Liebert CRV Component Location
7
Liebert
®
CRV
™
Figure 3
Overall dimensions, service area—600mm (24") models
Table 1
Dry weight, all model types, ± 5%
Model No.
Model Type
Air Cooled
lb (kg)
Water/Glycol
lb (kg)
Chilled Water
lb (kg)
CR020R
739 (335)
772 (350
—
CR035R
805 (365)
849 (385)
—
CR040R
—
—
728 (330)
Source: DPN001791, Rev. 2
Access required to service the
Liebert CRV within the row.
Rear service area is S+B or S+A
when B is not available.
12"
(305mm)
Nominal
78-3/4"
(2000mm)
25-9/16"
(650mm)
25-9/16"
(650mm)
107-5/16"
(2725mm)
13-3/4"
(350mm)
46-1/4"
(1175mm)
21-5/8"
(550mm)
35-9/16"
(903mm)
3-5/16"
(100mm)
3-15/16"
(100mm)
27-9/16"
(700mm)
Air Filters
23-5/8"
(600mm)
23-5/8"
(600mm)
Install
Install
49" (1245mm)
49" (1245mm)
Hot Air
46-1/4" (1
175mm)
3" (75mm)
Cold Air
REAR
REAR VIEW
FRONT
DPN001791
Rev. 3
A
S
S
TOP VIEW
B
Door
Fully
Open
Front or Rear
Clearance Required
Access required for installation of
the Liebert CRV within the row.
For proper airflow distribution:
Align the front door of neighboring
server racks with the front corner
of the Liebert CRV