PACMotion™ PSD Installation and User Manual
Section 6
GFK-3168A
September 2020
Setup
103
6.3
Fault and Warning Messages
6.3.1
Fault and warning messages from the PSD
PSD fault codes or warning codes are displayed constantly if present. Fault messages are coded
with "F", warnings are coded with "n".
When a fault occurs, the drive fault relay is opened, the output stage is switched off (motor loses all
torque), or the load is dynamically braked. The specific drive behavior depends on the type of fault.
The LED display on the front panel of the drive shows the number of the fault that occurred. If a
warning is issued prior to the fault, the warning is shown on the LED and has the same number as
the associated fault. Warnings do not trip the power stage of the drive or fault relay output.
The left side of the LED displays F (or E) for a fault or n for a warning. The right side displays the fault
or warning number as follows: 1-0-1-[break]. The highest priority fault is displayed. Multiple faults
may be present when a fault condition is occurring. Check the PACMotion Workbench Fault Screen
or read the status of DRV.FAULTS through the controller or HMI for the entire list of faults.
Note: Eliminate errors and faults in compliance with work safety rules. Troubleshooting only by
qualified and trained staff.
Note: More information about fault messages, remedy and clearing faults can be found in the
PACMotion Workbench Online Help.
Code
Message/Warning
..
24V power (X1) overload or 5V (X9) shorted
F0
Reserved.
F101, n101
Firmware incompatible. The FPGA is a laboratory FPGA.
F102, n102
Resident firmware failed. Operational FPGA is not a default FPGA.
F103
Resident FPGA failed.
F104
Operational FPGA failed.
F105
Non-volatile memory stamp invalid.
F106
Non-volatile memory data.
n107
Positive limit switch triggered.
n108
Negative limit switch triggered.
F120
Failed to default parameters.
F121
Homing error.
F123, n123
Invalid motion task.
F124
Cogging Compensation non volatile memory data error (CRC).
F125, n125
Fieldbus synchronization frames lost.
F126, n126
Bode plot: too much movement.
F127
Incomplete emergency procedure.
F128
MPOLES/FPOLES not integer.
F129
Fieldbus Heartbeat lost.
F130
Secondary feedback supply over current.
F131
Secondary feedback A/B line break.
F132
Secondary feedback Z line break.
F133
Fault number changed to F138.
F134
Secondary feedback illegal state.
F135, n135
Fault on feedback 2 prevents remote commutation on feedback 1.