Liebert iCOM Display Components and Functions
7
Liebert
®
iCOM
®
for Liebert DSE
™
Unit Screen with Rack View of Sensors
The temperatures shown at the top of the unit screen with rack view of sensors are determined by the
configuration of the Liebert iCOM. The values are based on which sensors are used for controlling
airflow, cooling capacity and humidification.
The data at the upper left of the screen can be either average or maximum rack temperature,
depending on the selection in the Remote Sensors Mode. The data at the upper middle of the screen
can be either dew point or relative humidity, depending on humidity control type.
Each unit can display individual remote rack sensors. The reading will be either an average or
maximum reading between the two sensors connected at each 2T sensor module.
The bar graph's upper limit is set at 77°F (25°C). The lower limit is set at 68°F (20°C), the rack inlet
temperature range recommended by ASHRAE. When a rack temperature is at or above the upper
limit, the bar graph will be all black. When a rack temperature is at or below the lower limit, the bar
graph will be all white.
Figure 7
Unit screen with rack view of sensors
Can be either
average
temperature
or maximum
temperature
Can be either dew point
or relative humidity
Arrow will be
shown when
compensation is
being performed