2.6
Startup and Operation
Before starting the FB107, perform the following checks to ensure the
unit is properly installed.
Check the field wiring for proper installation.
Make sure the input power has the correct polarity.
Make sure that the CPU, I/O, MVS, application, and communication
modules are seated in the backplane.
Make sure the input power is fused at the power source. Plug the
input power either into the
AUX PWR IN
on the base unit or into the
connector labeled
PWR+ / PWR
on the CPU module.
2.6.1
Startup
Before you apply power to the FB107, assess the power requirements
(including the base unit, expansion rack, and any installed modules and
peripheral devices) that comprise the total configuration for your FB107.
Refer to
Determining Power Consumption
in
Chapter 3,
Power
Connections
.
Apply power to the FB107. The power input PWR+ LED indicator
should light green to indicate that the applied voltage is correct and a
valid operation is active.
After the start-up diagnostics (RAM and other internal checks) complete,
you should be able to log in to the FB107, which indicates the FB107
completed a valid reset sequence. If you cannot log on to the FB107, refer
to
Chapter 7, Troubleshooting
, for possible causes.
Caution
Check the input power polarity before connecting power to the
FB107. Incorrect polarity can damage the FB107.
When working on units located in a hazardous area (where explosive
gases may be present), make sure the area is in a non-hazardous
state before performing procedures. Performing these procedures in
a hazardous area could result in personal injury or property damage.
2.6.2
Operation
Once startup is successful, it is necessary to configure the FB107 to meet
the requirements of the application. Refer to the
ROCLINK 800
Configuration Software User Manual (for FloBoss 107)
(Form A6217)
for procedures on configuring the FB107 and calibrating its I/O. Once
you configure and calibrate the FB107, you can place it in operation.