DVC6000f Digital Valve Controllers
December 2009
6-8
Supply Pressure Lo Alert—This alert is active if the
supply pressure exceeds the Supply Pressure Lo
Alert.
Temperature Limit
Temperature Hi Alert—This alert is active if the
temperature is greater than the Temperature Hi Alert
Point.
Temperature Lo Alert—This alert is active if the
temperature is greater than the Temperature Lo Alert
Point.
Travel—If a travel alert is active it will appear
under TRAVEL ALERTS
Travel Deviation
Travel Deviation Alert—This alert is active if the
Travel deviation exceeds the Travel Deviation Alert
Point by more than the Travel Deviation Time.
Travel Limit
Travel Limit Hi Hi Alert—This alert is active if Travel
exceeds the Travel Limit Hi Hi Alert point.
Travel Limit Lo Lo Alert—This alert is active if Travel
is lower than the Travel Limit Lo Lo Alert point.
Travel Hi/Lo
Travel Limit Hi Alert—This alert is active if Travel
exceeds the Travel Limit Hi Alert point.
Travel Limit Lo Alert—This alert is active if Travel is
lower than the Travel Limit Lo Alert point.
Proximity—If a proximity alert is active it will
appear under PROX ALERTS
Travel Open
Travel Open Alert—This alert is active if the travel is
greater than the travel open alert point.
Travel Closed
Travel Closed Alert—This alert is active if the travel
is greater than the travel closed alert point.
Proximity
Proximity Hi Hi Alert—This alert is active if the
Travel is within the detection band set by the Travel Hi
Hi Alert Point and the Travel Hi Hi Deadband.
Proximity Hi Alert—This alert is active if the Travel
is within the detection band set by the Travel Hi Alert
Point and the Travel Hi Deadband.
Proximity Lo Alert—This alert is active if the Travel
is within the detection band set by the Travel Lo Alert
Point and the Travel Lo Deadband.
Proximity Lo Lo Alert—This alert is active if the
Travel is within the detection band set by the Travel Lo
Lo Alert Point and the Travel Lo Lo Deadband.
Travel History Alerts—If a travel history alert is
active it will appear under TVL HIST ALERTS
Cycle Counter
Cycle Counter Alert—This alert is active if the Cycle
Counter exceeds the Cycle Count Alert Point.
Travel Accumulator
Travel Accumulator Alert—This alert is active if the
Travel Accumulator exceeds the Travel Accumulator
Alert Point.
Performance Alerts—if a performance alert is
active it will appear under PERF ALERTS
Performance Critical
Performance Critical Alert—This alert is active if the
instrument is no longer able to control the valve or
performance has been dramatically reduced.
Performance Reduced Alert—This alert is active if
the instrument has detected a reduction in
performance.
Performance Information Alert—This alert is active if
the instrument has detected a condition that may
pertain to control performance.
Status
(TB
>
Device Diagnostics
>
Status )
Self Test Status
Integrator Suspended—The integrator function is
temporarily suspended. The integrator is suspended if
any of the following conditions are met:
The setpoint and actual travel are greater than
98% or less than 2%.
The set point is in cutoff
The Transducer block is Out of Service (OOS)
Integrator Limited Lo—Indicates the integrator reached
its limit and cannot move the valve any further. High
valve friction may cause this situation.
Integrator Limited Hi—Indicates the integrator reached
its limit and cannot move the valve any further. High
valve friction may cause this situation.
Travel Sensor Span Error—Indicates that span
between the endpoints of travel are not far enough
apart. This error is reported during automatic
calibration.
MLFB Error—Indicates that the Minor Loop Feedback
sensor gave a non-valid value during automatic
calibration.
Travel Sensor Hi Error—Indicates the travel sensor
has reported a travel position that is significantly
above the normal operating range, and has failed.
Travel Sensor Lo Error—Indicates the travel sensor
has reported a travel position that is significantly below
the normal operating range, and has failed.
6
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...