User Manual
Chapter 8
GFK-2843A
Jan 2020
Errors: messages and removal
52
Error cause
Diagnostic code
(hex)
LED
Remark
Effect
Solution
Acknowle
dgment
X062: OUT2_Ch1
X069: OUT2_Ch2
at the output
failed
X063: OUT3_Ch1
X06A: OUT3_Ch2
Hardware fault
X091
All
OUT:
Detected by
internal tests.
All module out-
puts are in the
safe state
Power up with
error-free selftest
Replacement
Yes (1)
Red ON
Cross circuit at the
indicated output
X0An
All
Cross circuit
with another
output or
with an
external
signal
All module out-
puts are in the
safe state
Remove error
Power up with
error-free selftest
Yes (1)
OUT:
red
X0A0: OUT0_Ch1
X0A7: OUT0_Ch2
ON
X0A1: OUT1_Ch1
X0A8: OUT1_Ch2
X0A2: OUT2_Ch1
X0A9: OUT2_Ch2
X0A3: OUT3_Ch1
X0AA: OUT3_Ch2
Acknowledge all errors that are present. Only then can the outputs be re-enabled.
Acknowledgment: yes (1)
Acknowledging the diagnostic message deletes the message.
The module can only be re- started or reparameterized
following power up or soft reset and error-free selftest.
Acknowledgment: yes (2)
Acknowledging the diagnostic message deletes the message
and enables a restart. Following successful acknowledgment,
the module also expects a positive edge from the application
for the output.
WARNING
Unexpected machine startup
An operator acknowledgment leads to a positive edge and can therefore result in the out-
puts being re-enabled.
8.2
Supply voltage errors
Table 20: Supply voltage U
M
errors
Error cause Diagnostic
code (hex)
LED
Remark
Effect
Solution
Acknowled
gment
Undervoltage
U
M
X1F0
UM
flashing
U
M
below
the
permissible
voltage
range
All module
out- puts are
in the safe
state
Check supply
voltage level and
correct
Check supply line
length and load
Yes (3)
Acknowledgment: yes (3)
Acknowledging the diagnostic message deletes the message
and activates the outputs.