10.3
Diagnostic Alarm
Events from IO-Link Master and IO-Link devices are mapped to PROFINET alarms and channel
diagnostics according to the IO-Link on
PROFINET Working Document Version 13.4.2015
with some
modifications.
10.3.1
IO-Link Event Mapping Overview
IO-Link events are mapped into PROFINET Alarms and Channel Diagnostics using the following table.
Each appearing IO-Link event (mode Coming) results in adding channel diagnostics. Each
disappearing IO-Link event (mode Going) results in removing channel diagnostics. IO-Link events that
have mode Single will be mapped to the PROFINET process alarm.
IO-Link Event Mapping
IO-Link Event Mode
PROFINET
Single
Process alarm
Coming
Add channel diagnostics
Going
Remove channel diagnostics
In addition, only IO-Link events that have the type of Error or Warning are mapped to PROFINET
channel diagnostics. Type Message IO-Link events are not mapped.
Note
: Process alarms are reported as ‘Unexpected PROFINET Alarms’ in the IO fault table of the PLC
.
10.3.2
IO-Link EventCode Mapping
IO-Link events that are generated by IO-Link devices (remote events) are mapped to PROFINET
diagnostics using ChannelErrorType 0x500 and0x501.
•
For an EventCode that is between 0x0000 and 0x7FFF, ChannelErrorType 0x500 is used. The
EventCode is directly mapped to ExtChannelErrorType.
•
For an EventCode that is between 0x8000-0xFFFF, ChannelErrorType 0x501 is used. The
EventCode is mapped to ExtChannelErrorType with the MSB set to 0.
•
For IO-Link events that are generated by IO-Link Master (local events), ChannelErrorType
0x502 is used.
•
EventCode is directly mapped to ExtChannelErrorType.
The following table summarizes how IO-Link EventCode is mapped to PROFINET diagnostics.
IO-Link EventCode Mapping
Source
EventCode
ChannelError
Type
ExtChannel
ErrorType
Comment
IO-Link
Device
(remote)
0x0000-0x7FFFF
0x500
0x0000-
0x7FFFF
Direct mapping of
EventCode to
ExtChannelErrorType (e.g.
EventCode 0x6321 will be
mapped to
ExtChannelErrorType
0x6321)
IO-Link
Device
(remote)
0x8000-0xFFFF
0x501
0x0000-
0x7FFFF
Mapping of EventCode to
ExtChannelErrorType. Set
MSB (EventCode) to “0”
(e.g. EventCode 0x8005
| ExtChannelErrorType
0x0005
IO-Link
Master
(local)
0x0000-0x7FFFF 0x502
0x0000-
0x7FFFF
Direct mapping of local
EventCode to
ExtChannelErrorType