FloBoss 107 Instruction Manual
Revised June-2017
Inputs and Outputs
4-7
Note
:
Once you remove a module, always be sure to replace its cover.
This protects the module slot from dust and prevents damage to
the cover’s locking mechanism.
4.4
Wiring a Module
I/O wiring requirements are site and application dependent. Local, state,
or NEC requirements determine the I/O wiring installation methods.
Direct burial cable, conduit and cable, or overhead cables are options for
I/O wiring installations.
All I/O modules, the CPU I/O assembly, and RTD inputs have terminal
blocks for convenient wiring and servicing. The terminal blocks
accommodate size 16 to 24 AWG.
Caution
Failure to exercise proper electrostatic discharge precautions, such as
wearing a grounded wrist strap may reset the processor or damage
electronic components, resulting in interrupted operations.
To connect the wire to the removable block compression terminals:
1.
Strip ¼ inch of insulation from the wire.
2.
Insert the bare end into the clamp beneath the termination screw.
3.
Tighten the screw, taking care not to over-torque it.
Expose a minimum of bare wire to prevent short circuits. Allow some
slack when making connections to prevent strain.
Note
:
Twisted-pair cable is recommended for I/O signal wiring.
4.5
Selecting the Type of I/O
Caution
Configure all AO/DO points in ROCLINK before connecting any wiring.
Failure to do so may result in physical damage to the I/O board.
Using ROCLINK 800, you select the type of input or output.
1.
Log on to the FB107 using ROCLINK 800.
Note
:
ROCLINK 800 provides an enhanced graphical user interface
(GUI) for the FB107. This interface displays an image of the
FB107 above a tabbed screen (see
Figures 4-4
and
4-5
). You
select the FB107 module and then use the tabbed screen to
configure the components.
2.
Click the
I/O module
. The display immediately under the FB107
image changes to reflect your selection.
Содержание FloBoss 107
Страница 58: ...FloBoss 107 Instruction Manual 3 8 Power Connections Revised June 2017 This page is intentionally left blank ...
Страница 104: ...FloBoss 107 Instruction Manual 5 18 Communications Revised June 2017 This page is intentionally left blank ...