100
Reference Manual
00809-0100-4140, Rev AA
January 2017
6.4.3
Diagnostic message: advisory
Table 6-4. Status: Advisory
Alert name
LOI screen
Problem
Recommended action
Non-Critical
User Data
Warning
MEMORY
WARN
A user written parameter
does not match
expected value
1.Confirm and correct all parameters listed in Device
Information.
2.Perform a Device Reset.
3.Replace Electronics Board.
Scaled
Variable Alert
SCALED
ALERT
The Scaled Variable alert
diagnostic has gone
beyond the configured
trip points.
1.Verify that the Scaled Variable is at an expected value.
2.Verify the Scaled Variable is beyond the trip points.
3.Modify the trip points or turn off alert.
Sensor
Frequency
Alert
FREQ
ALERT
The Sensor Frequency
alert diagnostic has
detected that the
frequency has gone
beyond the configured
trip points.
1.Verify that the sensor frequency is at an expected value.
2.Verify the sensor frequency is beyond the trip points.
3.Modify the trip points or turn off alert.
Temperature
Alert
TEMP
ALERT
The Temperature alert
diagnostic has detected
that the electronics
temperature has gone
beyond the configured
trip points.
1.Verify that the process and environmental temperature is
at an expected value.
2.Verify the temperature is beyond the trip points.
3.Modify the trip points or turn off alert.
LOI Display
Update Failure
[If display
is not
updating]
The LOI display is not
receiving updates from
the fork sensor.
1.Check the connection between the LOI and the circuit
board.
2.Contact your local Emerson representative for advice.
Configuration
Changed
[none]
A recent change has
been made the device by
a secondary HART
master such as a
handheld device.
1.Verify that the configuration change of the device was
intended and expected.
2.Clear this alert by selecting Clear Configuration Changed
Status.
3.Connect a HART master such as AMS or similar which will
automatically clear it.
Analog
Output Fixed
ANALOG
FIXED
The analog output is
fixed and does not
represent the process
measurement. This may
be caused by other
conditions in the device,
or because the device
has been set to loop test
or multidrop mode
1.Take action on any other notifications from the device.
2.If the device is in loop test, and should no longer be,
disable or momentarily remove power.
3.If the device is in multidrop mode and should not be,
re-enable loop current by setting the polling address to 0.
Simulation
Active
[none]
The device is in
simulation mode and
may not be reporting
actual information
1.Verify that simulation is no longer required.
2.Disable simulation mode in service tools.
3.Perform a Device Reset.
Analog
Output
Saturated
ANALOG
SAT
The analog output is
saturated either high or
low due to the PV either
above or below the range
values
1.Check the PV applied to ensure it is between the 4-20mA
points.
Содержание Rosemount 2140
Страница 1: ...Reference Manual 00809 0100 4140 Rev AA January 2017 Rosemount 2140 Level Detector Vibrating Fork ...
Страница 2: ......
Страница 8: ...VI Reference Manual 00809 0100 4140 Rev AA Contents January 2017 Contents ...
Страница 14: ...4 Reference Manual 00809 0100 4140 Rev AA Introduction January 2017 Introduction ...
Страница 112: ...102 Reference Manual 00809 0100 4140 Rev AA Troubleshooting January 2017 Troubleshooting ...
Страница 143: ......