Variable
Setting
Discrete Outputs (optional)
—
Power (Internal or External):
—
Source:
—
Scaling (LRV, URV):
—
Fault Action:
Discrete Input (optional)
—
Power (Internal or External):
—
Source:
—
Scaling (LRV, URV):
—
Fault Action:
RS-485
Address:
Calibration parameters (for 9-wire installations only)
Flow calibration factor
FCF (Flow Cal or Flow Calibration Factor):
Density calibration factors
—
D1:
—
D2:
—
K1:
—
K2:
—
TC:
—
FD:
2.3
Power requirements
Self-switching AC/DC input, automatically recognizes supply voltage:
•
85 to 240 VAC, 50/60 Hz, 6 watts typical, 11 watts maximum
•
18 to 100 VDC, 6 watts typical, 11 watts maximum
Note
For DC power:
•
Power requirements assume a single transmitter per cable.
•
At startup, the power source must provide a minimum of 1.5 amps of short-term
current per transmitter and not pull voltage below 18 VDC.
•
Length and conductor diameter of the power cable must be sized to provide 18 VDC
minimum at the power terminals, at a load current of 0.7 amps.
Cable sizing formula
M = 18V + (R x L x 0.7A)
•
M: minimum supply voltage
•
R: cable resistance
•
L: cable length (in Ω/ft)
Installation Manual
Planning
MMI-20027478
February 2020
Installation Manual
9