164
Quantum MP User Guide
www.emersonct.com Issue: A4
Table 13-2 Serial communications look-up table
13.3 Trip Categories
Trips can be grouped into the following categories. It should be noted that a trip can only occur when the drive is not tripped or is already tripped but
with a trip with a lower priority number.
Table 13-3 Trip categories
Unless otherwise stated, trips cannot be reset until 1.0s after the trip has been accepted by the drive
No.
String
No.
String
No.
String
1
UU
90
UP div0
187
C.Typ
2
t002
91
UP Par
188
C.cpr
3
AOC
92
UP or
189
EnC1
4
t004
93
UP So
190
EnC2
5
PS
94
UP or
191
EnC3
6
Et
95
UP OFL
192-196
t192 - t196
7
O.SPd
96
UP uSEr
197
EnC9
8
PS.10V
97
UP AdV
198
EnC10
9
PS.24V
98
UP ACC
199
dESt
10
t010
99
t99
200
SL1.HF
11
tunE1
100
201
SL1.tO
12
tunE2
101
t101
202
SL1.Er
13
tunE3
102-111
t102 - t111
203
SL1.nF
14
tunE4
112-156
t112 - t156
204
SL1.dF
15
tunE5
157
F.OVL
205
SL2.HF
16
tunE6
158
AOP
206
SL2.tO
17
tunE7
159
Fable
207
SL2.Er
18
tunE
160
Fbr
208
SL2.nF
19
t019
161-167
t161 - t167
209
SL2.dF
20
It.AC
168
FdL
210
SL3.HF
21
O.ht1
169
FOC
211
SL3.tO
22
O.ht2
170
SL
212
SL3.Er
23
t023
171
S.OLd
213
SL3.nF
24
Th
172
S.Ov
214
SL3.dF
25
ThS
173
th.Err
215
SL.rtd
26
O.Ld1
174
PLL Err
216
t216
27
O.ht3
175
C.Prod
217-232
HF17 – HF32
28
cL2
176
t176
29
cL3
177
C.Boot
30
SCL
178
C.BUSy
31
EEF
179
C.Chg
32-33
t032 - t033
180
C.Optn
34
Pad
181
C.RdO
35
CL.bit
182
C.Err
36
SAVE.Er
183
C.dat
37
PSAVE.Er
184
C.FULL
38-39
t038 - t039
185
C.Acc
40-89
t040 - t089
186
C.rtg
Priority
Category
Trips
Comments
1
Hardware faults
HF01 to HF16
These indicate fatal problems and cannot be reset. The drive is
inactive after one of these trips and the display shows HFxx.
2
Non-resetable trips
HF17 to HF32, SL1.HF, SL2.HF,
SL3.HF
Cannot be reset
3
EEF trip
EEF
Cannot be reset unless a code to load defaults is first entered in
parameter x.00
4
SMARTCARD trips
C.Boot, C.Busy, C.Chg, C.Optn,
C.RdO, C.Err, C.dat, C.FULL,
C.Acc, C.rtg, C.Typ, C.cpr,
SMARTCARD trips have priority 5 during power up.
4
Encoder power supply trips
PS.24V, Enc1
These trips can only override the following priority 5 trips: Enc2 or
Enc9
5
Normal trips
All other trips not included in this
table
Can be reset after 1.0s
6
Self reseting trips
UU
Under voltage trip cannot be reset by the user, but is automatically
reset by the drive when the supply voltage is with specification.