background image

Emerson.com/FinalControl

VCIOM-02878-EN 18/12

© 2017 Emerson. All Rights Reserved.

DANGEROUS PRACTICES

Potentially dangerous practices:
• disregarding instructions
• improper use of product
• use of insufficiently qualified personnel.

Application pressure/temperature must not be 
higher than the pressure/temperature limits 
shown on the technical data sheet.

Before installation these instructions must be fully read and understood

KEYSTONE

 FIGURE 221/222 BUTTERFLY VALVES

INSTALLATION AND MAINTENANCE INSTRUCTIONS

INTRODUCTION

The Keystone Figure 221/222 is a rubber lined 
butterfly valve which has a maximum working 
pressure of 16 bar over a temperature range of 
-29°C to +120°C, depending on seat material. 
The Figure 221/222 utilizes a molded seat 
design.

SAFETY RELATED INFORMATION

1.  If in any doubt regarding any aspect of 

Figure 221/222 valves, contact your local 
Emerson sales office for guidance.

2.  Only use properly qualified personnel for 

installation.

3.  Ensure that the pipeline is fully drained 

or vented before removing the valve from 
the pipeline.

4.  Use appropriate protective equipment/

clothing, such as goggles, safety shoes, 
industrial gloves.

5.  This product is not intended for use in areas 

where external fire is a potential hazard.

6.  The piping design must take into account 

the following factors and any other factors 
which are not listed here, but known 
to be relevant to the safe operation of 
the installation.

  6.1  Valve weights which are shown in 

the technical data sheet.

  6.2  Formation of condensate in gas 

pipelines.

  6.3  Elimination of turbulence and vortex 

potential at the valve.

  6.4 Pipeline vibrations.
  6.5  The piping design should preclude 

the occurrence of water hammer at 
the valve.

7.  The valve design has not taken into account 

earthquake loading or traffic vibration.

8.  The normal shelf life of the Figure 221/222 

valve seat is 5 years under clean, dry 
ambient and conditions without UV exposure 
prior to installation.

9.  Tighten all flange bolts as per the 

nominated flange standards using the 
diagonal sequence method.

FLANGE AND PIPELINE COMPATIBILITY

Keystone butterfly valves are designed for 
installation between ANSI Class 125/150 flat or 
raised faced flanges. Gaskets are not required. 
Lined pipe, heavy wall pipe or flanges must 
have a minimum allowable inside diameter at 
the centered body face to clear the disc sealing 
edge when opening the valve.
Weld neck flanges (flange ID approximates 
flange bore) are recommended to ensure 
maximum valve performance; however, slip-on 
flanges may be used.
Do not weld near the valve, as this will result in 
serious damage to the valve.

Содержание Keystone Figure 221 Series

Страница 1: ...here external fire is a potential hazard 6 The piping design must take into account the following factors and any other factors which are not listed here but known to be relevant to the safe operation of the installation 6 1 Valve weights which are shown in the technical data sheet 6 2 Formation of condensate in gas pipelines 6 3 Elimination of turbulence and vortex potential at the valve 6 4 Pipe...

Страница 2: ...the gap between the flanges can accommodate the valve face to face dimension 4 Spread the flanges using suitable tooling such as flange spreaders to enable ease of insertion of the valve between the flanges WARNING Do not use the valve as a lever 5 Open the valve until the disc is free of the seat but still within the valve body about 5 open 6 Loosely insert two or more flange bolts through the ho...

Страница 3: ... valve flange assembly in the pipeline 3 Tack weld the flanges to the pipeline 4 Remove the flange bolts and the valve 5 Finish weld the flanges to the pipeline and allow to cool fully 6 Follow the procedure for installation in an existing system WARNING Do not finish weld the flanges to the pipeline with the valve still assembled to the flanges as this will result in serious damage to the valve s...

Страница 4: ...emove obstruction 3 Open and close the valve several times Operate the valve at least once a month Check the valve seat for deterioration Neither Emerson Emerson Automation Solutions nor any of their affiliated entities assumes responsibility for the selection use or maintenance of any product Responsibility for proper selection use and maintenance of any product remains solely with the purchaser ...