Specifications
55
Liebert
®
GXT4
™
User Manual
Table 8-3
External battery cabinet specifications
Model Number
GXT4-240VBATT
Used with UPS Model
GXT4-5000RT230; GXT4-6000RT230; GXT4-10000RT230
Dimensions, W x D x H, mm (in.)
Unit (with bezel)
430 x 581 x 173 (16.9 x 22.9 x 6.8)
530 x 745 x 475 (20.9 x 29.3 x 18.7)
Shipping
Weight, kg (lb)
Unit
65 (143.3)
Shipping
80 (176.4); “E” models 76 (167.6)
Battery Parameters
Type
Valve-regulated, non-spillable, lead acid
Quantity x V
1 x 20 x 12V
Battery Manufacturer, Part #
9AH; CSB UPS12460F2 or CSB HR1234WF2
Backup Time
Environmental
Operating Temp, °C (°F)
0 to 40 (32 to 104)
Storage Temp, °C (°F)
-15 to 50 (5 to 122)
Relative Humidity
0-95% non-condensing
Operating Elevation
Up to 1000m (3280.83 ft.) at 25°C (77°F)
Agency
Safety
IEC62040-1:2008 version
Transportation
ISTA Procedure 1E
Содержание Liebert GXT4-10000RT230
Страница 1: ...Liebert GXT4 UPS 230 V 5000 VA 10 000 VA User Manual ...
Страница 2: ......
Страница 44: ...Operation and Display Panel Liebert GXT4 User Manual 36 Page intentionally left blank ...
Страница 52: ...Communication Liebert GXT4 User Manual 44 Page intentionally left blank ...
Страница 60: ...Troubleshooting Liebert GXT4 User Manual 52 Page intentionally left blank ...
Страница 67: ......