28 • Network Connection to E2
026-1727 Rev 3
8
E2 Setup
The DAC is capable of communicating with an E2
version 3.0 or above.
Using DAC with a central E2 offers several
benefits over simple standalone control, including:
• Reporting of DAC-related alarms in the Alarm
Advisory Log.
• The ability to log DAC inputs in an E2 logging
group.
• The ability to share outside air temperature values
and control motor room temperature by sharing in-
put values between the and the E2.
• Remote access to DAC status and programming
from the E2 front panel.
• The ability to remotely access the DAC from
UltraSite32 or Site Manager, and to back up, restore,
and offline-program DAC configuration along with
E2 site configuration.
Communication between E2 and an DAC takes
place over the RS485 MODBUS. Follow the instruc-
tions in
, to connect
an DAC to the E2 MODBUS network. Then, follow
the instructions in this chapter to set up the DAC.
8.1. Network Connection to E2
Connecting a DAC to an E2 unit requires the E2 to
be version 3.0 or above. Contact Retail Solutions for
upgrade information if the controller is a version prior
to 3.0.
An E2 has up to three COM ports that can be
assigned for MODBUS communication (COM2, an
RS485 port on the E2 power interface board, and
COM4 and COM6, which are optional ports requiring
expansion cards). COM ports can only be used for one
function; in other words, if COM2 is set up as the
MODBUS, you cannot connect MODBUS devices to
COM2. Ensure your E2 is equipped with an RS485
COM Card
(P/N 637-4890)
and configured in E2
General Services (
,
Serial
tab) to
enable COM4 or an E2 Expansion COM Card
(P/N 637-4871)
to enable COM6.
Connect the MODBUS network cable to the three-
terminal connector on the COM port you wish to
assign as MODBUS. Like other DAC connections,
wire RS485+ to RS485+, RS485- to RS485-, and the
shield cable to the middle terminal. If the E2 will be
the first device in the daisy-chain, set the port’s
Figure 8-1
-
Location of E2 COM Ports (E2 Versions 3.xx
and Below)
E2 PIB COM PORT ASSOCIATIONS
COM1
COM4
COM6
COM2
Serial Device
RS485 COM Port
(2 Connectors)
RS485 COM Card
(2 Connectors)
Serial Device
RS232 Port
POWER INTERFACE BOARD
(PIB)
E2 Modem/Expansion
COM Card Mounted
Above PIB
Plug-In
Modem
Card
COM3
E2 Enclosure (Right Side)
RS485
RS232