background image

D103588X014

Installation Guide

English – April 2014

MR98 Series

www.fisherregulators.com

Introduction

This Installation Guide provides instructions for installation, startup 

and adjustment. To receive a copy of the instruction manual, 

contact your local Sales Office or view a copy at 

 

www.fisherregulators.com. For further information refer to 

 

MR98 Series Backpressure Regulators, Relief and Differential 

Relief valves Instruction Manual, D103588X012.

P.E.D. Category

This product may be used as a safety accessory with pressure 

equipment in the following Pressure Equipment Directive 97/23/EC 

categories. It may also be used outside of the Pressure Equipment 

Directive using Sound Engineering Practice (SEP) per table below.

Monel

®

 is a mark owned by Special Metals Corporation.

Hastelloy

®

 C is a mark owned by Haynes International, Inc.

1. The pressure/temperature limits in this Installation Guide and any applicable standard or code limitation should not be exceeded.

2.  The pressure limits given are based on the body size and body materials only. Actual pressure limits of the assembled regulator may decrease and vary depending on the 

temperature, body end connection, diaphragm, seat and/or trim material of the regulator.

3. Fluorocarbon (FKM) is limited to 93°C / 200°F hot water.

Maximum Spring Case Loading Pressure for 

Types MR98LD, MR98HD and MR98HHD (Spring Setting 

Plus Loading Pressure)

(1)(2)

Type MR98LD Spring Case 

Gray Cast Iron:

 3.4 bar / 50 psig

Steel or Stainless Steel:

 8.6 bar / 125 psig

Type MR98HD Spring Case 

Gray Cast Iron:

 17.2 bar / 250 psig

Steel or Stainless Steel:

 20.7 bar / 300 psig

Type MR98HHD Spring Case 

Steel or Stainless Steel:

 20.7 bar / 300 psig

Temperature Capabilities

(1)

 

Elastomer Parts: 

  

Nitrile (NBR) and Neoprene (CR):

 

-40 to 82°C / -40 to 180°F

 

  Fluorocarbon (FKM)

(3)

:

 

-18 to 149°C / 0 to 300°F

 

  Ethylenepropylene (EPDM):

 

-7 to 135°C / 20 to 275°F

 

  Perfluoroelastomer (FFKM):

 -18 to 218°C / 0 to 425°F

 

    Polytetrafluoroethylene (PTFE) Diaphragm protector:

  

-40 to 204°C / -40 to 400°F 

 

Body Materials:

 

  Gray Cast Iron:

 

-29 to 208°C / -20 to 406°F 

 

  WCC Steel:

 -29 to 232°C / -20 to 450°F

 

  LCC Steel:

 

-40 to 232°C / -40 to 450°F

 

  Stainless Steel, Monel

®

 and Hastelloy

®

 C: 

 

  

-40 to 232°C / -40 to 450°F

Pressure Registration

 

Internal or External

Shutoff Classification Per ANSI/FCI 70-3-2004 

Metal Seats: 

Class IV 

PTFE:

 Class IV 

Elastomer Seats:

 Class VI or better

Installation

!

WArNINg

Only qualified personnel shall install or service a 

relief valve or backpressure regulator. relief valve 

or backpressure regulator should be installed, 

operated and maintained in accordance with 

international and applicable codes and regulations 

and Emerson Process Management Regulator 

Technologies, Inc. instructions.

If using a relief valve or backpressure regulator 

on a hazardous or flammable fluid service, 

personal injury and property damage could 

occur due to fire or explosion of vented fluid 

that may have accumulated. To prevent such 

injury or damage, provide piping or tubing to 

vent the fluid to a safe, well-ventilated area 

or containment vessel. Also, when venting a 

hazardous fluid, the piping or tubing should be 

located far enough away from any buildings or 

windows so to not create a further hazard and 

the vent opening should be protected against 

anything that could clog it. 

Personal injury, equipment damage or leakage 

due to escaping fluid or bursting of pressure-

containing parts may result if this relief valve or 

backpressure regulator is overpressured or is 

installed where service conditions could exceed 

TYPE

PRODUCT SIZE

BODY MATErIAL

CATEgOrY

All

1/4 NPT, DN 15 to 25 / 

1/2 to 1-inch

All available 

materials

SEP

MR98H/

MR98HD

DN 40 and 50 / 

1-1/2 and 2-inch

Steel and 

Stainless Steel

II

Specifications 

Available Constructions

 

 Type  MR98L:

 Direct-operated low pressure backpressure 

regulator/relief valve with 0.14 to 2.6 bar / 2 to 38 psig set 

pressure range

  

Type MR98H:

 Direct-operated high pressure backpressure 

regulator/relief valve with 0.34 to 13.8 bar / 5 to 200 psig set 

pressure range

  

Type MR98HH: 

Direct-operated high pressure backpressure/

relief valve with 10.3 to 25.9 bar / 150 to 375 psig set 

pressure range

 

 Type  MR98LD:

 Pressure-loaded low pressure differential 

pressure relief valve with 0.14 to 2.6 bar / 2 to 38 psi set 

pressure range

 

 Type  MR98HD: 

Pressure-loaded high pressure differential 

pressure relief valve with 0.34 to 13.8 bar / 5 to 200 psi set 

pressure range

 

 Type  MR98HHD:

 Pressure-operated high pressure 

backpressure/relief valve with 10.3 to 25.9 bar / 

 

150 to 375 psi differential set pressure range

Body and Orifice Sizes

 

1/4 NPT body: 

7.22 mm / 0.284-inch orifice

 

DN 15 / 1/2-inch body:

 10.56 mm / 0.416-inch orifice

 

 DN 20 and 25 / 3/4 and 1-inch bodies: 

 

16.02 mm / 0.631-inch orifice

  

DN 40 and 50 / 1-1/2 and 2-inch bodies: 

 

29 mm / 1.142-inch orifice

End Connection Styles

 

 NPT, SWE and Welded and Integral CL150 RF, CL300 RF 

and PN 16/25/40 RF; all sizes are fabricated with slip-on 

flanges (for welded end connections) and are EN flanged 

356-mm face-to-face (14-inch face-to-face)

Maximum Inlet and Outlet Pressure Rating

See Table 2

Maximum Cold Working Pressures of Body Size and Materials

(1)(2)

See Table 2

Set Pressure Ranges

(1)

 

See Table 1

Содержание Fisher MR98HD

Страница 1: ... regulator should be installed operated and maintained in accordance with international and applicable codes and regulations and Emerson Process Management Regulator Technologies Inc instructions If using a relief valve or backpressure regulator on a hazardous or flammable fluid service personal injury and property damage could occur due to fire or explosion of vented fluid that may have accumulat...

Страница 2: ... of the spring range or the pressure requested so an initial adjustment may be required to give the desired results With proper installation completed and relief valves properly adjusted slowly open the upstream and downstream shutoff valves if applicable Adjustment To change the control pressure remove closing cap or loosen the jam nut and turn the adjusting screw clockwise to increase control pr...

Страница 3: ...nch bodies 12 required Types MR98H MR98HD MR98HH and MR98HHD 1 4 NPT body 6 required DN 15 to 50 1 2 to 2 inch bodies 8 required 17 Jam Nut 18 Drive Screw 4 required 19 Diaphragm Gasket 2 required for pressure loaded spring case 21 Diaphragm Head 22 Adjusting Screw Assembly 23 Handwheel not shown 24 Machine Screw 25 O ring Retainer 25 Seat Retainer 28 Lockwasher 29 Gasket 31 Locknut 32 Stuffing Bo...

Страница 4: ...ent Regulator Technologies Inc USA Headquarters McKinney Texas 75070 USA Tel 1 800 558 5853 Outside U S 1 972 548 3574 Asia Pacific Singapore 128461 Singapore Tel 65 6770 8337 Europe Bologna 40013 Italy Tel 39 051 419 0611 Chartres 28008 France Tel 33 2 37 33 47 00 Middle East and Africa Dubai United Arab Emirates Tel 971 4811 8100 TESCOM Emerson Process Management Tescom Corporation USA Headquart...