25
Reference Manual
00809-0100-2230, Rev CA
July 2017
3.4.5
Power requirements
The Rosemount 2230 is powered over the intrinsically safe Tankbus by the Rosemount 2410 Tank Hub.
The 2410 feeds the intrinsically safe fieldbus segment by acting as a FISCO power supply on the Tankbus
(9 - 17.5 Vdc, polarity insensitive). The Rosemount 2230 has a current consumption of 30 mA.
See the Rosemount 2410 Reference Manual (Document no. 00809-0100-2410) for more information.
When installed in a F
OUNDATION
fieldbus system, the Rosemount 2230 is powered by the FF segment with
standard fieldbus power supplies.
3.4.6
The Tankbus
The Rosemount Tank Gauging system is easy to install and wire. Devices can be “daisy-chained” thus
reducing the number of segment couplers.
In a Rosemount Tank Gauging system devices communicate with a Rosemount 2410 Tank Hub via the
intrinsically safe Tankbus. The Tankbus complies with the FISCO
(1)
F
OUNDATION
fieldbus standard and the
Rosemount 2410 acts as power supply to the field devices on the Tankbus.
Termination
A terminator is needed at each end of a F
OUNDATION
fieldbus network. Generally, one terminator is placed
in the fieldbus power supply, and the other one in the last device in the fieldbus network.
Note
Ensure that there are
two
terminators on the fieldbus.
The Rosemount 2410 Tank Hub acts as power supply. Since the 2410 normally is the first device in the
fieldbus segment, the built-in termination is enabled at factory.
Other devices such as the Rosemount 5900S Radar Level Gauge, the Rosemount 2230 Graphical Field
Display, and the Rosemount 2240S Multi-input Temperature Transmitter also have built-in terminators
which can easily be enabled by inserting a jumper in the terminal block when necessary.
Segment design
When designing a FISCO fieldbus segment a few requirements need to be considered. Cabling has to
comply with FISCO requirements as described in
.
You will also have to ensure that the total operating current of the connected field devices is within the
output capability of the Rosemount 2410 Tank Hub. The tank hub is able to deliver 250 mA. In a wireless
system the maximum current is 200 mA. Consequently, the number of field devices has to be considered
so that the total current consumption is less than the available current. See section “Power Budget” in
the Rosemount 2410 Reference Manual (Document no. 00809-0100-2410) for more information.
Ensure that all field devices have at least 9 V input voltage at their terminals. Therefore you will have to
take into account the voltage drop in the fieldbus cables.
Distances are normally quite short between the Rosemount 2410 Tank Hub and field devices on the
tank. In many cases you can use existing cables as long as the FISCO requirements are fulfilled (see
).
See section The Tankbus in the Rosemount 2410 Reference Manual (Document no. 00809-0100-2410) for
more information on segment design of a Rosemount Tank Gauging system.
1,
FISCO=Fieldbus Intrinsically Safe Concept
Содержание Rosemount 2230
Страница 1: ...Reference Manual 00809 0100 2230 Rev CA July 2017 Rosemount 2230 Graphical Field Display ...
Страница 2: ......
Страница 4: ...ii Reference Manual 00809 0100 2230 Rev CA Title Page July 2017 Title Page ...
Страница 16: ...6 Reference Manual 00809 0100 2230 Rev CA Introduction July 2017 Introduction ...
Страница 28: ...18 Reference Manual 00809 0100 2230 Rev CA Overview July 2017 Overview ...
Страница 44: ...34 Reference Manual 00809 0100 2230 Rev CA Installation July 2017 Installation ...
Страница 120: ...110 Reference Manual 00809 0100 2230 Rev CA Service and Troubleshooting July 2017 Service and Troubleshooting ...
Страница 132: ...122 Product Certifications Product Certifications July 2017 Reference Manual 00809 0100 2230 Rev CA ...
Страница 154: ...144 Reference Manual 00809 0100 2230 Rev CA Index July 2017 Index ...
Страница 155: ......