STATUS OPTION Screen
Main Screens • 57
Press the down arrow key:
11.4.11.1. Calibrate Gas Screen 3 Continued
The default gas name is
NEW GAS1
.
Pressing the down arrow key brings you back to the
CONFIG OPTION screen. To move back to the STA-
TUS OPTION screen, first press the up arrow key to
go back to the OPTION screen and select
1
for RLDS
STATUS. You should now be back at the STATUS
OPTION screen.
11.5. STATUS OPTION Screen
From the STATUS OPTION screen, you are able to
check zone status (individual zones), ctrl status (over-
all controller status), and diagnostics (diagnostic zone
data).
To display ZONE STATUS: (individual zones), press
the right arrow key and press
1.
Press the down arrow
key twice. The ZONE STATUS screen displays.
11.5.1. Zone Status Screen
The PPM count, alarm status, and alarm
acknowledge information is displayed for each
individual zone.
Press the down arrow key from the Zone Status screen
to scroll through the status concentration for each of
the zones in use. The PPM concentration will be
shown, alarm/failure indication, and if the alarm is
acknowledged. If the zone is normal (no alarm
detected), the alarm/failure fields and alarm
acknowledge field (where
LEAK A
appears) should
be blank.
ACKNOWLEDGING ALARMS
In order to acknowledge an alarm, press the left or
right arrow keys to select the zone and then press the
CANCEL
key so the
A
appears next to the alarm.
When the
A
appears, the alarm has been
acknowledged.
LEAK, SPIL(L), or EVAC(UATE) will display if
there is an alarm. If there is a flow problem (failure)
for the zone, FLOW displays. A failure cannot be
acknowledged--only LEAK, SPIL, or EVAC alarms
can be acknowledged.
Use the down arrow key to scroll through and view all
of the zones.
After you have scrolled through the zones you are
back at the STATUS OPTION screen where you can
make another selection.
To display CTRL STATUS: (overall controller
status), press the right arrow key and press
2
. Press the
down arrow key twice. The General Controller
(CTRL STATUS) screen displays:
11.5.2. General Controller (CTRL
STATUS) Screen
1: NEW GAS1
2: NEW GAS2
3: NEW GAS3
3: NEW GAS3
NOTE: The “blank” line is used to provide a
cursor so the user knows which character they
are editing. The user can use “.” and “—” keys
to scroll an individual character selection or
numeric numbers can be entered directly.
STATUS OPTION:
1 = ZONE STATUS
2 = CTRL STATUS
3 = DIAGNOSTICS
01: ZONE 01 LOC
1-01: 0 LEAK A
02: ZONE 02 LOC
1-02: A
Ux-MODE: NORMAL
Ux-STAT: <ZEROING:SAMPLE>
Ux-ALARM CNT:
Ux-ACT ZONE:
Содержание RLDS
Страница 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 8 ...
Страница 2: ......
Страница 4: ......
Страница 49: ...Service Mode General Operation of RLDS UI 43 RLDS Setup Screens System Map ...
Страница 76: ......
Страница 81: ......