90 Chapter 6 Use Of Monitoring Module M501D
change the sequence number of the module, and then press ENT key to confirm. The bottom line of the display
screen will display the last 10 digits of the serial number of the module. 2) Use the ▲ or ▼ key to shift the cursor to
the control operation option block and select the suitable value with the ◄ or ► key.
If the rectifier is blocked upon over-voltage, the user can reset the rectifier with ‘reset’ operation.
6. There is confirmation information prompt for the control command. If the control command can be executed, the
system prompts to press ENT for confirmation, and then the control action becomes valid, or the user can press the
ESC key to abandon the operation. If the control conditions are not satisfied, the monitoring module will prompt that
the control operation cannot be conducted.
Don't Maintain!
ESC return.
Press ENT to run
ESC Key Quit.
7. Press the ESC key on any Maintenance screen, the user can directly return to the ‘main menu 4 system control
output’. Repeatedly press the ESC key, the user can return to the root screen of the system information screen.
6.7 Setting System Parameters
Battery parameters are very important, for they are related to the life of battery. Before delivery, the battery
parameters have been initialized. Without any special needs, you only need to reset the battery group number and
battery capacity, and accept the defaults for other parameters.
6.7.1 Parameter Setting Method
1. At any system information page, press ENT to enter the main menu.
MAINMENU
Status
Maintenance
Settings
2. Press ▲ or ▼ to select the submenu ‘Settings’ and press ENT to confirm. System will then prompt you to input the
password.
Enter Password:
123456
3. Press ◄ or ► to select the number of password digits. Enter the password digit by digit using ▲ or ▼. Press ENT
to confirm and enter the parameter setting submenu.
SETTINGS
Alarms Settings
Batt Settings
AC Settings
SETTINGS
DC Settings
Rect Settings
Sys Settings
Users with different password levels are entitled to set different types of parameters or operation types, shown as
follows:
Table 1.1 Different password levels and revelant operation types
Level
Operation authority
Default password
User
Configuration of general parameters
1
Operator
User’s authority, plus resetting system, resetting password and modifying system type.
2
Administrator
Operator’s authority, plus modifying password of all levels, controling alarm sound volume,
browsing system parameters that can be set only through the host
640275
NetSure 501 A50, NetSure 501 AA0, NetSure 701 A51 19-Inch Subrack Power Supply System User Manual