34 • RLDS I&O Manual
6.4. Navigate to the Second Setup Screen
1. From RLDS
System Setup screen 1
select the
SYSTEM
option to go to
System Setup screen 2
.
2. Press the
ESC
key to return to the
System Setup screen 1
.
6.5. Location
This is the name you assign to the RLDS monitor to
identify its location. It may have up to 12
alphanumeric characters.
1. Press the
ENTER
key to adjust the setting.
2. Use the LEFT/RIGHT cursor keys to move
across the entry field and the UP/DOWN
cursor keys to modify the individual
characters.
3. Press
ENTER
to accept the new entry or
ESC
to revert to the previous setting.
6.6. Number of Zones
Installed
IMPORTANT:
DO NOT
change the number of
zones to deactivate unused zones. Changing the
number of installed zones is only necessary when
manifold blocks are added or removed. Go to the
individual zone that you wish to disable and set its
distance to zero.
1. Press the
ENTER
key to adjust the number.
2. Use the UP/DOWN cursor keys to modify the
number (must be 4, 8, 12, or 16).
3. Press
ENTER
to accept the new
number or
ESC
to revert to the previous
setting.
6.7. Alarm Acknowledge
(Ack) - Mode
This function programs the relays in the RLDS unit
for latching or non-latching operation.
1. Press the
ENTER
key to adjust the setting.
2. Use the UP/DOWN cursor keys to toggle
between settings.
AUTO
- Non-latching (Alarm relay will
automatically de-energize when the gas level drops
below its alarm point).
Figure 6-4
- Setup Screen 2
IMPORTANT: Do not change the number
of zones to deactivate unused zones.
Changing the number of installed zones is
only necessary when manifold blocks are
added or removed. Go to the individual zone that
you wish to disable and set its distance to zero.
Содержание GW-810-3760
Страница 1: ...Refrigerant Leak Detection System RLDS Installation and Operation Manual 026 1309 Rev 11 ...
Страница 37: ...30 RLDS I O Manual 026 1309 Rev 11 Figure 4 22 Connecting the Gateway to the RS485 Network ...
Страница 84: ...Appendix B System Menu Map B 79 Appendix B System Menu Map ...
Страница 85: ...B 80 RLDS I O Manual 026 1309 Rev 11 ...