User Manual
Chapter 8
GFK-1503F
Jan 2020
Elements of an Application Program
85
Within a rung, there are many complex functions that can be used for operations like
moving data stored in memory, performing math operations, and controlling
communications between the CPU and other devices in the system.
Some program functions, such as the Jump function and Master Control Relay, can be used
to control the execution of the program itself.
Together, this large group of Ladder Diagram relays, coils, and functions is called the
“Instruction Set” of the CPU.
8.4
The Instruction Set
The VersaMax PLC CPU provides a powerful Instruction Set for building application
programs.
As a guide to the programming capabilities of the VersaMax PLC, all of the relays, coils,
functions, and other elements of the Instruction Set are summarized on the following
pages. Complete reference information is included in the documentation and online help
for the programming software.
8.4.1
Contacts
–
| |
–
Normally Open
Passes power if the associated reference is ON.
–
|/|
–
Normally Closed
Passes power if the associated reference is OFF.
<+>
–––
Continuation
Passes power to the right if the preceding continuation coil
is set ON.
8.4.2
Coils
–
( )
–
Normally Open
Sets the associated reference ON if the coil receives power.
Otherwise OFF.
–
(/)
–
Negated
Sets the associated discrete reference ON if the coil does not
receive power. Otherwise OFF.
–
( )
–
Positive
Transition
If power flow was OFF to this coil the last time it was executed
and is ON this time, then the coil is turned ON. Otherwise, the
coil is turned OFF.
–
( )
–
Negative
Transition
If power flow was ON to this coil the last time it was executed
and is OFF this time, then the coil is turned ON. Otherwise, the
coil is turned OFF.
–
(S)
–
SET
Sets the associated discrete reference ON if the coil receives
power. It remains set until reset by an
–
(R)
–
coil.
–
(R)
–
RESET
Sets the associated discrete reference OFF if the coil receives
power. It remains reset until set by an
–
(S)
–
coil.
–
(SM)
–
Retentive SET
Sets the associated reference is set ON if the coil receives
power. The reference remains set until reset by an
–
(RM)
–
coil.
Its state is retained through power failure and STOP-TO-RUN
transition.