Options for mA Output Process Variable
(continued)
Table 6-1:
Process variable
Label
Display
ProLink II
ProLink III
Field Communicator
Concentration measurement
Density at reference
RDENS
CM: Density @ Reference Density at Reference
Temperature
ED Dens at Ref
Specific gravity
SGU
CM: Density (Fixed SG
units)
Density (Fixed SG Units)
ED Dens (SGU)
Standard volume flow
rate
STD V
CM: Std Vol Flow Rate
Volume Flow Rate at Ref-
erence Temperature
ED Std Vol flo
Net mass flow rate
NET M
CM: Net Mass Flow Rate
Net Mass Flow Rate
ED Net Mass flo
Net volume flow rate
NET V
CM: Net Vol Flow Rate
Net Volume Flow Rate
ED Net Vol flo
Concentration
CONC
CM: Concentration
Concentration
ED Concentration
Baume
BAUME
CM: Density (Fixed
Baume Units)
Baume
ED Dens (Baume)
6.2.2
Configure Lower Range Value (LRV) and Upper Range
Value (URV)
Display
•
OFF-LINE MAINT
>
OFF-LINE CONFG
>
IO
>
CH A
>
AO 4 mA
•
OFF-LINE MAINT
>
OFF-LINE CONFG
>
IO
>
CH A
>
AO 20 mA
ProLink II
•
ProLink
>
Configuration
>
Analog Output
>
Primary Output
>
Lower Range Value
•
ProLink
>
Configuration
>
Analog Output
>
Primary Output
>
Upper Range Value
ProLink III
Device Tools
>
Configuration
>
I/O
>
Outputs
>
mA Output
Field Communicator
•
Configure
>
Manual Setup
>
Inputs/Outputs
>
mA Output
>
mA Output Settings
>
PV LRV
•
Configure
>
Manual Setup
>
Inputs/Outputs
>
mA Output
>
mA Output Settings
>
PV URV
Overview
The
Lower Range Value
(LRV) and
Upper Range Value
(URV) are used to scale the mA output,
that is, to define the relationship between
mA Output Process Variable
and the mA output
level.
Note
For transmitter software v5.0 and later, if you change
LRV
and
URV
from the factory default values,
and you later change
mA Output Process Variable
,
LRV
and
URV
will not reset to the default values. For
example, if you set
mA Output Process Variable
to
Mass Flow Rate
and change the
LRV
and
URV
, then you
set
mA Output Process Variable
to
Density
, and finally you change
mA Output Process Variable
back to
Mass
Flow Rate
,
LRV
and
URV
for
Mass Flow Rate
reset to the values that you configured. In earlier versions of
the transmitter software,
LRV
and
URV
reset to the factory default values.
Integrate the meter with the control system
102
Micro Motion
®
Model 2700 Transmitters with Analog Outputs
Содержание MICRO MOTION 2700
Страница 10: ...Getting Started 2 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 14: ...Before you begin 6 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 26: ...Configuration and commissioning 18 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 84: ...Configure process measurement 76 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 142: ...Integrate the meter with the control system 134 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 154: ...Set up the Weights Measures application 146 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 156: ...Operations maintenance and troubleshooting 148 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 214: ...Measurement support 206 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 258: ...Troubleshooting 250 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 327: ...Device Tools Trending Figure C 24 Using ProLink III with the transmitter Configuration and Use Manual 319 ...
Страница 328: ...Using ProLink III with the transmitter 320 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 354: ...Default values and ranges 346 Micro Motion Model 2700 Transmitters with Analog Outputs ...
Страница 373: ......