21
Reference Manual
00809-0300-4410, Rev BA
Configuration
January 2018
Configuration
Figure 2-15. Re-mapping with LOI
2.12
Performing transmitter tests
2.12.1
Verifying alarm level
If the transmitter is repaired or replaced, verify the transmitter alarm level before returning the
transmitter to service. This is useful in testing the reaction of the control system to a transmitter in an
alarm state. Thus ensuring the control system recognizes the alarm when activated. To verify the
transmitter alarm values, perform a loop test and set the transmitter output to the alarm value (see
, and
on page
Note
Before returning transmitter to service, verify security switch is set to the correct position. Refer to
“Verify configuration” on page 11
2.12.2
Performing an analog loop test
The analog loop test command verifies the output of the transmitter, the integrity of the loop, and the
operations of any recorders or similar devices installed in the loop. It is recommended that the 4–20 mA
points in addition to alarm levels when installing, repairing, or replacing a transmitter.
The host system may provide a current measurement for the 4–20 mA HART output. If not, connect a
reference meter to the transmitter by either connecting the meter to the test terminals on the terminal
block, or shunting transmitter power through the meter at some point in the loop.
Field Communicator
From the
HOME
screen, enter the Fast Key sequence
Device Dashboard Fast Keys
3, 5, 1
VIEW CONFIG
ZERO TRIM
UNITS
RERANGE
LOOP TEST
DISPLAY
EXTENDED MENU
EXIT MENU
EXTENDED MENU
CALIBRAT
DAMPING
TRANSFER FUNCT
SCALED VARIAB
ASSIGN PV
TAG
ALARM SAT VALUES
PASSWORD
SIMULATE
HART REV
BACK TO
MENU
EXIT MENU
Содержание Rosemount 2051G
Страница 2: ......
Страница 10: ...2 Reference Manual 00809 0400 4101 Rev BA Introduction January 2018 Introduction ...
Страница 34: ...26 Reference Manual 00809 0300 4410 Rev BA Configuration January 2018 Configuration ...
Страница 64: ...56 Reference Manual 00809 0400 4101 Rev BA Operation and Maintenance January 2018 Operation and Maintenance ...
Страница 72: ...64 Reference Manual 00809 0400 4101 Rev BA Troubleshooting January 2018 Troubleshooting ...
Страница 89: ......