Input/Output
Revised August-2017
4.1.1 Selecting the Type of I/O
To select the type of output for the
Analog Output/Discrete Output
#1
channel, flip the AO/DO switch on the termination board to the desired
position. Refer to
Figure 4-1
for the switch location. Then select the
desired output type on the Configure > I/O > Setup screen in ROCLINK
800 configuration software. Analog Output is the default position for
this channel.
To select the type of input for the
Analog Input/Discrete Input
and
Pulse Input/Discrete Input
channels, use the Configure > I/O > Setup
screen in ROCLINK 800 configuration software. The defaults are
Analog Input and Pulse Input.
A
Optional I/O terminal block
B
250-ohm resistor switches
C
AO/DO switch
Figure 4-1. Termination Board with Optional I/O
A
Te
B
Te
C
Te