Quantum MP User Guide
23
Issue: A4 www.emersonct.com
3.8 Electrical terminals - Size 1
3.8.1 Location of the power and ground terminals
Figure 3-11 Location of the power and ground terminals
3.8.2 Terminal sizes and torque settings
3.8.3 Torque settings
Table 3-1 Control terminal data
Table 3-2 Auxiliary and Field terminal data
Table 3-3 Drive power (L1, L2, L3, and GND) terminals
Table 3-4 Drive power (A1 and A2) terminals
Control and
encoder
connection
2.5 mm
Relay
connector
3.5 mm
Field
connector
5 mm
Auxiliary
connector
5 mm
Tach
connection
3.5 mm
MP 10, 120 Vac
I/O connection
3.5 mm
GND, L1, L2, L3
connection
5/16 inch
QMP155 / 210
drives
5 mm
QMP45 / 75
drives
DB+,DB-,SR1, and SR2 connection
5 mm
A1, A2
connection
3/8 inch
QMP75 / 155 drives
5 mm
QMP45 / 75 drives
To avoid a fire hazard and maintain validity of the UL listing,
adhere to the specified tightening torques for the power and
ground terminals. Refer to the following tables.
Model
Connection type
Torque setting
All
Plug-in terminal block
0.5 Nm 0.4 lb ft
Model
Connection type
Torque setting
All
Terminal block
0.5 Nm 0.4 lb ft
WARNING
Model
Connection type
Torque setting
QMP45A4(R)
2-14 AWG Slot Screw Lug
4-5.6 Nm 2.9-4.2 lb ft
QMP75A4(R)
2-14 AWG Slot Screw Lug
4-5.6 Nm 2.9-4.2 lb ft
QMP155A4(R)
5/16” Socket Lug
31 Nm 23 lb ft
QMP210A4(R)
5/16” Socket Lug
31 Nm 23 lb ft
Model
Connection type
Torque setting
QMP45A4(R)
2-14 AWG Slot Screw Lug
4-5.6 Nm 2.9-4.2 lb ft
QMP75A4(R)
2-14 AWG Slot Screw Lug
4-5.6 Nm 2.9-4.2 lb ft
QMP155A4(R)
3/8” Socket Lug
42 Nm 31 lb ft
QMP210A4(R)
3/8” Socket Lug
42 Nm 31 lb ft