Configuring and operating the system
63
User Manual
UM6C55C (P7000597)
Lorain Power System (AP6C55CA/CB)
Standard 10.00 (March 2008)
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 5.8 – Structure of the SETTINGS menu
SETTINGS/BATTERY TYPE
None
CHNG
Change System Voltage
-54.5
APPL
None
VRLA
Enersys
GNB Marathon
GNB Absolyte IIP
DEKA Unigy I
Hawker SBS60
FIAM FAT
POWERSAFE HB/VF
SAFT NCX
APPL
SETTINGS/RESET
Reset to User Default
RESET
Do you really want to
Reset to User Default
YES NO
12 Hours
No Shut Off
5 Minutes
30 Minutes
APPL
SETTINGS/SYS VOLTAGE
System Voltage: -54.5V
CHNG
English_NA
APPL
English
Set Date
20030721 YYYYMMDD
SET
SETTINGS/DISP AUTOOFF
12 Hours
CHNG
Change Contrast
CONTRAST 8
APPL
CHNG
SETTINGS/LANGUAGE
English-NA
CHNG
SETTINGS/DATE
2003-07-21
SET
Set Time
1552 HHMM
CHNG
SETTINGS/CONTRAST
CONTRAST 8
CHNG
SETTINGS/TIME
15:52
SETTINGS/CHARGE CONT
Deactivated
CHNG
CHNG
SETTINGS/LOW VOLTAGE
BOD –51.0 LV –47.0
CHNG
SETTINGS/TEMP COMPENS
Activated
CHNG
SETTINGS/BATTERY TEST
Deactivated
TEMP COMPENSATION/STA
Activated
APPL
APPL
BATTERY TEST/STATUS
Deactivated
SETTINGS/LOAD DIS
LVD1 Volt, LVD2 Volt
CHNG
LOAD DIS/DISC MODE
LVD1 Volt, LVD2 Volt
CHG
LVD1 Time, LVD2 Time
LVD1 Volt, LVD2 Volt
APPL
CHARGE CONTROL/STATUS
Activated
CHNG
LOW VOLTAGE/LOW VOLTAGE
CHNG
Low Voltage –47.0V
Refer to section 5.5.7.13 for additional
menu selections for the LVD settings.
5.5.7.1. System Voltage
This submenu is used to set the nominal system voltage. The actual system
voltage may differ from the nominal system voltage if one or more of these
functions is/are active: temperature compensation, a boost charge, a battery
test or battery current limiting. To change the nominal system voltage, press
CHNG. In the next screen, use the
and
buttons to change the voltage in
increments of 0.1 V. Save the new value by pressing the APPL button.