![Emerson Micro Motion 5700 Скачать руководство пользователя страница 55](http://html.mh-extra.com/html/emerson/micro-motion-5700/micro-motion-5700_installation-manual_104641055.webp)
A
5700 to 3100 transmitter
connections
Use this section as a reference when wiring a 5700 transmitter to a 3100 transmitter.
The following graphic sets Channel B, configured as DO1, to relay 1. If a different channel
is assigned to DO, wire any DO to any relay.
•
Set up the transmitter channel configuration to DO before wiring.
•
Use active high and internal power.
•
Tie the three ground pins of the 5700 together and then land on A14 of the 3100. The
ground pins are even numbers: 4, 6, and 8.
Example (see the following figure): Use relay 1 (C) and 2 (B) with Channels B and C,
then connect terminal 2 and 4 together from 5700 and land on A14.
•
Land each positive power terminal on C14, C16, and C18.
Example: Using the same example as above, land 1 (Channel B) on C14 for relay 1, and
3 (Channel C) on C16 for relay 2.
•
Use wire size 24 AWG (0,25 mm
2
) to 16 AWG (1,5 mm
2
).
Figure A-1: 5700 to 3100 - screw-type or solder-tail connector
F3
C
A
IEC 127-2
J 3
DISC
OUT 3
T5A
250V
C
A
F1
C
A
IEC 127-2
J 1
J 4
MODEL 3300/3500
TERMINAL
CONNECTION
DS1
T5A
250V
K3
K2
K1
A
B
C
'
(
)
DISC
OUT 2
IEC 127-2
F2
T5A
250V
J 2
DS2
DISC
OUT 1
DS3
1
2
3
4
5
6
7
8
9
1
0
A14
C18
C16
C14
A. Relay 3, DO 3 pins 6 and 7, C18
B. Relay 2, DO 2 pins 5 and 6, C16
C. Relay 1, DO 1 pins 3 and 4, C14
D. Channel D
E. Channel C
F. Channel B
Installation Manual
5700 to 3100 transmitter connections
MMI-20027478
February 2020
Installation Manual
55