Installation, Operation and Maintenance Manual
MAN-10-04-100-0711-EN Rev. 0
October 2020
33
Actuator Configuration
Section 6: Actuator Configuration
NOTE
During the new stroke limit setup, the minimum range between open and close limit
position has to be at least 45 degree of the valve position; if the above condition is not
respected, the setup will not be successful and stroke limit error alarm will be signalized
(red LED blinking). The red LED will continuously flash when the actuator is in setup
functionality (dip switch SW3 in ‘on’ position) and rotary switches SW4 and SW6 are in
one of the following positions:
a.
SW4=3 and SW6=0
(stroke limit of open configuration by torque)
b.
SW4=2 and SW6=0
(stroke limit of close configuration by torque)
c.
SW4=1 and SW6=0
(stroke limit of open configuration by position)
d.
SW4=0 e SW6=0
(stroke limit of close configuration by position)
The alarm is then reset by:
a.
Switching off and on the actuator
b.
Doing a new correct stroke limit setup in one of the 4 possible combinations.
!
WARNING
In configuration phase, touch only the configuration area of the logic board; don’t touch
the actuator in its other parts.
6.2.8
Stroking Time Selection in Closing
•
Enter set up configuration: move switch SW3 to position ON (configuration function)
•
Move switch SW4 to position 4
•
Move switch SW6 to positions 4, 6, 8 for the requested stroking time according
to the table below
•
Push ENTER pushbutton SW5 to confirm
•
When pushing SW5, the red LED switches on for confirmation
•
The selected stroking time in closing is now set
•
Exit set up configuration (move switch SW3 to position 1) or proceed with
t
he next param
eter