background image

Liebert

®

 IntelliSlot

®

 Web/485 Card 

With Adapter

Quick Start Guide

I

NSTALL

• Locate the adapter mounting location within your Liebert 

equipment.

• Secure the card with the supplied screws.

• Connect the equipment’s communication cable to the TB1 terminal 

block or P1 on the card (See equipment user manual for details).

• Connect an Ethernet cable to RJ45.
• Connect a Modbus (RS-485) cable to the TB2 terminal block.
• Connect an input power supply cable to Pins 1 & 2 on the TB3 terminal 

block; Pin 1 is at the far left, and Pin 2 is the middle pin.

DHCP

: The card ships with DHCP service enabled. The MAC address is 

printed on a sticker affixed to the top of the card.

OR

Static IP

: To assign a static IP address, use the Service Terminal to con-

figure the card. Proceed to Steps 2 & 3.

C

ONNECT

 

THE

 C

ABLE

• Connect a configuration cable (null modem) to the DB-9 port 

on the card and to a COM port on your PC. The configuration 

cable is available separately from Emerson (P/N LIEBNULL).

C

ONFIGURE

 

THE

 C

ARD

• Use terminal emulation software, 

such as HyperTerminal

, to open a 

direct connection to the card.

• Press 

Enter

 for the 

Main Menu

.

• Select option 

2

 and follow the instructions to 

enter an IP ADDRESS, NETMASK and 

GATEWAY.

• Press 

Esc

 to return to the 

Main Menu

.

• Enter 

X

 to save your changes and reboot the card.

TB2

(P1: +)

(P2: -);

P1 is at 

the right side 

of terminal block.

Network Port 

for NMS and 

Web Access

TB3

(P1: +)

(P2: -)

(P3: NC)

P1 is on the 

left end of 

terminal 

block.

DB-9

Port

MAC Address

P1

TB1 (P1: +; P2: -); P1 is at 

the right side of terminal block.

Terminal Emulation

Software Configuration

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control: None