Remote Rack Sensor Wiring
151
Liebert
®
CRV
™
Figure 132 2T rack sensors installed on neighboring racks-300mm (12") models
The sensors can be set up to either display or control temperature, give them a rack name and draw a
rack layout that can be viewed in the User menu. To do so, go to the Service / Rack Setup Menu of the
Liebert iCOM
®
display.
DPN002975
REV 0
REAR VIEW
Temperature sensing probes
FRONT VIEW
Cable Connection Entry
Top Inlet
Remove terminating
plug. Install terminating
plug into last sensor.
Install CAN cable
into the slot previously
occupied by the
terminating plug.
Liebert IntelliSlot temperature sensor
located in the rear of the unit.
Bottom inlet see DPN002813 for Air, Water/Glycol
units and DPN002815 for Chilled Water units.
Install temperature sensors on the perforated
portion of the rack door using the supplied
wire ties. Ensure door can swing open freely
without binding cables.
Approximate
center of
rack in front
of equipment
12"
(305mm)
Maximum Depth
1-5/8" (41mm)
Each temperature
probe wire is
6ft (1.8m) long
3/16"
(4mm)
4-3/8"
(112mm)
86
(3 3/8")
1-5/8"
(41mm) 2 5/8"
(67mm)
Sensor wire enters 300mm
(12") Liebert CRV’s at rear;
refer to Figure 130.