applying the grease, use the appropriate tools to fit and tighten the sensor to the
transmitter or junction box enclosure.
The transmitter and junction box have mounting holes to allow mounting to a flat surface
or pole as desired. Mounting kit accessories are available to aid in mounting the detector
to a flat surface or a pole. Contact your local Net Safety representative for detailed
information.
Note
Always mount the sensor vertically such that its mouth is pointed in the downward
position as shown in
.
Figure 2-2: Sensor Mounted to a Net Safety Millennium II Transmitter
A.
¾
-in. national pipe thread (NPT)
B. ATEX locking collar
C. Sensor pointing downwards
D. Sensor mouth
Reference Manual
Install
00809-0100-4303
November 2020
Net Safety ST3
11