
30
Quantum MP User Guide
www.emersonct.com Issue: A4
Figure 4-2 Control connections, Quantum MP size 1
X1
X2
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
Q9
Q10
Q11
Q12
MP10 User Interface Board
N/C
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
E-Stop
Stop
Run
Jog
Fwd
Reset
Drive ON
Rev
Motor
Thermal
System
Interlocks
120 VAC
30 VA max.
C5
C6
C7
C8
Run
Two wire Run
Pr 6.40 = 0
Three wire Stop/Run
Pr 6.40 = 1
Programming Notes: Changes to Mentor MP USA Default Values
Parameter
Quantum MP
Value
Description
5.16
1
DC Contactor
6.40
1
Enable sequencer latching
8.22
0.00
T25 digital I/O 2 source/ destination
8.23
0.00
T26 digital I/O 3 source/ destination
8.24
0.00
T27 digital input 4 destination
8.26
0.00
T29 digital input 6 destination
9.04
17.06
Logic function 1 source 1
9.05
1
Logic function 1 source 1 invert
9.09
0.1
Logic function 1 delay
9.10
10.32
Logic function 1 destination (External Trip)
9.37
1
Logic block 1 mode
17.21
6.39
SM-IO-120V T1 digital input 1 destination (Not stop)
17.22
6.34
SM-IO-120V T2 digital input 2 destination (Run)
17.23
6.31
SM-IO-120V T4 digital input 3 destination (Jog)
17.24
6.33
SM-IO-120V T5 digital input 4 destination (Forward/reverse)
17.25
10.33
SM-IO-120V T7 digital input 5 destination (Drive reset)
17.28
6.55
SM-IO-120V Relay 2 source (Contactor enable)