Installation Drawings
Liebert
®
APM
™
62
7.0
I
NSTALLATION
D
RAWINGS
The diagrams in this section illustrate the key mechanical and electrical characteristics of the Liebert
APM UPS System cabinets (UPS, Liebert BDC and battery).
Figure 47 UPS dimensions- front view
Figure 48 Lineup arrangement, Liebert APM with battery and Liebert BDCs
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit;
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4.Top and bottom cable entry available through
removable access plates.
Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in
separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national
and local electrical codes.
9. All battery cabinets must be positioned on the
left side of the UPS.
FRONT VIEW
UAM03000
Rev. 0
UPS
Battery
Cabinet #1
78.7"
(2000mm)
55.4" (1408mm)
23.8" (604mm)
Total Width with Additional Battery Cabinets
Total Width
In. (mm)
79.1 (2008)
102.7 (2608)
126.3 (3208)
Number of
Battery Cabinets
2
3
4
UAM03001
Rev. 1