501 PN 10 40 DN 50 20 mm 125 mm 165 mm 4 18 mm NA 4 0 102 DIN 2501 PN 25 40 DN 80 24 mm 160 mm 200 mm 8 18 mm 66 mm 5 4 138 DN 100 24 mm 190 mm 235 mm 8 22 mm 89 mm 6 2 158 DIN 2501 PN 10 16 DN 100 20 mm 180 mm 220 mm 8 18 mm 89 mm 6 2 158 Class Pipe size Process side F Lower housing G H 1 4 NPT 1 2 NPT ASME B16 5 ANSI 150 2 51 2 12...

Страница 139: ...em Sensor Module 5 0 127 4 3 110 0 75 19 Clearance for Cover Removal Transmitter Circuitry Nameplate Terminal Connections 0 75 19 Clearance for Cover Removal 1 2 18 NPT on Process Flange for Pressure Connection Without the Use of Mounting Adapters Drain Vent Valve Housing Rotation Set Screw 1 2 30 1 1 28 3 4 86 4 1 105 10 8 275 9 0 228 1 2 14 NPT on Optional Mounting Adapters Adapters Can Be Rotat...

Страница 140: ... reference data 3051H Mounting Brackets for 2 in Pipe and Panel Mount Option Code B5 B6 PIPE MOUNTING CONFIGURATION PANEL MOUNTING CONFIGURATION 7 16 20 3 4 Bolts Supplied for Attaching Bracket to Transmitter Dimensions are in inches millimeters Impulse Piping 2 7 67 0 7 16 4 4 109 Impulse Piping 2 7 67 ...

Страница 141: ...mbar 6 2 mbar 0 to 150 psia 1 5 psia 0 to 10 3 bar 0 1 bar 3 1000 to 1000 inH2O 10 inH2O 2 5 to 2 5 bar 25 mbar 393 to 1000 inH2O 10in H2O 0 98 to 2 5 bar 25 mbar 0 to 800 psia 8 psia 0 to 55 2 bar 0 55 bar 4 300 to 300 psi 3 psi 20 7 to 20 7 bar 0 2 bar 14 2 to 300 psi 3 psi 0 98 to 20 7 bar 0 2 bar 0 to 4000 psia 40 psia 0 to 275 8 bar 2 8 bar 5 2000 to 2000 psi 20 psi 137 9 to137 9 bar 1 4 bar ...

Страница 142: ...Flange See Options on page 156 Isolating Diaphragm Standard Standard 2 5 316L SST 3 5 Alloy C 276 Expanded 4 Alloy 400 5 Tantalum Available on 3051CD and CG Ranges 2 5 only Not available on 3051CA 6 Gold plated Alloy 400 Use in combination with O ring Option Code B 7 Gold plated SST O ring Standard Standard A Glass filled PTFE B Graphite filled PTFE Sensor Fill Fluid Standard Standard 1 Silicone 2...

Страница 143: ...Compliant Traditional Flange SST 1 16 in Adapter Manifold Bolting FA Level Flange SST 2 in ANSI Class 150 Vertical Mount FB Level Flange SST 2 in ANSI Class 300 Vertical Mount FC Level Flange SST 3 in ANSI Class 150 Vertical Mount FD Level Flange SST 3 in ANSI Class 300 Vertical Mount FP DIN Level Flange SST DN 50 PN 40 Vertical Mount FQ DIN Level Flange SST DN 80 PN 40 Vertical Mount Expanded HK ...

Страница 144: ...m Direct Mount Connection Type S7 6 One Seal All Welded System Capillary Connection Type S8 6 Two Seals All Welded System Capillary Connection Type S9 6 Two Seals All Welded System One Direct Mount and One Capillary Connection Type Mounting Bracket Standard Standard B1 Traditional Flange Bracket for 2 in Pipe Mounting CS Bolts B2 Traditional Flange Bracket for Panel Mounting CS Bolts B3 Traditiona...

Страница 145: ...2 combination of C6 and K8 K7 7 IECEx Flame proof Dust Ignition proof Intrinsic Safety and Type n combination of I7 N7 and E7 K8 12 ATEX Flameproof Intrinsic Safety Type n Dust combination of E8 I1 and N1 KB FM and CSA Explosion proof Dust Ignition Proof Intrinsically Safe and Division 2 combination of K5 and C6 KD 12 FM CSA and ATEX Explosion proof Intrinsically Safe combination of K5 C6 I1 and E...

Страница 146: ...ode S1 Quality Certification for Safety Standard Standard QS Certificate of FMEDA Data Zero Span Adjustment Standard Standard J1 9 10 Local Zero Adjustment Only J3 9 10 No Local Zero or Span Adjustment Transient Protection Terminal Block Standard Standard T1 Transient Protection Terminal Block Software Configuration Standard Standard C1 9 Custom Software Configuration Completed CDS 00806 0100 4001...

Страница 147: ...tandard P8 0 04 accuracy to 5 1 turndown Range 2 4 Flange Adapters Standard Standard DF 1 2 14 NPT flange adapter s D3 18 NPT Process Connections No flange adapters Hastelloy D3 18 NPT Process Connections No flange adapters Monel Vent Drain Valves Expanded D7 Coplanar Flange Without Drain Vent Ports Conduit Plug Standard Standard DO 316 SST Conduit Plug RC1 4 RC1 2 Process Connection Expanded D9 J...

Страница 148: ...ith Local Operator Interface required for local addressing and configuration 4 Not available with hazardous locations certification Options Codes I1 N1 E4 K6 and K8 5 Materials of Construction comply with recommendations per NACE MR0175 ISO 15156 for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also co...

Страница 149: ...ignal Based on HART Protocol F FOUNDATION fieldbus Protocol W 2 Profibus PA Protocol Expanded M Low Power 1 5 Vdc with Digital Signal Based on HART Protocol Process Connection Style Standard Standard 2B 1 2 14 NPT Female 2C G A DIN 16288 Male Available in SST for Range 1 4 only Expanded 2F Coned and Threaded Compatible with Autoclave Type F 250 C Includes Gland and Collar Available in SST for Rang...

Страница 150: ...ntrol Functionality Standard Standard A01 Advanced Control Function Block Suite PlantWeb Diagnostic Functionality Standard Standard D01 FOUNDATION fieldbus Diagnostics Suite Integral Assembly Standard Standard S5 4 Assemble to Rosemount 306 Integral Manifold Seal Assemblies Standard Standard S1 4 Assemble to one Rosemount 1199 seal Mounting Bracket Standard Standard B4 Bracket for 2 in Pipe or Pan...

Страница 151: ...TEX Flame proof Intrinsic Safety Type n Dust combination of E8 I1 and N1 KB FM and CSA Explosion proof Dust Ignition proof Intrinsically Safe and Division 2 combination of K5 and C6 KD 5 FM CSA and ATEX Explosion proof Intrinsically Safe combination of K5 C6 I1 and E8 N1 5 ATEX Type n Certification and Dust N3 China Type n N7 5 IECEx Type n Certification Custody Transfer Standard Standard C5 Measu...

Страница 152: ...nal Block Standard Standard T1 Transient Protection Terminal Block Software Configuration Standard Standard C1 6 Custom Software Configuration Completed CDS 00806 0100 4001 required with order Expanded C2 6 0 8 3 2 Vdc Output with Digital Signal Based on HART Protocol Output Code M only Alarm Limit Standard Standard C4 7 9 Analog Output Levels Compliant with NAMUR Recommendation NE 43 Alarm High C...

Страница 153: ... 1 3051TG lower range limit varies with atmospheric pressure 2 Option code M4 LCD Display with Local Operator Interface required for local addressing and configuration 3 Materials of Construction comply with recommendations per NACE MR0175 ISO 15156 for sour oil field production environments Environmental limits apply to certain materials Consult latest standard for details Selected materials also...

Страница 154: ...ection Size Material Extension length High Side Standard Standard Code Process Connection Size Material Extension Length G0 3 2 in DN 50 316L SST Flush Mount Only H0 3 2 in DN 50 Alloy C 276 Flush Mount Only J0 2 in DN 50 Tantalum Flush Mount Only A0 3 3 in DN 80 316L SST Flush Mount A2 3 3 in DN 80 316L SST 2 in 50 mm A4 3 3 in DN 80 316L SST 4 in 100 mm A6 3 3 in DN 80 316L SST 6 in 150 mm B0 3 ...

Страница 155: ... ASME B16 5 Class 600 CS E 3 in ANSI ASME B16 5 Class 600 CS X 3 2 in ANSI ASME B16 5 Class 150 SST F 3 3 in ANSI ASME B16 5 Class 150 SST G 3 4 in ANSI ASME B16 5 Class 150 SST Y 3 2 in ANSI ASME B16 5 Class 300 SST H 3 3 in ANSI ASME B16 5 Class 300 SST J 3 4 in ANSI ASME B16 5 Class 300 SST Z 3 2 in ANSI ASME B16 5 Class 600 SST L 3 3 in ANSI ASME B16 5 Class 600 SST Q DN 50 PN 10 40 per EN 109...

Страница 156: ...r 1 13 5 to 203 F 15 to 95 C N Neobee M 20 0 92 5 to 401 F 15 to 205 C P Propylene Glycol and Water 1 02 5 to 203 F 15 to 95 C Low Pressure Side Configuration Flange Adapter Diaphragm Material Sensor Fill Fluid Standard Standard 11 3 Gage SST 316L SST Silicone 21 3 Differential SST 316L SST Silicone 22 3 Differential SST Alloy C 276 Silicone 2A 3 Differential SST 316L SST Inert Halocarbon 2B 3 Dif...

Страница 157: ...I5 FM Intrinsically Safe Division 2 K5 FM Explosion proof Dust Ignition proof Intrinsically Safe and Division 2 I1 5 ATEX Intrinsic Safety and Dust N1 5 ATEX Type n Certification and Dust E8 ATEX Flameproof and Dust E4 5 TIIS Flameproof C6 CSA Explosion proof Dust Ignition proof Intrinsically Safe and Division 2 K6 5 CSA and ATEX Explosion proof Intrinsically Safe and Division 2 combination of C6 ...

Страница 158: ...ST Bolts L5 ASTM A 193 Grade B7M bolts L6 Alloy K 500 Bolts L8 ASTM A 193 Class 2 Grade B8M Bolts Display Type Standard Standard M4 6 LCD Display with Local Operator Interface M5 LCD Display for Aluminum Housing Housing Codes A B C and D only M6 LCD Display for SST Housing Housing Codes J K L and M only Calibration Certification Standard Standard Q4 Calibration Certificate QP Calibration Certifica...

Страница 159: ...sient Protection Terminal Block Software Configuration Standard Standard C1 8 Custom Software Configuration Completed CDS 00806 0100 4001 required with order Low Power Output Standard Standard C2 8 0 8 3 2 Vdc Output with Digital Signal Based on HART Protocol Available with Output code M only Alarm Limit Standard Standard C4 8 11 NAMUR alarm and saturation levels high alarm CN 8 11 NAMUR alarm and...

Страница 160: ...4 20 mA output output code A 8 Not available with fieldbus output code F or profibus protocols output code W 9 Local zero and span adjustments are standard unless Option Code J1 or J3 is specified 10 The T1 option is not needed with FISCO Product Certifications transient protection is included in the FISCO product certification codes IA IE IF and IG 11 NAMUR Compliant operation is pre set at the f...

Страница 161: ...3 2 Alloy C 276 5 Tantalum Code O ring Material HD HG Expanded A Glass Filled PTFE Code Process Fill Fluid HD HG Expanded D D C 200 Silicone H Inert N Neobee M 20 P Propylene glyco water Code Sensor Module Isolator Material HD HG Expanded 2 316L SST Code Sensor Module Fill Fluid HD HG Expanded 1 Silicone 2 Inert fill Halocarbon Code Housing Material Conduit Entry Size HD HG Expanded A Polyurethane...

Страница 162: ... proof Dust Ignition proof Intrinsically Safe and Division 2 E4 5 TIIS Flameproof E5 FM Explosion proof Dust Ignition proof E7 IECEx Flameproof Dust Ignition proof E8 ATEX Flameproof and Dust Certification I1 4 ATEX Intrinsic Safety and Dust I5 FM Intrinsically Safe Division 2 I7 IECEx Intrinsic Safety IA ATEX FISCO Intrinsic Safety IE FM FISCO Intrinsically Safe K5 FM Explosion proof Dust Ignitio...

Страница 163: ...nly Code Calibration Certification HD HG Expanded Q4 Calibration Certificate QG Calibration Certificate and GOST Verification Certificate QP Calibration Certificate and tamper evident seal Code Material Traceability Certification HD HG Expanded Q8 Material traceability certification per EN 10204 3 1 Code Zero Span Adjustment HD HG Expanded J1 5 6 Local Zero Adjustment Only J3 5 6 No Local Zero or ...

Страница 164: ...ng Process Area HD HG Expanded P2 Cleaning for Special Service Code Flange Adapters HD HG Expanded DF 1 2 14 NPT flange adapters SST Code Vent Drain Valves HD HG Expanded D8 Ceramic Ball Drain Vents Code Conduit Plug HD HG Expanded DO 316 SST Conduit Plug Code Ground Screw HD HG Expanded V5 8 External Ground Screw Assembly Code Bar Code Tag HD HG Expanded BT Customer Specified Barcode Tag Code Qua...

Страница 165: ...ly to certain materials Consult latest standard for details Selected materials also conform to NACE MR0103 for sour refining environments 3 Assemble to items are specified separately and require a completed model number 4 Not available with Low Power code M 5 Not available with fieldbus output code F or profibus protocols output code W 6 Local zero and span adjustments are standard unless Option C...

Страница 166: ...onfiguration Hardware Selectable Information Signal Selection Refer to the HART Protocol C1 Option Configuration Data Sheet document number 00806 0100 4001 Engineering units Differential Gage Absolute 3051T inH2O Range 0 1 2 and 3 psi Range 4 and 5 psi all ranges 4 mA 1 Vdc 1 1 Not applicable to fieldbus 0 engineering units above 20 mA 5 Vdc Upper range limit Output Linear Flange type Specified mo...

Страница 167: ...ters Refer to the following Product Data Sheet document number 00813 0100 4839 for Rosemount 304 and 00813 0100 4733 for Rosemount 305 and 306 for additional information Optional Diaphragm and Sanitary Seals Refer to Product Data Sheet 00813 0100 4016 or 00813 0201 4016 for additional information Output Information 1 Output range points must be the same unit of measure Available units of measure i...

Страница 168: ...olts L5 ASTM A 193 Grade B7M Bolts L6 Alloy K 500 Bolts Rosemount 3051C Coplanar Flange and 3051T Bracket Option B4 Bracket for 2 in Pipe or Panel Mounting For use with the standard Coplanar flange configuration Bracket for mounting of transmitter on 2 in pipe or panel Stainless steel construction with stainless steel bolts Rosemount 3051H Bracket Options B5 Bracket for 2 in Pipe or Panel Mounting...

Страница 169: ...bolts Coated with polyurethane paint B7 B1 Bracket with SST Bolts Same bracket as the B1 option with Series 300 stainless steel bolts B8 B2 Bracket with SST Bolts Same bracket as the B2 option with Series 300 stainless steel bolts B9 B3 Bracket with SST Bolts Same bracket as the B3 option with Series 300 stainless steel bolts BA Stainless Steel B1 Bracket with SST Bolts B1 bracket in stainless ste...

Страница 170: ...9 0 20 8 9 5 21 8 9 9 DN 100 PN 40 23 2 10 5 25 2 11 5 26 2 11 9 27 2 12 3 Table A 8 Transmitter options weights Code Option Add lb kg J K L M Stainless Steel Housing T 3 9 1 8 J K L M Stainless Steel Housing C L H P 3 1 1 4 M5 LCD display for Aluminum Housing 0 5 0 2 M6 LCD display for SST Housing 1 25 0 6 B4 SST Mounting Bracket for Coplanar Flange 1 0 0 5 B1 B2 B3 Mounting Bracket for Tradition...

Страница 171: ... 33 155 145 15514 5 1034 3 103430 psi 0 01806 0 903 0 0902 9 03183 0 36127 36 127 3 300 20 2000 bar 0 00125 0 06227 0 00623 0 62272 0 02491 2 491 0 20684 20 6843 1 37895 137 895 mbar 1 2454 62 2723 6 22723 622 723 24 9089 2490 89 206 843 20684 3 1378 95 137895 g cm2 1 26775 63 3875 6 33875 633 875 25 355 2535 45 210 547 21054 7 1406 14 140614 kg cm2 0 00127 0 0635 0 00635 0 635 0 0254 2 54 0 21092...

Страница 172: ...6 14 140614 kg cm2 0 00635 0 635 0 0254 2 54 0 21092 21 0921 1 40614 140 614 Pa 622 723 62160 6 2490 89 249089 20684 3 2068430 137895 13789500 kPa 0 62272 62 2723 2 49089 249 089 20 6843 2068 43 137 895 13789 5 torr 4 67082 467 082 18 6833 1868 33 155 145 15514 5 1034 3 103430 atm 0 00615 0 61460 0 02458 2 458 0 20414 20 4138 1 36092 136 092 When using a Field Communicator 5 adjustment is allowed ...

Страница 173: ... 46 When using a Field Communicator 5 adjustment is allowed on the sensor limit to allow for unit conversions Range 1 span Range 2 span Range 3 span Range 4 span Units min max min max min max min max inH2O 8 30397 831 889 41 5198 4151 98 221 439 22143 9 1107 2 110720 inHg 0 61081 61 0807 3 05403 305 403 16 2882 1628 82 81 441 8144 098 ftH2O 0 69199 69 3241 3 45998 345 998 18 4533 1845 33 92 2663 9...

Страница 174: ...45 0017 250 to 250 inH2O 2 5 inH2O Range 2 316L SST 03031 1045 0022 03031 1145 0022 Alloy C 276 03031 1045 0022 03031 1145 0022 Alloy 03031 1045 0024 03031 1145 0024 Tantalum 03031 1045 0025 03031 1145 0025 Gold plated Alloy 03031 1045 0026 03031 1145 0026 Gold plated 316 SST 03031 1045 0027 03031 1145 0027 1000 to 1000 inH2O 10 inH2O Range 3 316L SST 03031 1045 0032 03031 1145 0032 Alloy C 276 03...

Страница 175: ...5 to 25 in H2O 0 5 in H2O 316L SST 03031 1045 0012 03031 1145 0012 Alloy C 276 03031 1045 0013 03031 1145 0013 Alloy 400 03031 1045 0014 03031 1145 0014 Gold plated Alloy 400 03031 1045 0016 03031 1145 0016 Gold plated 316 SST 03031 1045 0017 03031 1145 0017 Range 2 250 to 250 inH2O 2 5 inH2O 250 to 250 inH2O 2 5 inH2O 316L SST 03031 1045 0022 03031 1145 0022 Alloy C 276 03031 1045 0023 03031 1145...

Страница 176: ...old plated Alloy 400 03031 1045 2056 03031 1145 2056 Gold plated 316 SST 03031 1045 2057 03031 1145 2057 Rosemount 3051C absolute sensor modules Min Span Range Silicone fill Inert fill Part number Part number Note One spare part is recommended for every 50 transmitters Note Listed by Range and Process Isolator Order Numbers Range 1 0 to 30 psia 0 3 psia 316L SST 03031 2020 0012 Alloy C 276 03031 2...

Страница 177: ... 20 mA HART 316 SST 03031 0193 0111 1 5 Vdc HART Low Power Aluminum 03031 0193 0001 1 5 Vdc HART Low Power 316 SST 03031 0193 0011 Fieldbus FOUNDATION or PROFIBUS PA Aluminum 03031 0193 0104 Fieldbus FOUNDATION or PROFIBUS PA 316 SST 03031 0193 0112 LCD Display Only 4 20 mA HART 03031 0193 0103 1 5 Vdc HART Low Power 03031 0193 0003 Fieldbus FOUNDATION or PROFIBUS PA 03031 0193 0105 Terminal block...

Страница 178: ...004 Housing covers include o ring Part number Field terminal cover Aluminum 03031 0292 0001 Field terminal cover 316 SST 03031 0292 0002 HART electronics cover Aluminum 03031 0292 0001 HART electronics cover 316 SST 03031 0292 0002 HART LCD Display cover Aluminum 03031 0193 0002 HART LCD Display cover 316 SST 03031 0193 0012 Fieldbus extended electronics cover Aluminum 03031 0292 0003 Fieldbus ext...

Страница 179: ...N DN 50 PN 40 03031 0393 1002 DIN DN 80 PN 40 03031 0393 1012 Flange adapter kits each kit contains parts for one DP transmitter or two GP AP transmitters Part number CS bolts glass filled PTFE O Rings SST adapters 03031 1300 0002 Cast Alloy C 276 adapters 03031 1300 0003 Alloy 400 adapters 03031 1300 0004 Nickel plated carbon steel adapters 03031 1300 0005 SST bolts glass filled PTFE O Rings SST ...

Страница 180: ...lectronics housing cover 03031 0232 0001 Electronics housing module 03031 0233 0001 Process flange glass filled PTFE White 03031 0234 0001 Process flange graphite filled PTFE Black 03031 0234 0002 Process flange for 3051H PTFE White 02051 0167 0001 Flange adapter glass filled PTFE Light Brown 03031 0242 0001 Flange adapter graphite filled PTFE Black 03031 0242 0002 Bolt kits Part number COPLANAR F...

Страница 181: ...31 0395 0001 316 SST 03031 0395 0002 3051H Process Flange Bolt Kit Set of 4 Carbon Steel 02051 0164 0001 316 SST 02051 0164 0002 Drain Vent valve kits each kit contains parts for one transmitter Part number Differential Drain Vent Kits 316 SST stem and seat kit 01151 0028 0022 Alloy C 276 stem and seat kit 01151 0028 0023 Alloy K 500 stem and Alloy 400 seat kit 01151 0028 0024 316 SST ceramic ball...

Страница 182: ...ts 03031 0313 0001 B2 bracket panel mount CS bolts 03031 0313 0002 B3 flat bracket 2 in pipe mount CS bolts 03031 0313 0003 B7 B1 bracket SST bolts 03031 0313 0007 B8 B2 bracket SST bolts 03031 0313 0008 B9 B3 bracket SST bolts 03031 0313 0009 BA SST B1 bracket SST bolts 03031 0313 0011 BC SST B3 bracket SST bolts 03031 0313 0013 3051H Bracket Kits B5 universal bracket 2 in pipe and panel mount CS...

Страница 183: ...ations and reference data Figure A 1 Spare parts diagram Electronics Housing Terminal Block Electronics Housing Module o ring Process o ring Flange Adapter o ring Housing Cover Electronics Housing Cover o ring Electronics Board Sensor Module Drain Vent Valve Flange Adapter Flange Adapter Bolts ...

Страница 184: ...174 Reference Manual 00809 0100 4001 Rev JA Appendix A Reference Data November 2012 Specifications and reference data ...

Страница 185: ...verview This Appendix contains information on Approved manufacturing locations European directive information Ordinary Location certification Hazardous Locations Certifications and approval drawings for HART protocol B 2 Safety messages Procedures and instructions in this section may require special precautions to ensure the safety of the personnel performing the operations Information that raises...

Страница 186: ...tional Safety and Health Administration OSHA Explosions could result in death or serious injury Installation of this transmitter in an explosive environment must be in accordance with the appropriate local national and international standards codes and practices Please review this section of the Model 3051 reference manual for any restrictions associated with a safe installation Before connecting ...

Страница 187: ...emount 3051 transmitter housing contains aluminum and is considered a potential risk of ignition by impact or friction Care must be taken into account during installation and use to prevent impact and friction 2 The Rosemount 3051 transmitter with the transient terminal block Option code T1 will not pass the 500Vrms dielectric strength test and this must be taken into account during installation C...

Страница 188: ...itance of the wrap around label to the enclosure 1 6E 9 F exceeds the limit in Table 9 of IEC 60079 0 The user shall determine suitability for the specific application 4 Wait at least 5 minutes after powering down device before opening covers when a hazardous atmosphere is present I1 ATEX Intrinsic Safety and Dust Certificate No BAS 97ATEX1089X Applicable Standards IEC60079 0 2011 EN60079 11 2012 ...

Страница 189: ...f the flameproof joints Japanese certifications E4 TIIS Flame Proof Markings Ex d IIC T6 I4 TIIS Intrinsic Safety Certification No TC16406 Markings Ex ia IIC T4 IECEx certifications E7 IECEx Flame proof Certification No IECEx KEM 09 0034X Applicable Standards IEC60079 0 2011 IEC60079 1 2007 04 IEC60079 26 2006 Markings Ex d IIC T5 T6 Ga Gb T5 50 C Ta 80 C T6 50 C Ta 65 C Conditions of Certificatio...

Страница 190: ...s 2 The enclosure may be made of aluminum alloy and given a protective polyurethane paint finish however care should be taken to protect it from impact or abrasion if located in Zone 0 N7 IECEx Type n Certification No IECEx BAS 09 0077X Applicable Standards IEC60079 0 2011 IEC60079 15 2010 Markings Ex nA IIC T5 Gc 40 Ta 70 C Conditions of Certification X The apparatus is not capable of withstandin...

Страница 191: ...66 or higher level should be applied 2 4 Obey the warning Keep tight when the circuit is alive 2 5 End users are not permitted to change any component s insides 2 6 When installing using and maintaining the transmitter observe the following standards GB3836 13 1997 Electrical apparatus for explosive gas atmospheres Part 13 Repair and overhaul for apparatus used in explosive gas atmospheres GB3836 ...

Страница 192: ...plosive gas atmospheres GB3836 15 2000 Electrical apparatus for explosive gas atmospheres Part 15 Electrical installations in hazardous area other than mines GB3836 16 2006 Electrical appartus for explosive gas atmospheres Part 16 Inspection and maintenance of electrical installation other than mines GB50257 1996 Code for construction and acceptance of electric device for explosion atmospheres and...

Страница 193: ...and maintaining transmitter observe following standards GB3836 1 1997 Electrical apparatus for explosive gas atmospheres Part 13 Repair and overhaul for apparatus used in explosive gas atmospheres GB3836 15 2000 Electrical apparatus for explosive gas atmospheres Part 15 Electrical installations in hazardous area other than mines GB3836 16 2006 Electrical appartus for explosive gas atmospheres Part...

Страница 194: ...184 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications B 6 Approval drawings B 6 1 Factory mutual 03031 1019 ...

Страница 195: ...185 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 196: ...186 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 197: ...187 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 198: ...188 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 199: ...189 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 200: ...190 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 201: ...191 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 202: ...192 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 203: ...193 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 204: ...194 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 205: ...195 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 206: ...196 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 207: ...197 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications B 6 2 Canadian standards association CSA 03031 1024 ...

Страница 208: ...198 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 209: ...199 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 210: ...200 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 211: ...201 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 212: ...202 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 213: ...203 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 214: ...204 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 215: ...205 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 216: ...206 Reference Manual 00809 0100 4001 Rev JA Appendix B Product Certifications November 2012 Product certifications ...

Страница 217: ...3 Recal factory trim Analog output 80 Sensor trim 84 Sensor trim 81 Tasks 74 Zero trim 82 Certifications 175 Cloning 64 Closed Vessels Dry Leg Condition 36 Liquid Level Measurement 35 Wet Leg Condition 36 Communicator 94 Compensating line pressure 85 Configuration 39 Applying a user configuration 66 Cloning 64 Data review 42 LCD display Custom 59 LCD meter 58 Recalling 64 Reusable copy 66 Saving 6...

Страница 218: ... Config 92 Elect 92 Module 92 Failure mode Alarm values 61 Saturation values 61 Features 2 Filtering Draft range 7 Foundation fieldbus 3 Full trim 83 G Grounding 23 Transmitter Case 28 H HART Communicator Diagnostics 94 Hazardous Locations 31 Housing Remove 99 I Impulse piping 14 Installation 5 10 Bolts 11 13 Cover 10 Draft range 7 Environmental Considerations 29 Examples 16 HART flowchart 9 Hazar...

Страница 219: ...4 Press Limit 93 Process Connections 16 Process variables 50 Units 52 Product certifications 175 R Reassembly Attaching sensor module 100 Installing terminal block 101 Process sensor body 101 Recall factory trim Analog output 80 Sensor trim 84 Recalling 64 Rerange 53 AMS only 57 HART Communicator only 55 Pressure input source With HART Communicator 55 With local zero and span 56 Returning products...

Страница 220: ...80 Sensor trim 84 Sensor 81 Zero 82 Troubleshooting Reference table 91 U Units Process variable 52 V Vessels Open Closed 35 W Warnings 92 Wet Leg Condition Example Figure 4 6 37 Liquid Level Measurement 36 Wiring 23 Diagrams Bench hook up 41 Low power 41 Signal Terminals 23 Test Terminals 23 Write protect 20 94 X Xmtr Info 93 Z Zero Button 20 Fail 93 Pass 93 Zero trim 82 ...

Страница 221: ......

Страница 222: ...a registered trademark of the HART Communication Foundation Foundation fieldbus is a registered trademark of the Fieldbus Foundation All other marks are the property of their respective owners November 2012 Rosemount Inc All rights reserved Emerson Process Management GmbH Co Argelsrieder Feld 3 82234 Wessling Germany Tel 49 8153 9390 Fax 49 8153 939172 Emerson Process Management Asia Pacific Priva...