Liebert IntelliSlot

®

 OC-485 Card

Quick Start Guide

I

NSTALL

• Locate the Intellislot option bay for your Liebert equipment. You might 

need to remove a plastic cover.

• Insert the Liebert IntelliSlot OC-485 Card into the Intellislot bay.
• Secure the card with the supplied screws.
• Connect RS-485 cable.

IGM

: The card ships with IGM service enabled. (No configuration is 

required for IGM communications.)

Modbus

: To assign a server ID address, use the Service Terminal to con-

figure the card. Proceed to Steps 2 & 3.

C

ONNECT

 

THE

 C

ABLE

• Locate the blue serial configuration cable (null modem) that shipped 

with the card.

• Connect the configuration cable to the DB-9 port on the card and to a 

COM port on your PC.

C

ONFIGURE

 

THE

 C

ARD

• Use terminal emulation soft-

ware, such as HyperTerminal™, 

to open a direct connection to 

the card.

• Press 

ENTER

 for the Main 

Menu, above right.

• Select option 

1

 and press 

Enter

 

to access the communications 

settings, shown at right.

• Enter 

1

 and press 

enter

 to 

enable the Modbus application.

• At the next screen, enter 

3

 to 

access the screen to set the 

server ID for the Liebert 

IntelliSlot OC-485 Card (the ID 

default is 1, but may be any 

number up to 255). In the 

example at right, the server ID 

is “2.”

• Press 

Esc

 to return to the main 

Menu.

• Enter 

X

 and press 

Enter

 to exit 

HyperTerminal, save your 

changes and reboot the card.

Baud Rate:

9600

Data Bits:

8

Parity:

None

Stop Bits:

1

Flow Control:

None

NOTE

When installing the card in a Liebert NX

, configure the 

communication port of the Liebert NX to 2400 baud.  Refer to the 

Liebert NX user manual for instructions.