Procedure
Select
Lower Sensor Trim
.
Note
Select pressure points so that lower and upper values are equal to or outside the expected
process operation range.
5.5
Status
Along with the measured or calculated PV value, every F
OUNDATION
™
Fieldbus block passes
an additional parameter called STATUS. The PV and STATUS are passed from the
Transducer Block to the Analog Input Block. The STATUS can be one of the following:
GOOD, BAD, or UNCERTAIN. When there are no problems detected by the self-diagnostics
of the block, the STATUS will be GOOD. If a problem occurs with the hardware in the
device or the quality of the process variable is compromised for some reason, the STATUS
will become either BAD or UNCERTAIN depending upon the nature of the problem. It is
important that the Control Strategy that makes use of the Analog Input Block is
configured to monitor the STATUS and take action where appropriate when the STATUS is
no longer GOOD.
5.6
Master reset method
5.6.1
Resource block
Menu navigation:
Service Tools
→
Maintenance
→
Reset/Restore
Note
Master reset (sometimes called restart) is performed in the resource block. For block
oriented user interfaces, perform the reset in the resource block.
There are two master reset options. One restarts the transmitter processor but doesn't
change device configuration. The second is a restart with factory defaults. It returns all
device and function block parameters to the factory defaults. An automated procedure
called a
Method
guides you through both reset options.
Figure 5-3: Master Reset Button
The
Master Reset
button starts the method that initiates the reset and verifies the reset is
complete. Note that during the reset communication between the device and the host is
lost. There may be some delay before the device is recognized again by the host.
Set the Restart to one of the options below:
Operation and maintenance
Reference Manual
July 2020
00809-0100-4774
100
Rosemount 3051
Содержание Rosemount 3051 CF Series
Страница 4: ...4 ...
Страница 56: ...Configuration Reference Manual July 2020 00809 0100 4774 56 Rosemount 3051 ...
Страница 92: ...Electrical installation Reference Manual July 2020 00809 0100 4774 92 Rosemount 3051 ...
Страница 102: ...Operation and maintenance Reference Manual July 2020 00809 0100 4774 102 Rosemount 3051 ...
Страница 118: ...Troubleshooting Reference Manual July 2020 00809 0100 4774 118 Rosemount 3051 ...
Страница 138: ...Reference data Reference Manual July 2020 00809 0100 4774 138 Rosemount 3051 ...
Страница 145: ...Reference Manual 00809 0100 4774 July 2020 Reference Manual 145 ...