FloBoss 107 Instruction Manual
5-8
Communications
Revised June-2017
The EIA-232 (RS-232) default values are: 19,200 baud rate, 8 bits, 1 stop
bit, no parity, 10 millisecond key-on delay, and 10 millisecond key-off
delay. The maximum baud rate is 115.2 Kbps.
EIA-232 (RS-232) supports the log-on security feature of the FB107 if
you enable the security on the communication port
using ROCLINK 800.
The EIA-232 (RS-232) signals include RX, TX, and RTS signal/control
lines. Light-emitting diodes (LEDs) indicate if the FB107 is transmitting
(TX) or receiving (RX).
Table 5-3. EIA-232 (RS-232) Field Wiring Terminals
Label
Definition
TX
Transmit
data
signals that data is being transmitted from the
comm port
RX
Receive
data signals that data is being received at the comm
port
RTS
Ready to Send signals that the port is ready to transmit
NC
No connection (comm module only)
NC
No connection (comm module only)
GND
Ground (common)
5.6
Liquid Crystal Display (LCD) Touchpad
The FB107 supports an external liquid crystal display (or “Touchpad”).
See
Figure 5-4.
ALARM
KEY ACK
TO ACTIVATE
TOUCH SCREEN
Figure 5-4. Liquid Crystal Display (“Touchpad”)
The FB107 base unit provides connections for the Touchpad (see
Figure
5-5
). The display functions as an EIA-232 (RS-232) communications
device, supporting ROC or Modbus slave communications protocols.