background image

Type HSR

Installation Sheet

D103075X012
June 2019

Introduction

This manual provides instructions for the installation, 

startup and adjustment of the Type HSR pressure regulator. 

If maintenance is required, refer to the Type HSR 

Instruction Manual, form 5753. To receive a copy of the 

instruction manual, contact your local Sales Office.

Specifications

Maximum Emergency Inlet Pressures

(1)

150 psi / 10.3 bar

Maximum Emergency Outlet (Casing) Pressures

(1)

25 psig / 1.72 bar

Outlet Pressure Ranges

4 to 6 in. w.c / 10 to 15 mbar

6 to 8 in. w.c / 15 to 20 mbar

8 to 10 in. w.c / 20 to 25 mbar

10 to 12.5 in. w.c / 25 to 31 mbar

12.5 to 20 in. w.c / 31 to 50 mbar

20 to 35 in. w.c / 50 to 87 mbar

1.25 to 2.2 psig / 0.09 to 0.15 bar

Temperature Capabilities

(1)

-20 to 160°F / -29 to 71°C

Installation

!

WARNING

Personal injury, equipment damage or 

leakage due to escaping gas or bursting of 

pressure-containing parts might result if these 

regulators are overpressured or installed 

where service conditions could exceed the 

limits for which the regulators were designed, 

or where conditions exceed any ratings of 

the adjacent piping or piping connections. 

To avoid such injury or damage, provide 

pressure-relieving or pressure-limiting 

devices (as required by the appropriate code, 

regulation or standard) to prevent service 

conditions from exceeding those limits.
Additionally, physical damage to a regulator 

could cause personal injury and property 

damage due to escaping gas. To avoid such 

injury and damage, install the regulator in a 

safe location.
A regulator may vent some gas to the 

atmosphere in hazardous or flammable gas 

service, vented gas might accumulate and 

cause personal injury, death or property 

damage due to fire or explosion. Vent a 

regulator in hazardous gas service to a 

remote, safe location away from air intakes or 

any hazardous location. The vent line must be 

protected against condensation or clogging.

Before installing the regulator, check for damage which might 

have occurred in shipment. Also check for dirt or foreign 

matter which may have accumulated in the regulator body 

or in the pipeline. Apply pipe compound to the male threads 

of the pipeline and install the regulator so that the flow is in 

the direction of the arrow cast on the side of the body. The 

diaphragm actuator assembly can be rotated to any position 

relative to the body, in 90° increments. 

Remove the two 

cap screws that hold the body to the actuator in order to 

rotate the diaphragm actuator assembly.

Do not install the regulator in a location where there can be 

excessive water accumulation, such as directly beneath a 

downspout or in an undrained pit.
To obtain the maximum flow capacities or other performance 

characteristics, the length of pipe from the regulator outlet 

to the meter should have no bends and should be the same 

size as the regulator outlet. Replace the regulator if water 

gets into the spring case or the lower casing of the regulator.

CAUTION

You are advised to use new vent piping 

because defective threads on the relief 

vent piping may interfere with the venting 

assembly if the piping obstructs the 

movement of the vent flapper.

On indoor installations, the vent should be piped outside 

the building. Remove the screen from the regulator vent 

connection and connect vent piping from that connection 

to the outdoors. Install a weather and insect resistant 

vent assembly on the outside end of the pipe. Inspect the 

vent opening regularly. On some installations, it may be 

necessary to install the regulator beneath a protective hood. 

The vent should be pointing or sloping down sufficiently 

to allow any condensate to drain. Also check the regulator 

periodically for external or internal corrosion.

Overpressure Protection

!

WARNING

Some type of overpressure protection is 

needed if actual inlet pressure can exceed 

the outlet pressure rating. Overpressuring 

any portion of this equipment may cause 

1.  The pressure/temperature limits in this installation sheet and any applicable standard or 

code limitation should not be exceeded.

Отзывы: