background image

Example of correct 

installation 

: The inside 

diameter of the pipe/flange 

is Schedule 40 pipe inside 

diameter or less. The 

pipe/flange presents a flat 

face to the seat. 

Typical F955 valve. DN150 with 

schedule 40 pipe shown.

Example of incorrect 

installation

 : Void area of 

pipe flange/pipe connection 

does not support seat 

sufficiently. Fillet weld 

between pipe and flange 

shown creates this void area. 

Thin walled pipes can also 

fail to support seats.

A

B

KEYSTONE

 KNIFE GATE VALVES

FIGURE 955/956

Storage and installation instructions for F955 ported slide gate valves and F956 dual gland ported slide gate valves

STORAGE

IMPORTANT

Do not remove any identification or instruction 
tags from the valve assembly.
For optimum protection, undercover storage is 
desirable.

Valves

Flange faces should be protected at all times 
with wooden, or heavy cardboard shields. 
Valves should be handled carefully to prevent 
damage to exterior protective coating. Flange 
bolt holes should be coated with a suitable 
rust inhibitor for prolonged or exterior storage. 
Care should be taken in the placement of valves 
in storage to assure excessive pressure is not 
placed on polymer body shrouds or spindle 
covers so as to cause component damage.

F955 

valves should be stored in the closed 

position.

F956

 valves should be stored in the open 

position.
Handwheel spindle thread should NOT be 
lubricated as dirt will accumulate in threads.

VCIOM-02872-EN 17/05

INSTALLATION INSTRUCTIONS

Heavy valves will require a chain block 
or crane to assist in the installation. 
In difficult installations, large actuator 
cylinders may be removed from the valve 
and re-fitted after installation. When re-fitting 
the actuator cylinder care must be taken 
to ensure the cylinder/valve alignment is 
maintained (refer cylinder fitting instruction 
sheet). Larger actuated valves installed in 
vertical pipework will require structural 
support to take the weight of the actuator. 
This support may also be desirable in larger 
valves installed in non-vertical positions.

The F955/F956 is configured for installation 
in conventional bolted flange connections. 
Flanges are required to support the seat by 
presenting a flat surface across the seat. If 
the flange does not present a flat surface 
then companion flanges can be used. The 
companion flanges should be raised or flat 
face type to ensure full sleeve support and a 
continuous, unvarying I.D.  If slip-on flanges 
are used without companion flanges, the pipe 
should be cut square and welded in position 
with the pipe end matched evenly with the 
flange face. (see below diagram)

CAUTION 

Care must be taken with the installation of the 
F955/F956 valve to resilient faced companion 
flanges. Excessive tightening of the flange bolts 
will result in severe valve seat damage on valve 
actuation. Companion flange bolts must only be 
tightened as noted below.

1.  Close valve.
2.  Check the valve size is correct and there 

is adequate clearance to install the valve.

3.  Check valve and pipe flange faces are clean 

and smooth, and that the valve bolt pattern

  is the same as the flange.
4.  Check flange bolt sizing and ensure the bolt 

threads are clean (separate technical data is 
available).

5.  Check the alignment of the upstream and 

downstream pipes and the squareness 
of the pipe flanges.

Actuators

All air line and electrical cable entries should 
be plugged to prevent the ingress of foreign 
material. Actuator cylinders, where not fitted 
to a valve, should be stored with the piston rod 
fully retracted. Internal cylinder components 
should not require any corrosion inhibitor as 
they are assembled with a light coating of 
grease.

SAFETY PRECAUTIONS

Actuated valves are generally operated from 
a remote location.
Caution should be exercised when working in 
close proximity to these valves. The F955/F956 
valves are supplied with upper body shrouds 
and spindle covers for environmental and safety 
purposes.
To ensure the long term operation and safety 
of the valves, the covers and shrouds must be 
maintained at all times.

Spare parts

Seats, cord and packing should be carefully 
stored and protected from sharp edges or 
heavy objects which could damage sealing 
faces.

A) Example of incorrect installation:   

Void area of pipe flange/pipe connection 
does not support seat sufficiently. Fillet weld 
between pipe and flange shown creates this 
void area. Thin walled pipes can also fail to 
support seats. 

B) Example of correct installation: 

The inside diameter of the pipe/flange is 
Schedule 40 pipe inside diameter or less. The 
pipe/flange presents a flat face to the seat.       

TYPICAL VALVE INSTALLATION WITH 

SCHEDULE 40 PIPE SHOWN.

Emerson.com/FinalControl

© 2017 Emerson. All rights reserved.

Отзывы: