5.2.1
Enable or disable Totalizer Start/Stop from the display
Display
OFF-LINE MAINT
>
OFF-LINE CONFG
>
DISPLAY
>
TOTALS STOP
ProLink II
ProLink
>
Configuration
>
Display
>
Display Options
>
Display Start/Stop Totalizers
ProLink III
Device Tools
>
Configuration
>
Totalizer Control Methods
Field Communicator
Configure
>
Manual Setup
>
Display
>
Display Variable Menu Features
>
Start/Stop Totalizers
Overview
You can control whether or not the operator is able to start and stop totalizers and
inventories from the display.
Restrictions
•
You cannot start and stop totalizers individually from the display. All totalizers are started or
stopped together.
•
You cannot start or stop inventories separately from totalizers. When a totalizer is started or
stopped, the associated inventory is also started or stopped.
•
If the petroleum measurement application is installed on your computer, the operator must
enter the off-line password to perform this function, even if the off-line password is not
enabled.
Procedure
1.
Ensure that at least one totalizer is configured as a display variable.
2.
Enable or disable
Totalizer Reset
as desired.
Option
Description
Enabled
Operators can start and stop totalizers and inventories from the display,
if at least one totalizer is configured as a display variable.
Disabled
(default)
Operators cannot start and stop totalizers and inventories from the dis-
play.
5.2.2
Enable or disable Totalizer Reset from the display
Display
OFF-LINE MAINT
>
OFF-LINE CONFG
>
DISPLAY
>
TOTALS RESET
ProLink II
ProLink
>
Configuration
>
Display
>
Display Options
>
Display Totalizer Reset
ProLink III
Device Tools
>
Configuration
>
Totalizer Control Methods
Field Communicator
Configure
>
Manual Setup
>
Display
>
Display Variable Menu Features
>
Totalizer Reset
Overview
You can configure whether or not the operator is able to reset totalizers from the display.
Configure device options and preferences
Configuration and Use Manual
83
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......