Overview
Damping is used to smooth out small, rapid fluctuations in process measurement.
Damping
Value
specifies the time period (in seconds) over which the transmitter will spread changes
in the reported process variable. At the end of the interval, the reported process variable
will reflect 63% of the change in the actual measured value.
Procedure
Set
Density Damping
to the value you want to use.
The default value is 1.6 seconds. The range depends on the core processor type and the
setting of
Update Rate
, as shown in the following table:
Core processor type
Update Rate
setting
Density Damping
range
Standard
Normal
0 to 51.2 seconds
Special
0 to 10.24 seconds
Enhanced
Not applicable
0 to 40.96 seconds
Tips
•
A high damping value makes the process variable appear smoother because the reported value
changes slowly.
•
A low damping value makes the process variable appear more erratic because the reported value
changes more quickly.
•
Whenever the damping value is non-zero, the reported measurement will lag the actual
measurement because the reported value is being averaged over time.
•
In general, lower damping values are preferable because there is less chance of data loss, and less
lag time between the actual measurement and the reported value.
The value you enter is automaticaly rounded down to the nearest valid value. The valid
values for
Density Damping
depend on the setting of
Update Rate
.
Valid values for Density Damping
Table 4-11:
Core processor type
Update Rate
setting
Valid damping values
Standard
Normal
0
,
0.2
,
0.4
,
0.8
, ...
51.2
Special
0
,
0.04
,
0.08
,
0.16
, ...
10.24
Enhanced
Not applicable
0
,
0.04
,
0.08
,
0.16
, ...
40.96
Effect of Density Damping on volume measurement
Density Damping
affects liquid volume measurement. Liquid volume values are calculated
from the damped density value rather than the measured density value.
Density Damping
does not affect gas standard volume measurement.
Configure process measurement
Configuration and Use Manual
49
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......