background image

NetSure

 -48 VDC Power System 

User Manual, UM582137200 

Spec. No: 582137200 

 

Document Code:  UM582137200 

Model No: NetSure™ 5100 

 

Revision A, January 11, 2017 

[14 of 17]

 

Figure 7. 

Circuit Card Locations 

 

A CAN termination plug

(P/N 548398) must be

installed if an external

device or system is not

connected here.

System Interface Board

Rear

Rear

The IB2 Controller Interface Board

OR

The IB4 Second Controller Ethernet Port Board

Can Be Installed in the Distribution Unit

Slide Out Tray with

IB2

 Board Installed

Slide Out Tray with

IB4

 Board Installed

System

Interface

Board

10M Ethernet

Port (RJ-45)

LAN Connection

10M Ethernet

Port (RJ-45)

LAN Connection

USB-B Port

(Factory connected

to NCU Controller

backplane.)

USB-B Port

(Customer connected

to NCU Controller.)

USB-A Port

(not used)

USB-A Port

(not used)

Internal

IB4 Board

External

IB4 Board

IB2 Board

Содержание NetSure 5100

Страница 1: ...NetSure 48 VDC Power System User Manual UM582137200 Revision A January 11 2017 Specification Number 582137200 Model Number NetSure 5100 ...

Страница 2: ...NetSure 48 VDC Power System User Manual UM582137200 Spec No 582137200 Document Code UM582137200 Model No NetSure 5100 Revision A January 11 2017 This page is intentionally blank ...

Страница 3: ...r Documentation Package 1 System Description 1 Operating Procedures 1 Controller and Rectifier 1 ESTOP Function 2 Controller Battery Charge Current Limit Feature 2 Local Controls and Indicators 2 Maintenance 2 System Maintenance Procedures 2 Adding a Rectifier 2 Installing a Field Expansion Rectifier Shelf 2 Troubleshooting and Repair 8 Contact Information 8 Controller and Rectifier 8 Controller C...

Страница 4: ...ury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Alerts the reader to an action that must be avoided in order to protect equipment software data or service ISO ALERT Alerts the reader to an action that must be performed in order to preven...

Страница 5: ...t breakers remain de energized during installation DO NOT apply AC input power to the system until all electrical connections have been completed and checked DC Output and Battery Voltages DANGER This system produces DC power and may have a battery source connected to it Although the DC voltage is not hazardously high the rectifiers and or battery can deliver large amounts of current Exercise extr...

Страница 6: ...atteries Do not dispose of batteries in a fire They may explode ALWAYS FOLLOW THE BATTERY MANUFACTURER S RECOMMENDATIONS AND SAFETY INSTRUCTIONS DANGER This equipment may be used in conjunction with lead acid batteries Working near lead acid batteries is dangerous In addition to the hazard of electric shock gas produced by batteries can be explosive and sulfuric acid can cause severe burns Do not ...

Страница 7: ...NFPA 70E Standard for Electrical Safety in the Workplace Hazardous Voltage DANGER Hazard of electrical shock More than one disconnect may be required to de energize the system before servicing Handling Equipment Containing Static Sensitive Components ALERT Installation or removal of equipment containing static sensitive components requires careful handling Before handling any equipment containing ...

Страница 8: ...in one megohm resistor no external resistor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive components Handle equipment containing static sensitive components only by the edges that do not have connector pads 4 After removing equipment containing static sensitiv...

Страница 9: ...ntroller NCU NetSure Control Unit The controller provides power system control including optional low voltage battery disconnect LVBD and low voltage load disconnect LVLD control rectifier control including a charge control function metering functions monitoring functions local remote alarm functions and connections for binary inputs and programmable relay outputs via a controller interface board ...

Страница 10: ...g as battery voltage is above 47 VDC Local Controls and Indicators Controller and Rectifier Refer to the controller and rectifier instructions for descriptions of the local controls and indicators located on these units Maintenance System Maintenance Procedures It is recommended to perform the maintenance procedures listed in Table 1 every 6 months to ensure continual system operation Table 1 Main...

Страница 11: ...hese busbars to the expansion module mounting assembly with the hardware provided with the expansion module mounting assembly Secure these busbars to the main module mounting assembly with the hardware provided with the main module mounting assembly Refer to Figure 1 for hardware build up and torque 8 Disconnect the cable coming from the distribution unit that is connected to the left side as view...

Страница 12: ...rear shield from the expansion module mounting assembly MOUNTING HARDWARE 12 24 x 3 4 Thread Forming Hex Head Screw No 10 12 Ground Washer Torque 65 in lbs Install the ground washers so the teeth make contact with the metal on the mounting angles 23 Front AC Option Shown 19 Rear AC Option Similar Rear Shield Rear Shield Rear Rear Front 2 When the main module mounting assembly is configured with th...

Страница 13: ... Build Up Busbar M6 Flat Washer M6 Lock Washer M6 Hex Nut Torque to 52 in lbs Hardware Build Up Busbar M6 Flat Washer M6 Lock Washer M6 Hex Nut Torque to 52 in lbs 5 Install the busbars provided with the expansion module mounting assembly between the shelves Torque to52 in lbs Do this by removing the hardware from the main shelf busbars loosening the hardware on the expansion shelf busbars and sli...

Страница 14: ...ry 11 2017 6 of 17 Figure 1 Installing a Field Expansion Rectifier Shelf cont d from previous page Rear Installed View 6 Install the new rear shields supplied with the expansion module mounting assembly to the main module mounting assembly 7 Re install the rear shield previously removed onto the expansion module mounting assembly Rear ...

Страница 15: ...t List 01 Main Shelf List 02 Expansion Shelf Cable P N 555716 Provided with Expansion Shelf Field Installed Exploded View Shown to Illustrate Wire Connections Only Termination Resistor P N 548398 Termination Resistor P N RPM628350 2 Distribution Unit with List 01 Distribution Unit with List 01 and 02 Termination Resistor P N 548398 These Are Factory Connected Together These Are Factory Connected T...

Страница 16: ...ded the new current limit setpoint will be 100 of the combined capacity including the new rectifier module If a rectifier module is removed from the system and the Rect Comm Fail is cleared the current limit point will remain unchanged unless the capacity of the remaining rectifiers is not sufficient to maintain this current limit point If that happens the current limit point will automatically de...

Страница 17: ...LACING THE NCU CONTROLLER Refer to the NCU Controller Instructions UM1M830BNA for a controller replacement procedure REPLACING A DISTRIBUTION DEVICE Replace distribution devices with the same type and rating Refer to System Application Guide SAG582137200 for part numbers Replacing a GMT Distribution Fuse Procedure 1 Refer to Figure 3 and replace the fuse Ensure a safety fuse cover is installed on ...

Страница 18: ...l No NetSure 5100 Revision A January 11 2017 10 of 17 Figure 3 GMT Distribution Fuse Replacement List BA BC BF LC NA NC NF Figure 4 Installation of Safety Fuse Covers GMT Fuse Safety Cover Front List BA shown List BC BF LC NA NC NF similar Safety Cover P N 248898700 GMT X Safety Cover P N 102774 GMT Y ...

Страница 19: ...ockets on distribution unit Insert these terminals into corresponding sockets on distribution unit Shorter Side of Breaker Longer Side of Breaker Longer Side of Breaker Turn circuit breaker off before installing OFF Position Towards Center List BC shown List LC NC similar Load Disconnect Circuit Breakers Front Components removed in illustration for clarity only Load Distribution Circuit Breakers I...

Страница 20: ...mper and Switch Options section of the Power System Installation Instructions IM582137200 8 Orient the replacement circuit card over its mounting position and secure with the screws removed from the old circuit card 9 Plug all connectors removed from the old circuit card into the same position on the replacement circuit card 10 Reinstall the rear top cover to the distribution unit 11 Remove the gr...

Страница 21: ...riate personnel that this procedure is finished 16 Ensure that there are no local or remote alarms active on the system Replacing the IB4 Board if furnished Procedure NOTE Refer to Figure 9 as this procedure is performed 1 Performing this procedure may activate external alarms Do one of the following If possible disable these alarms If these alarms cannot be easily disabled notify the appropriate ...

Страница 22: ...ard Rear Rear The IB2 Controller Interface Board OR The IB4 Second Controller Ethernet Port Board Can Be Installed in the Distribution Unit Slide Out Tray with IB2 Board Installed Slide Out Tray with IB4 Board Installed System Interface Board 10M Ethernet Port RJ 45 LAN Connection 10M Ethernet Port RJ 45 LAN Connection USB B Port Factory connected to NCU Controller backplane USB B Port Customer co...

Страница 23: ... or system is not connected here System Interface Board 1 2 3 No Battery Pwr Battery Pwr Shorting Jumper J4 Selects to power controller from Battery Power or not if a battery LVD contactor is furnished J4 1 2 3 System Temp 1 System Temp 2 CAN Port RJ 45 H1 J1 J2 J3 J4 J7 J8 R1 R2 R3 1 1 1 1 BATT PW R 562209 0 0 0 X X X X X A X X X X X X X X System Interface Board P N 562209 J3 Wire Size Capacity 1...

Страница 24: ...4 2 8 7 6 5 4 3 2 1 NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC NO C NC 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 5 3 1 4 6 2 Relay No Relay No Input No Input No 8 7 6 5 4 3 2 1 ON OFF 1 2 Rear The IB2 Controller Interface Board OR The IB4 Second Controller Ethernet Port Board Can Be Installed in the Distribution Unit Slide Out Tray with IB2 Board Installe...

Страница 25: ... power systems and outside plant enclosures for customers and channel partners Reps VARs Distributors Phone 1 800 800 1280 option 2 Spare Parts Email DCpower Spares Emerson com OSP Spares Emerson com Pricing and purchase orders for spare parts including but not limited to breakers cables fuses rectifier fans misc breaker and fuse panels enclosure fans doors and switches etc Phone 1 800 800 1280 op...

Страница 26: ...on Network Power Energy Systems North America Inc Any copying use or disclosure of it without the written permission of Emerson Network Power Energy Systems North America Inc is strictly prohibited Names of companies and products are trademarks or registered trademarks of the respective companies Any questions regarding usage of trademark names should be directed to the original manufacturer Emers...

Отзывы: