Operation
33
Liebert
®
NXL
™
9. Close all Battery/DC breakers associated with this module. The UPS will stay in this mode until
all breakers are closed.
Skip this command if the DC sources are not ready to be started. The DC breakers can be closed
later from the startup command (see
).
.
The UPS is ready to be placed online. Go to the SCC Startup screen to complete the startup.
2.15.3 Startup—1+N System
This section lists typical step-by-step instructions. The touchscreen will list all steps required for the
process, based on the unit’s condition and other factors.
NOTICE
Risk of equipment damage. If an abnormal situation occurs during this startup procedure, open
the input circuit breaker and investigate the problem. Call Liebert Services if help is needed.
NOTE
The DC source charge current may increase quickly, but should slowly decrease. If the system is
recovering from a DC source shutdown or an input power failure, the UPS rectifier will be
recharging the battery. Recharge current can be more than 100A. The maximum allowable
recharge current for a unit depends on the kVA rating and the DC source recharge current limit.
!
WARNING
Risk of electrical shock and high short circuit current. Can cause equipment damage, personal
injury and death.
If the UPS has been shut down for maintenance, verify that all of the UPS system doors are
closed and latched. All test equipment must be removed from the system. All electrical
connections must be secure.
!
WARNING
Risk of electrical shock. Can cause equipment damage, personal injury and death.
The following procedure may provide power to the critical load distribution system. Verify
that the critical load distribution is ready to accept power. Make sure that personnel and
equipment are ready for the critical load distribution system to be energized.
NOTE
If the system was shut down in response to an “Emergency Off,” there may be alarm messages
on the touchscreen that describe system conditions before or at the time of the shutdown. Some
or all of the alarm conditions may have been resolved.
To clear these alarm messages, turn Off control power (see
and
). Wait at least
10 minutes for the control power circuitry to completely de-energize. After 10 minutes, turn
control power back On.
Содержание Liebert NXL 250 kVA
Страница 8: ...vi ...
Страница 51: ...Operation 43 Liebert NXL Figure 42 1 N UPS Transfer to Inverter menu commands ...
Страница 57: ...Operation 49 Liebert NXL Figure 45 1 N UPS shutdown menu commands ...
Страница 86: ...Specifications Liebert NXL 78 ...
Страница 110: ...UPS Alarm and Status Messages Liebert NXL 102 NOTES ...
Страница 111: ......