DVC6000f Digital Valve Controllers
December 2009
4-90
Table 4-31. PID Function Block System Parameters Definitions (Continued)
Label
PARAMETER_NAME
Description
Initial Value
Range
Block
Mode
RO /
RW
Index
Number
Output Scale
OUT_SCALE
11
OOS
EU at 100%
EU at 0%t
Units index
Decimal
Point
100
0
%
2
Data Type: DS-68
The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with OUT.
Grant Deny
GRANT_DENY
12
Data Type: DS-70
Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block. Not used by the
device.
GRANT: 0=N/A, 1=granted
DENY: 0 = N/A, 1= denied
GRANT
12.1
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
DENY
12.2
ALL
0: Program
1: Tune
2: Alarm
3: Local
All bits: 0
Control Options
CONTROL_OPTS
13
OOS
0: Bypass Enable
1: SP tracks PV in MAN
2: SP tracks PV in ROUT
3: SP tracks PV in LO or
MAN
4: SP tracks RCAS or CAS
in IMAN, LO, MAN or
ROUT
5: Direct Acting
7: Track Enable
8: Track in Manual
9: Use PV for BKCAL_OUT
10: Act on IR
12: Restrict SP to limits in
Cas and RCas
13: No output limits in MAN
All bits: 0
Data Type: Bit String
0=disable
1=enable
Allows you to specify control strategy options.
Status Options
STATUS_OPTS
14
OOS
0: IFS (Initiate Fault State)
if BAD IN
1: IFS if BAD CAS_IN
2: Use Uncertain as Good
5: Target to MAN if BAD IN
All bits: 0
Data Type: Bit String
0=disable
1=enable
Allows you to select options for status handling
and processing.
Input
IN
15
ALL
Status
BAD:
NC:
const
Data Type: DS-65
The primary input value of the block.
Value
0
Process Value Filter Time
PV_FTIME
16
ALL
Positive
0
Data Type: Float
The time constant of the first
−
order PV filter. It is
the time, in seconds, required for a 63 percent
change in the IN value.
Bypass
BYPASS
17
MAN
OOS
1=Off
2=On
0=undefined
Data Type: Enum
Used to override the calculation of the block.
When enabled, the SP is sent directly to the
output.
Cascade Input
CAS_IN
18
ALL
Status
BAD
NC:
const
Data Type: DS-65
The setpoint value from another block.
Value
0
Setpoint Rate Down
SP_RATE_DN
19
ALL
Positive
+ INF
Data Type: Float
Ramp rate for downward SP changes. When the
ramp rate is set to zero, the SP is used
immediately. PV per second
Setpoint Rate UP
SP_RATE_UP
20
ALL
Positive
+ INF
Data Type: Float
Ramp rate for upward SP changes. When the
ramp rate is set to zero, the SP is used
immediately. PV per second
Setpoint High Limit
SP_HI_LIM
21
ALL
PV Scale +/
−
10%, must be
greater than SP_LO_LIM
100
Data Type: Float
The highest SP value allowed.
Setpoint Low Limit
SP_LO_LIM
22
ALL
PV Scale
+/
−
10%, must be less than
SP_HI_LIM
0
Data Type: Float
The lowest SP value allowed.
−
Continued
−
4
Содержание Fisher FIELDVUE DVC6000f
Страница 54: ...DVC6000f Digital Valve Controllers December 2009 2 30 2 ...
Страница 62: ...DVC6000f Digital Valve Controllers December 2009 4 2 4 ...
Страница 127: ...Transducer Block December 2009 4 67 4 ...
Страница 141: ...AO Function Block December 2009 4 81 4 ...
Страница 207: ...MAI Function Block December 2009 4 147 4 ...
Страница 219: ...DO Function Block December 2009 4 159 4 ...
Страница 231: ...DI Function Block December 2009 4 171 4 ...
Страница 232: ...DVC6000f Digital Valve Controllers December 2009 4 172 Block Parameter Index 4 173 Block Channel Index 4 186 4 ...
Страница 302: ...DVC6000f Digital Valve Controllers December 2009 8 16 8 ...
Страница 303: ...Principle of Operation December 2009 A 1 A A Appendix A Principle of Operation Digital Valve Controller Operation A 2 A ...
Страница 306: ...DVC6000f Digital Valve Controllers December 2009 A 4 A ...
Страница 350: ...DVC6000f Digital Valve Controllers December 2009 E 6 E ...
Страница 368: ...DVC6000f Digital Valve Controllers December 2009 F 18 F ...
Страница 372: ...DVC6000f Digital Valve Controllers December 2009 Glossary 4 Notes G Glossary ...
Страница 382: ...DVC6000f Digital Valve Controllers December 2009 Index 10 F Index ...
Страница 383: ...This page intentionally left blank ...