Options for mA Output Fault Action and mA Output Fault Level
(continued)
Table 6-4:
Option
mA output behavior
mA Output Fault Level
None
Tracks data for the assigned process vari-
able; no fault action
Not applicable
CAUTION!
If you set
mA Output Fault Action
or
Frequency Output Fault Action
to
None
, be sure to set
Digital
Communications Fault Action
to
None
. If you do not, the output will not report actual process data,
and this may result in measurement errors or unintended consequences for your process.
Restriction
If you set
Digital Communications Fault Action
to
NAN
, you cannot set
mA Output Fault Action
or
Frequency
Output Fault Action
to
None
. If you try to do this, the transmitter will not accept the configuration.
6.3
Configure the frequency output
The frequency output is used to report a process variable. The frequency output
parameters control how the process variable is reported. Your transmitter may have zero
or one frequency output: Channel B can be configured as a frequency output or a discrete
output.
The frequency output parameters include:
•
Frequency Output Process Variable
•
Frequency Output Polarity
•
Frequency Output Scaling Method
•
Frequency Output Maximum Pulse Width
•
Frequency Output Fault Action
and
Frequency Output Fault Value
Important
Whenever you change a frequency output parameter, verify all other frequency output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
6.3.1
Configure Frequency Output Process Variable
Display
OFF-LINE MAINT
>
OFF-LINE CONFG
>
IO
>
CH B
>
SET FO
>
FO SRC
ProLink II
ProLink
>
Configuration
>
Frequency/Discrete Output
>
Frequency
>
Tertiary Variable
ProLink III
Device Tools
>
Configuration
>
I/O
>
Outputs
>
Frequency Output
Field Communicator
Configure
>
Manual Setup
>
Inputs/Outputs
>
Frequency Output
>
FO Settings
>
Third Variable
Integrate the meter with the control system
108
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......